Watthour meter accuracy under controlled unbalanced harmonic voltage and current conditions

被引:16
|
作者
Domijan, A [1 ]
EmbrizSantander, E [1 ]
Gilani, A [1 ]
Lamer, G [1 ]
Stiles, C [1 ]
Williams, CW [1 ]
机构
[1] FLORIDA POWER CORP,ST PETERSBURG,FL 33711
关键词
watthour meter; harmonics; power quality; unbalance; field monitoring; testing; waveform reproduction;
D O I
10.1109/61.484002
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This work presents the results of phase I of the project on the accuracy of watthour meters when subjected to closely-duplicated real-world unbalanced harmonic voltage and current conditions. Such real-world conditions involved differences in voltage and current magnitudes as well as differences in the voltage and current total harmonic distortion levels of each phase. Tests were performed on a selected sample of nine three-phase and three single-phase watthour meters. Some results showed that under a particular set of unbalanced waveforms with harmonic conditions of I-THD > 80% and V-THD > 2%, the percentage errors exhibited by these meters ranged from -10.09% to +0.52%.
引用
收藏
页码:64 / 72
页数:9
相关论文
共 50 条
  • [41] Dual-current Loops Control Strategy of PWM Rectifier Under Unbalanced Grid Voltage Conditions
    Ni Yifeng
    Zhu Yongqiang
    MECHATRONICS ENGINEERING, COMPUTING AND INFORMATION TECHNOLOGY, 2014, 556-562 : 2114 - 2118
  • [42] PWM inverter power transfer under unbalanced voltage conditions
    Lazarov, Vladimir
    Apostolov, Deian
    2006 FIRST INTERNATIONAL SYMPOSIUM ON ENVIRONMENT IDENTITIES AND MEDITERRANEAN AREA, VOLS 1 AND 2, 2006, : 258 - +
  • [43] Current Reference Control for Shunt Active Power Filters Under Unbalanced and Distorted Supply Voltage Conditions
    Nie, Xiaohua
    Liu, Jijun
    IEEE ACCESS, 2019, 7 : 177048 - 177055
  • [44] Control of Distributed Generation Systems under Unbalanced Voltage Conditions
    Kabiri, R.
    Holmes, D. G.
    McGrath, B. P.
    2014 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-HIROSHIMA 2014 - ECCE-ASIA), 2014, : 3306 - 3313
  • [45] Harmonic Currents suppression for three-phase photovoltaic power generation system under unbalanced grid voltage conditions
    Zhou, Niancheng
    Lou, Xiaoxuan
    Wang, Qianggang
    Wang, Jiajia
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (16): : 246 - 254
  • [46] Comprehensive harmonic analysis of matrix converter under unbalanced/distorted conditions
    Barcellona, Simone
    Carmeli, Maria Stefania
    Superti-Furga, Gabrio
    ELECTRIC POWER SYSTEMS RESEARCH, 2013, 96 : 296 - 310
  • [47] Control strategy for doubly-fed wind power system under unbalanced and harmonic distorted grid voltage conditions
    Yao, Jun
    Chen, Zhiqian
    Li, Qing
    Yu, Mengting
    Zhou, Te
    Zhao, Lei
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2014, 38 (18): : 6 - 12
  • [48] Optimal control strategy of voltage source converter-based high-voltage direct current under unbalanced grid voltage conditions
    Sun, Li-Xia
    Chen, Yu
    Wang, Zhe
    Ju, Ping
    Jin, Yu-Qing
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (02) : 444 - 451
  • [49] Balanced Current Control Strategy for Current Source Rectifier Stage of Indirect Matrix Converter under Unbalanced Grid Voltage Conditions
    Bak, Yeongsu
    Lee, June-Seok
    Lee, Kyo-Beum
    ENERGIES, 2017, 10 (01)
  • [50] Double Synchronous Frame Current Regulation of Distributed Generation Systems under Unbalanced Voltage Conditions without Sequence Current Separation
    Kabiri, R.
    Holmes, D. G.
    McGrath, B. P.
    2015 THIRTIETH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC 2015), 2015, : 1822 - 1829