Thermal performance of a pump-driven loop heat pipe as an air-to-air energy recovery device

被引:27
|
作者
Zhou, Feng [1 ]
Duan, Wei [1 ]
Ma, Guoyuan [1 ]
机构
[1] Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Pump; Loop heat pipe; Energy recovery; Refrigerant; Mass flow rate; COOLING LOOP; DATA CENTERS; SYSTEM; EXCHANGERS;
D O I
10.1016/j.enbuild.2017.06.057
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A pump-driven loop heat pipe (PLHP) was proposed for energy recovery from exhaust air to reduce fresh air handling energy consumption of air conditioning systems. The influences of working fluid, mass flow rate, heat exchanging area and facing air velocity on heat transfer capacity, temperature effectiveness and coefficient of performance (COP) were studied experimentally under different working conditions. The optimum working fluid and value were obtained, respectively. Results indicate that the heat transfer capacity and COP increase with the temperature difference between indoor and outdoor air while the temperature effectiveness decreases. The general performance for R32 as working fluid was better than R22 and R152a. For summer condition, the heat transfer capacity was 4.09 kW and the COP was 9.26 when the mass flow rate was 250 kg h(-1), the heat exchanging area was 58.0 m(2) and the facing air velocity was 1.8 ms(-1). For winter condition, the heat transfer capacity was 6.63 kW and the COP was 14.20 while the mass flow rate was 300 kg h(-1), the heat exchanging area was 58.0 m(2) and the facing air velocity was 1.8 m s(-1). The tested device could meet the energy recovery need with remarkable energy savings. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:206 / 216
页数:11
相关论文
共 50 条
  • [1] Thermal performance of a multi-loop pump-driven heat pipe as an energy recovery ventilator for buildings
    Zhou, Feng
    Duan, Wei
    Ma, Guoyuan
    APPLIED THERMAL ENGINEERING, 2018, 138 : 648 - 656
  • [2] SIMULATION RESEARCH ON HEAT RECOVERY SYSTEM OF HEAT PUMP COMPOSITE PUMP-DRIVEN LOOP HEAT PIPE
    Liu, Shuailing
    Ma, Guoyuan
    Jia, Xiaoya
    Xu, Shuxue
    Wu, Guoqiang
    THERMAL SCIENCE, 2022, 26 (05): : 4301 - 4313
  • [3] Experimental study of ventilation system with heat recovery integrated by pump-driven loop heat pipe and heat pump
    Liu, Shuailing
    Ma, Guoyuan
    Xu, Shuxue
    Jia, Xiaoya
    Wu, Guoqiang
    JOURNAL OF BUILDING ENGINEERING, 2022, 52
  • [4] Thermodynamic performance analysis of air-to-air hybrid heat recovery unit driven by pump combined with booster
    Zhou, Feng
    Li, Dongzhe
    Chen, Rong
    Ma, Guoyuan
    JOURNAL OF BUILDING ENGINEERING, 2023, 77
  • [5] Air-to-air energy recovery heat exchangers
    Dieckmann, J
    Roth, KW
    Brodrick, J
    ASHRAE JOURNAL, 2003, 45 (08) : 57 - 58
  • [7] Performance evaluation of a compact air-to-air heat pump
    Kent, EF
    ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (04) : 341 - 345
  • [8] Performance of a heat recovery ventilator coupled with an air-to-air heat pump for residential suites in Canadian cities
    Li, Bo
    Wild, Peter
    Rowe, Andrew
    JOURNAL OF BUILDING ENGINEERING, 2019, 21 : 343 - 354
  • [9] Air-to-air energy recovery
    Besant, RW
    Simonson, CJ
    ASHRAE JOURNAL, 2000, 42 (05) : 31 - +
  • [10] FACTORS AFFECTING PERFORMANCE OF A RESIDENTIAL AIR-TO-AIR HEAT PUMP
    PARKEN, WH
    BEAUSOLIEL, RW
    KELLY, GE
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1976, 18 (12): : 43 - 44