Fault Identification for Circuit Breakers Based on Vibration Measurements

被引:31
|
作者
Yang, Qiuyu [1 ]
Ruan, Jiangjun [1 ]
Zhuang, Zhijian [2 ]
Huang, Daochun [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Peoples R China
[2] PPMV Technol Ctr ABB China Ltd, Xiamen 361006, Peoples R China
关键词
Circuit breaker (CB) testing; fault detection; field application; maintenance; vibration analysis; EMPIRICAL MODE DECOMPOSITION; HILBERT-HUANG TRANSFORM; SIGNAL ANALYSIS; DIAGNOSIS;
D O I
10.1109/TIM.2019.2946470
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Mechanical condition assessment of circuit breakers (CBs) in the power system, if correctly applied, can make an optimal decision on whether, where, and how to perform maintenance. This article presents a new approach to the detection and identification of CB's mechanical states, using its vibration data during switching operations. The morphological correlation coefficient (MCC), which can detect whether or not a fault is present in a CB, is introduced first. Then, a quantitative methodology to specify the specific fault type of the CB, i.e., the ensemble empirical mode decomposition (EEMD)-Hilbert marginal spectrum energy entropy (HMSEE), combined with a classifier [e.g., support vector machine (SVM)], is proposed. By using this approach, the mechanical condition of CBs can be reliably estimated. Some typical mechanical faults of a 12-kV vacuum CB were simulated in the test laboratory to evaluate the effectiveness of the proposed approach. The application in two field cases demonstrates the applicability of the proposed approach.
引用
收藏
页码:4154 / 4164
页数:11
相关论文
共 50 条
  • [12] Research on the Mechanical Fault Diagnosis Method for Circuit Breakers Based on KFCM
    Xia, Xiaofei
    Lu, Yufeng
    Su, Yi
    Yang, Jian
    2020 6TH INTERNATIONAL CONFERENCE ON ENERGY MATERIALS AND ENVIRONMENT ENGINEERING, 2020, 508
  • [13] Research on Mechanical Fault Diagnosis of Circuit Breakers Based on Hybrid Features
    Yao Y.
    Lin J.
    Liu H.
    Xiao H.
    Li Q.
    Wang Z.
    Ma S.
    Zhao Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (21): : 6439 - 6451
  • [14] CIRCUIT-BREAKERS - THE MECHANICS OF FAULT INTERRUPTION
    WORSLEY, EG
    PULP & PAPER-CANADA, 1985, 86 (11) : 56 - 58
  • [15] Ground fault circuit breakers for heat tracing
    Sandberg, C
    Zylstra, H
    INDUSTRY APPLICATIONS SOCIETY 45TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE - RECORD OF CONFERENCE PAPERS, 1998, : 273 - 279
  • [16] CIRCUIT BREAKERS - THE MECHANICS OF FAULT INTERRUPTION.
    Worsley, E.G.
    Pulp and Paper Canada, 1985, 86 (11): : 56 - 58
  • [17] Nanocrystallized cores for ground fault circuit breakers
    Waeckerlé, T
    Fraisse, H
    Gautard, D
    JOURNAL OF MAGNETISM AND MAGNETIC MATERIALS, 2003, 254 : 253 - 255
  • [18] Research on fault identification of high-voltage circuit breakers with characteristics of voiceprint information
    Wang, Sihao
    Zhou, Yongrong
    Ma, Zhaoxing
    SCIENTIFIC REPORTS, 2024, 14 (01):
  • [19] Identification Method for Operation State of High Voltage Circuit Breakers Based on Spectral Shape Entropy Characteristics of Vibration Signals
    Zhao S.
    Xu W.
    Liu H.
    Zeng R.
    Xia X.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (09): : 2170 - 2178
  • [20] Review of Digital Vibration Signal Analysis Techniques for Fault Diagnosis of High-Voltage Circuit Breakers
    Tan, Yaxiong
    Hu, Erhan
    Liu, Yuan
    Li, Jian
    Chen, Weigen
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (01) : 404 - 418