Experimental and numerical investigation of natural convection in a double skin facade

被引:28
|
作者
Inan, Tugba [1 ]
Basaran, Tahsin [1 ]
Ezan, Mehmet Akif [2 ]
机构
[1] Izmir Inst Technol, Dept Architecture, TR-35430 Izmir, Turkey
[2] Dokuz Eylul Univ, Dept Mech Engn, TR-35397 Izmir, Turkey
关键词
Natural convection; Double skin facade; Differentially heated cavity; Closed cavity; FILLED SQUARE CAVITY; HEAT-TRANSFER; AIR-FLOW;
D O I
10.1016/j.applthermaleng.2016.06.124
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, airflow and heat transfer in a rectangular cavity that simulates a double skin facade and includes natural convection were examined numerically and experimentally. This cavity separates the exterior space and the thermally controlled interior space. The temperatures of the surfaces that interact with these spaces were determined experimentally, while the other surfaces were regarded as adiabatic. With these temperature values, the parameters of the numerical study were defined. After the validation of the numerical model was completed based on experimental studies in the literature, the results related to flow and heat transfer in the cavity were analyzed. The numerical model provided results that agree with the air temperature values found experimentally in the cavity. Accordingly, in natural convection, with Rayleigh numbers ranging from 8.59 * 10(9) to 1.41 * 10(10) and the effect of buoyancy on the regions close to the surface, the increasing tendency of the average Nusselt number from 142.6 to 168.8 was shown. In addition, a correlation between the Rayleigh and Nusselt numbers for a cavity aspect ratio of 8.64 was constructed to evaluate the heat flux; this correlation was also shown graphically. (C) 2016 Elsevier Ltd. All rights reserved.
引用
下载
收藏
页码:1225 / 1235
页数:11
相关论文
共 50 条
  • [41] NUMERICAL STUDIES ON SMOKE SPREAD IN THE CAVITY OF A DOUBLE-SKIN FACADE
    Ji, Jie
    Li, Yi Fan
    Shi, Wen Xi
    Sun, Jin Hua
    JOURNAL OF CIVIL ENGINEERING AND MANAGEMENT, 2016, 22 (04) : 470 - 479
  • [42] Numerical investigation of developing natural convection in vertical double-passage porous annuli
    Girish N.
    Makinde O.D.
    Sankar M.
    Defect and Diffusion Forum, 2018, 387 : 442 - 460
  • [43] Natural ventilation performance of a double-skin facade with a solar chimney
    Ding, WT
    Hasemi, YJ
    Yamada, T
    ENERGY AND BUILDINGS, 2005, 37 (04) : 411 - 418
  • [44] Numerical investigation on the natural convection of liquid gallium
    Men, Yu-Bin
    Ma, Jun-Jun
    Wang, Shu-Fu
    Peng, Wen-Gen
    Liu, Yuan-Chun
    He, Yu-Rong
    Harbin Gongye Daxue Xuebao/Journal of Harbin Institute of Technology, 2011, 43 (01): : 114 - 118
  • [46] Concrete solar collectors for facade integration: An experimental and numerical investigation
    O'Hegarty, Richard
    Kinnane, Oliver
    McCormack, Sarah J.
    APPLIED ENERGY, 2017, 206 : 1040 - 1061
  • [47] Experimental Research and Numerical Simulation of Natural Convection
    Jia, Zhiqiang
    Wang, Qite
    Feng, Yanghe
    Huang, Honglan
    Huang, Jincai
    Huang, Kuihua
    PROCEEDINGS OF INTERNATIONAL CONFERENCE ON ROBOTICS, CONTROL AND AUTOMATION ENGINEERING (RAE 2018) AND INTERNATIONAL CONFERENCE ON ADVANCED MECHANICAL AND ELECTRICAL ENGINEERING (AMEE 2018), 2018, : 137 - 141
  • [48] Effect of inclination angle of the adiabatic wall in asymmetrically heated channel on natural convection: Application to double-skin facade design
    Kimouche, Nedjmeddine
    Mahri, Zinelabidine
    Abidi-Saad, Aissa
    Popa, Catalin
    Polidori, Guillaume
    Maalouf, Chadi
    JOURNAL OF BUILDING ENGINEERING, 2017, 12 : 171 - 177
  • [49] Experimential investigation of optical properties of double skin facade shading louvers
    Chen, Youming (ymchen@hnu.com), 1600, Science Press (38):
  • [50] NUMERICAL AND EXPERIMENTAL INVESTIGATION OF UNSTEADY NATURAL CONVECTION IN A VERTICAL OPEN-ENDED CHANNEL
    Lau, G. E.
    Timchenko, V.
    Menezo, C.
    Giroux-Julien, S.
    Fossa, M.
    Sanvicente, E.
    Reizes, J.
    Yeoh, G. H.
    COMPUTATIONAL THERMAL SCIENCES, 2012, 4 (05): : 443 - 456