NUMERICAL INVESTIGATION OF THE PERFORMANCE OF A FORCED DRAFT AIR-COOLED HEAT EXCHANGER

被引:0
|
作者
Engelbrecht, Ruan A. [1 ]
Van der Spuy, Johan [1 ]
Meyer, Chris J. [1 ]
Zapke, Albert [2 ]
机构
[1] Stellenbosch Univ, Dept Mech Engn, Private Bag X1, ZA-7602 Stellenbosch, South Africa
[2] Enexio Management GmbH, Global Head Technol R&D, Dorstener St 18-29, D-44651 Herne, Germany
关键词
FLOW-FIELD; SIMULATION;
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper details the design, validation and verification of. two implicit modelling techniques used to model an Air-Cooled Condenser (ACC) in the computational fluid dynamics (CFD) code environment of OpenFOAM (Open Source Field And Manipulation). The actuator disk model was chosen as the axial flow fan model and the heat exchanger model was implemented as an A-frame, or Delta frame, heat exchanger commonly found on power stations. Both models were validated and verified. A 30 fan ACC was verified against previous literature. The results for all validation and verification procedures showed good agreement with respective data. Three different fan configurations in an ACC were compared at different wind speeds namely the A fan, B2a-fan and a Combined ACC. The study showed small differences between ACCs with regard to fan and thermal performance. However, the B2a-fan ACC consumed 20 % less power than the A-fan ACC and 3-10 % less power than the Combined ACC. This performance increase was most prominently show-cased by the increased heat-to-power ratio with the B2a-fan exhibiting heat-to-power ratios of 110 W/W compared to 96 W/W for the A-fan.
引用
收藏
页数:13
相关论文
共 50 条
  • [41] Performance evaluation on an air-cooled heat exchanger for alumina nanofluid under laminar flow
    Teng, Tun-Ping
    Hung, Yi-Hsuan
    Teng, Tun-Chien
    Chen, Jyun-Hong
    [J]. NANOSCALE RESEARCH LETTERS, 2011, 6 : 1 - 11
  • [42] Enhance air-cooled heat exchanger performance (vol 80, pg 49, 2001)
    Shastri, SS
    Karimi, IA
    Rangaiah, GP
    Yap, C
    [J]. HYDROCARBON PROCESSING, 2002, 81 (05): : 43 - 43
  • [43] Cooling performance evaluation for double-layer configuration of air-cooled heat exchanger
    Wang, Weijia
    Chen, Lei
    Kong, Yanqiang
    Yang, Lijun
    Niu, Yuguang
    Du, Xiaoze
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 151
  • [44] A preliminary method for estimating the effective plume chimney height above a forced-draft air-cooled heat exchanger operating under natural convection
    Chu, CM
    [J]. HEAT TRANSFER ENGINEERING, 2002, 23 (03) : 3 - 12
  • [45] Numerical study on thermal performance of an air-cooled heat exchanger: Effects of hybrid nanofluid, pipe arrangement and cross section
    Karimi, Ali
    Afrand, Masoud
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2018, 164 : 615 - 628
  • [46] Plume recirculation in mechanical-draft air-cooled heat exchangers
    Duvenhage, K
    Kroger, DG
    [J]. HEAT TRANSFER ENGINEERING, 1995, 16 (04) : 42 - 49
  • [47] CORRECTING AIR-COOLED EXCHANGER PROBLEMS
    SHIPES, K
    [J]. CHEMICAL ENGINEERING PROGRESS, 1983, 79 (07) : 56 - 57
  • [48] Air side heat transfer characteristics of wavy-finned-tube in a forced draft direct air-cooled steam condenser
    Zhang, Zhaoying
    Yang, Jianguo
    Zhang, Haizhen
    [J]. ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 3 - 8
  • [49] INVESTIGATION OF A MULTIPLE IMPELLER DESIGN FOR A HIGH PERFORMANCE AIR-COOLED HEAT SINK
    Staats, Wayne L.
    Peters, Teresa B.
    Allison, Jon M.
    McCarthy, Matthew
    Wang, Evelyn N.
    Brisson, John G.
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION - 2010, VOL 7, PTS A AND B, 2012, : 313 - 320
  • [50] An algorithm for simulation of the performance of air-cooled heat exchanger applications subject to the influence of complex circuitry
    Kuo, MC
    Ma, HK
    Chen, SL
    Wang, CC
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (01) : 1 - 9