Power Quality Improvement for Grid-connected PV System Based on Distribution Static Compensator with Fuzzy Logic Controller and UVT/ADALINE-based Least Mean Square Controller

被引:44
|
作者
Kumar, Amit [1 ]
Kumar, Pradeep [1 ]
机构
[1] Natl Inst Technol Sikkim, Elect & Elect Engn Dept, Ravangla, Sikkim, India
关键词
Adaptive linear neuron; least mean square (LMS); fuzzy logic controller (FLC); maximum power point tracking (MPPT); photovoltaic (PV); unit vector template; ALGORITHM; MPPT;
D O I
10.35833/MPCE.2021.000285
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a novel method of power quality enrichment in a grid-connected photovoltaic (PV) system using a distribution static compensator (DSTATCOM). The paper consists of two-step control processes. In the primary step, a fuzzy logic controller (FLC) is employed in the DC-DC converter to extract the peak power point from the PV panel, where the FLC produces a switching signal for the DC-DC converter. In the secondary step, a unit vector template (UVT)/adaptive linear neuron (ADALINE)-based least mean square (LMS) controller is adopted in the DC-AC converter, i.e., voltage source converter (VSC). The input to this VSC is the boosted DC voltage, which originates from the PV panel as a result of DC-DC conversion. The VSC shunted with the power grid is known as a DSTATCOM, which can maintain the power quality in the distribution system. The UVT controller generates reference source currents from the grid voltages and DC-link voltages. The ADALINE-based LMS controller calculates the online weight according to the previous weights by the sensed load current. The UVT/ADALINE-based LMS controller of a DSTAT-COM performs several tasks such as maintaining the sinusoidal source current, achieving a unity power factor, and performing reactive power compensation. The reference current extracted from the UVT/ADALINE-based LMS controller is fed to the hysteresis current controller to obtain the desired switching signal for the VSC. A 100 kW solar PV system integrated into a three-phase four-wire distribution system through a four-leg VSC is designed in MATLAB/Simulink. The performances of the FLC and UVT/ADALINE-based LMS controllers are demonstrated under various irradiances as well as constant temperature and nonlinear loading conditions.
引用
收藏
页码:1289 / 1299
页数:11
相关论文
共 50 条
  • [21] ANN and fuzzy logic controller design for hybrid wind/PV system connected to MV distribution grid
    Skretas, Sotirios B.
    Papadopoulos, Demetrios P.
    Singh, S. N.
    INTERNATIONAL JOURNAL OF ENERGY SECTOR MANAGEMENT, 2008, 2 (04) : 499 - 520
  • [22] Transient Stability Enhancement of a Grid-Connected Large-Scale PV System Using Fuzzy Logic Controller
    Hazari, Md Rifat
    Jahan, Effat
    Mannan, Mohammad Abdul
    Das, Narottam
    ELECTRONICS, 2021, 10 (19)
  • [23] Maximum Power Point Tracking in Grid Connected PV System Using A Novel Fuzzy Logic Controller
    Subiyanto
    Mohamed, A.
    Hannan, M. A.
    2009 IEEE STUDENT CONFERENCE ON RESEARCH AND DEVELOPMENT: SCORED 2009, PROCEEDINGS, 2009, : 349 - 352
  • [24] Maximum power point tracking for grid-connected photovoltaic system using Adaptive Fuzzy Logic Controller
    Ali, Majid
    Ahmad, Mujtaba
    Koondhar, Mohsin Ali
    Akram, Muhammad Sarfraz
    Verma, Aanchal
    Khan, Baseem
    COMPUTERS & ELECTRICAL ENGINEERING, 2023, 110
  • [25] Real-Time Testing of a Fuzzy-Logic-Controller-Based Grid-Connected Photovoltaic Inverter System
    Hannan, M. A.
    Abd Ghani, Zamre
    Mohamed, Azah
    Uddin, M. Nasir
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 4775 - 4784
  • [26] Power quality improvement and seamless transfer in a grid-connected microgrid system using H∞ controller
    Lavanya, V.
    Kumar, N. Senthil
    INTERNATIONAL JOURNAL OF AUTOMATION AND CONTROL, 2023, 17 (06) : 657 - 685
  • [27] Sun Flower Optimization with Self-Tuned Fuzzy Logic MPPT Controller and Reactive Power Compensation for Grid-Connected PV System
    Rajendran, Nirmala
    Sundharajan, Venkatesan
    IETE JOURNAL OF RESEARCH, 2023, 69 (12) : 9413 - 9427
  • [28] FPGA-Based Controller for a Hybrid Grid-Connected PV/Wind/Battery Power System with AC Load
    Allani, Mohamed Yassine
    Riahi, Jamel
    Vergura, Silvano
    Mami, Abdelkader
    ENERGIES, 2021, 14 (08)
  • [29] Fuzzy Logic Controller based Maximum Power Point Tracking for PV System
    Narendiran, S.
    Sahoo, Sarat Kumar
    Das, Raja
    Sahoo, Ashwin Kumar
    2016 3RD INTERNATIONAL CONFERENCE ON ELECTRICAL ENERGY SYSTEMS (ICEES), 2016, : 29 - 34
  • [30] Fuzzy Logic Controller based Model for Rooftop/Grid connected Solar Photovoltaic System
    Charan, Chandragiri Radha
    Sujatha, K. Naga
    Satsangi, K. Pritam
    2016 IEEE REGION 10 HUMANITARIAN TECHNOLOGY CONFERENCE (R10-HTC), 2016,