Leak location in pipelines using the impulse response function

被引:55
|
作者
Lee, Pedro J.
Vitkovsky, John P.
Lambert, Martin F.
Simpson, Angus R.
Liggett, James
机构
[1] Univ Canterbury, Dept Civil Engn, Christchurch, New Zealand
[2] Queensland Govt, Nat Resources & Water, Water Assess Grp, Indooroopilly, Qld 4068, Australia
[3] Univ Adelaide, Sch Civil & Environm Engn, Adelaide, SA 5005, Australia
关键词
leakage; frequency response; linear systems; transients; water pipelines;
D O I
10.1080/00221686.2007.9521800
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Current transient-based leak detection methods for pipeline systems often rely on a good understanding of the system-including unsteady friction, pipe roughness, precise geometry and micro considerations such as minor offtakes-in the absence of leaks. Such knowledge constitutes a very high hurdle and, even if known, may be impossible to include in the mathematical equations governing system behavior. An alternative is to test the leak-free system to find precise behavior, obviously a problem if the system is not known to be free of leaks. The leak-free response can be used as a benchmark to compare with behavior of the leaking system. As an alternative, this paper uses the impulse response function (IRF) as a means of leak detection. The IRF provides a unique a relationship between an injected transient event and a measured pressure response from a pipeline. This relationship is based on the physical characteristics of the system and is useful in determining its integrity. Transient responses of completely different shapes can be directly compared using the IRE The IRF refines all system reflections to sharp pulses, thus promoting greater accuracy in leak location, and allowing leak reflections to be detected without a leak-free benchmark, even when complex signals such as pseudo-random binary signals are injected into the system. Additionally, the IRF approach can be used to improve existing leak detection methods. In experimental tests at the University of Adelaide the IRF approach was able to detect and locate leaks accurately.
引用
收藏
页码:643 / 652
页数:10
相关论文
共 50 条
  • [11] System Response Function-Based Leak Detection in Viscoelastic Pipelines
    Duan, Huan-Feng
    Lee, Pedro J.
    Ghidaoui, Mohamed S.
    Tung, Yeou-Koung
    JOURNAL OF HYDRAULIC ENGINEERING, 2012, 138 (02) : 143 - 153
  • [12] Location Estimation Method of Steam Leak in Pipelines Using Leakage Area Analysis
    Kim, Se-Oh
    Jeon, Hyeong-Seop
    Son, Ki-Sung
    Park, Jong Won
    JOURNAL OF THE KOREAN SOCIETY FOR NONDESTRUCTIVE TESTING, 2016, 36 (05) : 384 - 390
  • [13] Method and instrument for water pipelines leak detection and location
    Tang, Xiujia
    Shuili Xuebao/Journal of Hydraulic Engineering, (09): : 19 - 27
  • [14] New work in acoustic leak location in underground pipelines
    Clark, MA
    Roberts, R
    Rewerts, LE
    REVIEW OF PROGRESS IN QUANTITATIVE NONDESTRUCTIVE EVALUATION, VOLS 15A AND 15B, 1996, 15 : 1853 - 1857
  • [15] Prediction of the probabilistic water leak location in underground pipelines using Monte Carlo simulation
    Proenca, Matheus
    Paschoalini, Amarildo T.
    Obata, Daniel H. S.
    WATER PRACTICE AND TECHNOLOGY, 2023, 18 (03) : 522 - 535
  • [16] LEAK DETECTION, TIMING, LOCATION AND SIZING IN GAS-PIPELINES
    TURNER, WJ
    MUDFORD, NR
    MATHEMATICAL AND COMPUTER MODELLING, 1988, 10 (08) : 609 - 627
  • [17] A liquid leak location gradient-type method for pipelines
    Sobczak, R
    PRZEMYSL CHEMICZNY, 2002, 81 (10): : 651 - 655
  • [18] RESEARCH OF LEAK DETECTION AND LOCATION METHOD FOR HEAT OIL PIPELINES
    Zhang Laibin
    Chen Zhigang
    Liang Wei
    Wang Mingda
    IPC2008: PROCEEDINGS OF THE ASME INTERNATIONAL PIPELINE CONFERENCE - 2008, VOL 1, 2009, : 469 - 474
  • [19] A novel hybrid technique for leak detection and location in straight pipelines
    Zhang, Tiantian
    Tan, Yufei
    Zhang, Xuedan
    Zhao, Jinhui
    JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2015, 35 : 157 - 168
  • [20] Leak detection in pipelines by frequency response method
    Sattar, Ahmed M.
    Chaudhry, M. Hanif
    JOURNAL OF HYDRAULIC RESEARCH, 2008, 46 (SUPPL. 1) : 138 - 151