Safety Verification of a 275-kV HTS Cable System Under Short-Circuit Current Accidents

被引:2
|
作者
Yokoo, Yusuke [1 ]
Takeda, Natsuo [1 ]
Horita, Daichi [1 ]
Agatsuma, Koh [1 ]
Ishiyama, Atsushi [1 ]
Wang, Xudong [2 ]
Takagi, Tomohiro [3 ]
Yagi, Masashi [3 ]
机构
[1] Waseda Univ, Dept Elect Engn & Biosci, Tokyo 1698555, Japan
[2] High Energy Accelerator Res Org, Tsukuba, Ibaraki 3050801, Japan
[3] Furukawa Elect, Ichihara, Chiba 2908555, Japan
关键词
AC loss; fault currents; HTS cables; power cables; temperature; thermal conductivity; POWER CABLE;
D O I
10.1109/TASC.2018.2797525
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A simulation code that analyzes the temperature and pressure in a high-temperature superconducting (HTS) power cable cooled by a forced flow of subcooled liquid nitrogen (LN) has been developed. Analysis of the HTS cable is useful for comprehending the normal operating condition and the generation of heat during the transient state. In Japan, an excessive current of 63 kA may flow in an HTS cable for 0.6 s in the worst case when a short-circuit current accident occurs in a 275-kV class cable. To assess the safety under this condition, a simulation of a 275-kV class 20-m model cable was performed, and the simulation results of the temperature profiles qualitatively agreed with the experimental results. In this study, a finite-difference method was used to solve the nonlinear partial differential equations of the heat-transfer phenomenon through heat conduction. By solving these equations, the temperature profiles of the LN coolant and the cable cores were analyzed. The GASPAK software package (Cryodata) was used to evaluate the fluid properties when the LN temperature in the cable was calculated. According to this result, the simulations focused on the analysis of a real-scale HTS cable in this work.
引用
收藏
页数:5
相关论文
共 50 条
  • [21] Experimental Research on Interference in Secondary Cable from Short-circuit Current in Substations
    Zhang, Bo
    He, Jinliang
    Jiang, Yukuan
    Li, Qian
    Xiao, Leishi
    2015 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIII SIPDA), 2015, : 137 - 140
  • [22] Modelling, simulation, and verification for detailed short-circuit analysis of a 1 x 25 kV railway traction system
    Chen, Tsai-Hsiang
    Liao, Rih-Neng
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (05) : 1124 - 1135
  • [23] Short-circuit current of solar cells under artificial light
    Ortega, P
    Silvestre, S
    Castañer, L
    PROGRESS IN PHOTOVOLTAICS, 2003, 11 (02): : 131 - 138
  • [24] Characteristics of Bi-2223 HTS Tapes Under Short-Circuit Current Impacts in Hybrid Energy Transmission Pipelines
    Sun, Yuguang
    Yin, Chao
    Li, Weizhen
    Li, Xinyang
    Jiang, Xiaohua
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2024, 10 (02): : 736 - 745
  • [25] The probabilistic model of the dynamic of the cables under short-circuit current
    Miroshnik, R
    COMPUTER METHODS IN APPLIED MECHANICS AND ENGINEERING, 2000, 187 (1-2) : 201 - 211
  • [26] PREVENTING WORKING ACCIDENTS BY SHORT-CIRCUIT CURRENTS IN ISOLATED NEUTRAL SYSTEMS OVER 1 KV
    Beiu, Constantin
    Buica, Georgeta
    Toader, Cornel
    ENVIRONMENTAL ENGINEERING AND MANAGEMENT JOURNAL, 2014, 13 (06): : 1355 - 1359
  • [27] Instability of the continuously transposed cable under axial short-circuit forces in transformers
    Patel, MR
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) : 149 - 154
  • [28] Stabilization of short-circuit current levels in grids rated 100 kV and above
    Mozgalev K.V.
    Neklepaev B.N.
    Shuntov A.B.
    Power Technology and Engineering, 2002, 36 (1) : 28 - 30
  • [29] SHORT-CIRCUIT PROTECTION FOR EL-CHOCON 500 KV SYSTEM
    ILAR, F
    LAWTON, K
    BROWN BOVERI REVIEW, 1974, 61 (2-3): : 77 - 81
  • [30] Transient analysis of a 22.9 kV/2 kA HTS cable under short circuit using equivalent circuit model considering different fault parameters
    Sadeghi, Alireza
    Seyyedbarzegar, Seyyed Meysam
    Yazdani-Asrami, Mohammad
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2021, 589