Single-Pole Ground Fault Location Method for Multi-terminal Flexible DC Transmission Lines Based on LSSVM

被引:0
|
作者
Wei, Ke [1 ]
Lan, Sheng [1 ]
Li, Zhichuan [1 ]
机构
[1] Fuzhou Univ, Coll Elect Engn & Automat, Fuzhou, Peoples R China
关键词
multi-terminal flexible DC power grid; fault location; Pearson correlation coefficient; least squares support vector machine;
D O I
10.1109/ICPES56491.2022.10072468
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In order to ensure the safe and stable operation of multi-terminal flexible DC system and improve the accuracy of single-pole grounding fault location of transmission lines. This paper proposes a single-pole grounding fault location method based on Least Squares Support Vector Machine (LSSVM). When the ground fault occurs, the line mode voltage of different sections in series is combined with the classification mechanism of least squares support vector machine to identify the fault section. Then, the frequency domain characteristics of the line mode voltage in this section are extracted by wavelet packet decomposition combined with Pearson correlation coefficient, and the LSSVM model is established based on the characteristic results to realize fault location. The sparrow search algorithm is used to optimize the parameters of LSSVM model. This paper established +/- 500kV four-terminal flexible DC simulation model for testing. The results show that the method has good anti-transition resistance ability, and the location error is within 0.37 km at the sampling frequency of 50 kHz.
引用
收藏
页码:214 / 218
页数:5
相关论文
共 50 条
  • [31] Parameter fitting-based traveling wave fault location method for multi-terminal DC grids
    Liu, Le
    Xie, Fan
    Kang, Xiaoning
    Hao, Zhiguo
    Lekic, Aleksandra
    Popov, Marjan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2025, 164
  • [32] NEW CONTROL METHOD FOR MULTI-TERMINAL DC TRANSMISSION
    NOZARI, F
    CARROLL, DP
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (02): : 619 - 627
  • [33] Similarity Comparison Based Single-pole Grounding Fault Protection for Lines in Ring-shaped Flexible DC Distribution Network
    Dai Z.
    Liu X.
    Huang M.
    Lu H.
    Liu Y.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (23): : 107 - 115
  • [34] Single-pole Grounding Line Selection Scheme for Multi-terminal Flexible DC System Based on the Ratio of Positive and Negative Current Wavelet Noise Reduction Residual Sum
    Xia F.
    Qin W.
    Chen W.
    Shangguan X.
    Niu Y.
    Zuo P.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (03): : 1032 - 1041
  • [35] Multi-terminal medium voltage DC grids fault location and isolation
    Monadi, Mehdi
    Koch-Ciobotaru, Cosmin
    Luna, Alvaro
    Ignacio Candela, Jose
    Rodriguez, Pedro
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (14) : 3517 - 3528
  • [36] Multi-terminal Flexible DC control and protection cooperation based on fault current limiting
    Xue, Shimin
    Zhang, Haoming
    Liu, Baibing
    Zhang, Junting
    Yin, Wenxiang
    Li, Botong
    Electric Power Systems Research, 2025, 245
  • [37] Fault Location for Multi-Terminal Tapped Lines using Synchronized Measurements
    George, Neethu
    Naidu, O. D.
    Srivastava, Sachin
    Sai, A. V. S. S. R.
    2018 IEEE RECENT ADVANCES IN INTELLIGENT COMPUTATIONAL SYSTEMS (RAICS), 2018, : 153 - 158
  • [38] DC fault location in multi-terminal DC distribution network based on voltage similar triangle principle
    Yang, Yachao
    Huang, Chun
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 184
  • [39] Fault Analysis of Multi-terminal Flexible DC Distribution System With RES
    Dai, Zhihui
    Zhang, Cheng
    Chen, Xi
    Li, Yong
    2018 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2018,
  • [40] A single terminal fault location method for a DC transmission line based on circuit breaker reclosing
    Zhao G.
    Jia K.
    Chen J.
    Chen M.
    Bi T.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (07): : 48 - 56