Experimental evaluation of a cooling radiant wall coupled to a ground heat exchanger

被引:37
|
作者
Romani, Joaquim [1 ]
Perez, Gabriel [1 ]
de Gracia, Alvaro [2 ]
机构
[1] Univ Lleida, GREA Innovacio Concurrent, Edifici CREA,Pere de Cabrera S-N, Lleida 25001, Spain
[2] Univ Rovira & Virgili, Dept Engn Mecan, Ave Paisos Catalans 26, E-43007 Tarragona, Spain
关键词
TABS; Radiant walls; Radiant cooling; Ground heat exchanger; EMBEDDED BUILDING ENVELOPE; PERFORMANCE EVALUATION; SYSTEMS; ENERGY; EFFICIENCY; MODEL;
D O I
10.1016/j.enbuild.2016.08.028
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A building prototype was built in the experimental set-up located in Puigverd de Lleida (Spain) to study the energy performance of a radiant wall with ventilated, facade cooled with a ground coupled heat exchanger. The installed geothermal heat pump operates only as a ground coupled beat exchanger on cooling mode, thus providing free-cooling. In this case, only the circulation pumps consume power. The summer experimental campaign showed the energy savings potential and the peak load shifting ability of the system. On continuous operation and taking as reference a cubicle equipped with a conventional air-to-air heat pump, the radiant wall cooled with the ground coupled heat-exchanger achieved savings up to 54.17% and 82.08% at set-point temperatures of 24 degrees C and 26 degrees C, respectively. The thermal storage capacity of the system was studied in night charging test, when the cubicles were pre-cooled during night-time. During the day, the temperature raise caused by heat loads was small and the system kept the temperature inside comfort range despite it only operated overnight. However, the performance was very sensitive to set-point temperature. Free-cooling was limited by the temperatures in the boreholes, showing that with lower set-points the gradient between supply temperature and room temperature was small, and thus it required a higher water flow to achieve the necessary cooling power. Intermittent operation of the system according to different schedules also affected the radiant walls performance as they interacted with the thermal inertia of the system, which could even have a negative impact on energy use. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:484 / 490
页数:7
相关论文
共 50 条
  • [31] Experimental validation of a ground heat exchanger model in a hybrid ground source heat pump
    Pertzborn, Amanda
    Hackel, Scott
    Nellis, Greg
    Klein, Sanford
    [J]. HVAC&R RESEARCH, 2011, 17 (06): : 1101 - 1114
  • [32] Adaptation of adsorption cooling system for hot and dry climates: Use of ground water heat exchanger coupled to direct evaporative cooling tower
    Kheireddine, Mohamed-Abdelbassit
    Benchabane, Adel
    Rouag, Amar
    Mahbubul, I. M.
    Arici, Muslum
    Demir, Hakan
    Sevindir, Mustafa Kemal
    [J]. ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2023, 45 (03) : 9133 - 9148
  • [33] Experimental investigation on the ground heat exchanger with air fluid
    Durmaz, U.
    Yalcinkaya, O.
    [J]. INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2019, 16 (09) : 5213 - 5218
  • [34] An experimental study on the thermal performance of ground heat exchanger
    Lim, Kyoungbin
    Lee, Sanghoon
    Lee, Changhee
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2007, 31 (08) : 985 - 990
  • [35] Numerical modeling of a simplified ground heat exchanger coupled with sandbox
    Li, Wenxin
    Dong, Jingliang
    Wang, Yong
    Tu, Jiyuan
    [J]. 1ST INTERNATIONAL CONFERENCE ON ENERGY AND POWER, ICEP2016, 2017, 110 : 365 - 370
  • [36] Experimental investigation on the ground heat exchanger with air fluid
    U. Durmaz
    O. Yalcinkaya
    [J]. International Journal of Environmental Science and Technology, 2019, 16 : 5213 - 5218
  • [37] EVALUATION OF A PLATE HEAT EXCHANGER FOR ACETIC ACID COOLING
    Perez Sanchez, A.
    Perez Sanchez, E. J.
    Ranero Gonzalez, E.
    [J]. NEXO REVISTA CIENTIFICA, 2020, 33 (01): : 1 - 21
  • [38] Heat transfer characteristics of a composite radiant wall under cooling/heating conditions
    Qin, S. Y.
    Wang, Y. A.
    Gao, S.
    Xu, D. G.
    Cui, X.
    Zhao, M.
    Jin, L. W.
    [J]. INDOOR AND BUILT ENVIRONMENT, 2020, 29 (08) : 1155 - 1168
  • [39] Ground-coupled heat pump system with a buried underfloor heat exchanger
    Den Braven, Karen R.
    Drown, David C.
    [J]. American Society of Mechanical Engineers, Advanced Energy Systems Division (Publication) AES, 1992, 28 : 97 - 101
  • [40] Experimental evaluation of coupled heat and mass transfer in geothermal water cooling tower
    [J]. 2ND INTERNATIONAL CONFERENCE ON ENGINEERING SCIENCES, 2018, 433