A methodology for the performance evaluation of an experimental desiccant cooling system

被引:20
|
作者
Çarpinlioglu, MO
Yildirim, M
机构
[1] Univ Gaziantep, Fac Engn, Dept Mech Engn, TR-27310 Gaziantep, Turkey
[2] HVAC Ind, Gaziantep, Turkey
关键词
desiccant cooling system (DCS); desiccant wheel (DW); coefficient of performance (COP); cooling capacity (CC); regeneration temperature (T-R); system performance parameter (PP);
D O I
10.1016/j.icheatmasstransfer.2005.07.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental investigation was conducted in an open cycle desiccant cooling system (DCS) operating on the ventilation mode in the laboratory site [M. Yildirim, An experimental investigation on heat and mass transfer in a desiccant cooling system, PhD thesis, Gaziantep University, Turkey (2002). [1]]. Although the operation of DCS is presumably affected by the design of primary components of rotary regenerator (RR) and desiccant wheel (DW) the methodology used in the analysis of experimental data is presented in this paper to set a different approach for the performance evaluation of similar systems. The rotational speeds of RR and DW (N-RR and N-DW), air mass flow rate (M-a) in process and regeneration lines, and the regeneration temperature (T-R) were defined as operation parameters. Meanwhile coefficient of performance (COP) and cooling capacity (CC) of the system were called as the performance parameters. The system operation with a variety of experimental conditions resulted in an extensive data set covering the ranges of N-RR, N-DW, m(a) and T-R as 5 rpm <= N-RR <= 20 rpm, 0.1 rpm <= N-DW <= 0.4 rpm, 0.05 kg/s <= m(a)0.139 kg/s and 60 degrees C <= T-R <= 90 degrees C, respectively. The interactive influence of the operation parameters was determined through the realization of the psychrometric cycle in deviation from an ideal cycle. A dimensional analysis based on a trial and error procedure was followed to determine the functional relationship of COP and CC. The proposed correlations between COP and CC and the introduced system performance parameter (PP) were determined to be a sole function of m(a) independent of N-RR, N-DW and T-R in their covered ranges. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1400 / 1410
页数:11
相关论文
共 50 条
  • [42] DESICCANT DEGRADATION IN DESICCANT COOLING SYSTEMS - A SYSTEM STUDY
    PESARAN, AA
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1993, 115 (04): : 237 - 240
  • [43] DESICCANT DEGRADATION IN DESICCANT COOLING SYSTEMS - AN EXPERIMENTAL-STUDY
    PESARAN, AA
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1993, 115 (04): : 212 - 219
  • [44] Performance analysis of desiccant cooling system using polyacrylic acid sodium salt desiccant wheel
    Belguith, Sarra
    Meddeb, Zina
    Ben Slama, Romdhane
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2021, 27 (10) : 1368 - 1380
  • [45] Experimental Study on Effectiveness of Celdek Packed Liquid Desiccant Cooling System
    Kumar, Rakesh
    Asati, Arun Kumar
    HEAT TRANSFER ENGINEERING, 2018, 39 (10) : 914 - 922
  • [46] Experimental study on a two-stage rotary desiccant cooling system
    Ge, T. S.
    Li, Y.
    Wang, R. Z.
    Dai, Y. J.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (03): : 498 - 508
  • [47] Performance analysis of a solid desiccant cooling system for a residential air conditioning system
    Lee, Yulho
    Park, Sungjin
    Kang, Sanggyu
    APPLIED THERMAL ENGINEERING, 2021, 182
  • [48] Performance evaluation of a solar powered solid desiccant evaporative cooling system with different recirculation air ratios
    Lai, Lanbo
    Wang, Xiaolin
    Kefayati, Gholamreza
    Hu, Eric
    ENERGY AND BUILDINGS, 2022, 270
  • [49] Energy performance evaluation of a demo solar desiccant cooling system with heat recovery for the regeneration of the adsorption material
    Beccali, Marco
    Finocchiaro, Pietro
    Nocke, Bettina
    RENEWABLE ENERGY, 2012, 44 : 40 - 52
  • [50] Experimental study of an ultrasonic regenerative evaporative cooler for a desiccant cooling system
    Arun, B. S.
    Mariappan, V.
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2019, 40 (02): : 151 - 175