The optimal passive filters to minimize voltage harmonic distortion at a load bus

被引:20
|
作者
Zobaa, AF [1 ]
机构
[1] Cairo Univ, Fac Engn, Elect Power & Machines Dept, Giza 12613, Egypt
关键词
harmonics; power factor; reactive power optimization;
D O I
10.1109/TPWRD.2004.838458
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A method is presented for finding the optimum fixed inductance-capacitance combination to minimize voltage harmonic distortion at a load bus where it is desired to maintain the displacement power factor at a desired level constraining the compensator values, which would create resonance conditions, and the manufacturers' standard values for power shunt capacitors according to IEEE Standard 18-2002. A comparison study of using the constraint, holding either the displacement power factor or the power factor at a desired value, is done. Finally, the contribution of the newly developed method is demonstrated in six examples taken from existing publications.
引用
收藏
页码:1592 / 1597
页数:6