A novel 3D simulation model for investigating liquid desiccant dehumidification performance based on CFD technology

被引:30
|
作者
Wen Tao [1 ]
Luo Yimo [2 ]
Lu Lin [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
[2] Technol & Higher Educ Inst Hong Kong, Fac Sci & Technol, Hong Kong, Peoples R China
关键词
Falling film dehumidification; Film shrinkage; Contact angle; Penetration theory; 3D CFD simulation; ADAPTIVE THERMAL COMFORT; MASS-TRANSFER PROCESS; REGENERATION PERFORMANCE; NUMERICAL-SIMULATION; STRUCTURED PACKING; LICL SOLUTION; FILM FLOW; SURFACTANT; ABSORPTION; STANDARDS;
D O I
10.1016/j.apenergy.2019.02.068
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Previous 2D CFD simulation models fail to elaborate the actual simultaneous flow and dehumidification process in liquid desiccant cooling system. Accordingly, the present study successfully developed a novel 3D simulation model for investigating the liquid desiccant dehumidification performance of a falling film dehumidifier. The penetration mass transfer model was implemented in the simulation to account for the interfacial dehumidification process. Experimental system was built for the model validation and the results indicated that the newly developed 3D CFD model could predict the absolute moisture removal accurately with an average deviation of 7%. Parametric study revealed that the dehumidification performance was closely related with air humidity, velocity, solution temperature, centration, temperature and contact angle but seldom affected by air temperature. The simulation results also indicated that falling film of liquid desiccant shrank gradually along the flow direction, leading to an inhomogeneous water vapor absorption process in the dehumidifier. Intense water vapor absorption occurred at the phase interface, resulting in large solution concentration gradient and humidity content in the zone near the air/liquid contact interface. However, minor mass transfer occurred in other zones mainly in the form of diffusion. Accordingly, several heat/mass transfer enhancement approaches, i.e. structural modifications and surface modification, were proposed to improve the flow turbulence and to enlarge the falling film wettability. The newly proposed 3D simulation model and dehumidification enhancement approaches are meaningful for the design and operation of liquid desiccant cooling system.
引用
收藏
页码:486 / 498
页数:13
相关论文
共 50 条
  • [1] CFD simulation of structured packing in Liquid Desiccant Dehumidification System (LDDS)
    Shen, Suping
    Cai, Wenjian
    Yon, Haoren
    Wang, Qing-Guo
    PROCEEDINGS OF THE 2016 IEEE 11TH CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2016, : 1117 - 1121
  • [2] A simulation model for the performance of a hybrid liquid desiccant system during cooling and dehumidification
    Mago, PJ
    Chamra, L
    Steele, G
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2006, 30 (01) : 51 - 66
  • [3] Performance investigation of a liquid desiccant regenerator with CFD technology
    Guo, Xiaodong
    Wen, Tao
    Wang, Meng
    Luo, Yimo
    She, Xiaohui
    APPLIED THERMAL ENGINEERING, 2021, 184
  • [4] Liquid desiccant dehumidifier: Development of a new performance predication model based on CFD
    Luo, Yimo
    Yang, Hongxing
    Lu, Lin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 69 : 408 - 416
  • [5] Application of CFD Model in Analyzing the Performance of a Liquid Desiccant Dehumidifier
    Luo, Yimo
    Yang, Hongxing
    Chen, Yi
    Wang, Yuanhao
    CUE 2015 - APPLIED ENERGY SYMPOSIUM AND SUMMIT 2015: LOW CARBON CITIES AND URBAN ENERGY SYSTEMS, 2016, 88 : 491 - 497
  • [6] CFD simulation of liquid desiccant dehumidifier performance with smooth and rough plates
    Lu, Hao
    Lu, Lin
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 124 : 1 - 12
  • [7] Dynamic model development of heat and mass transfer for a novel desiccant regeneration system in liquid desiccant dehumidification system
    Ou, Xianhua
    Cai, Wenjian
    He, Xiongxiong
    Wu, Yiming
    APPLIED THERMAL ENGINEERING, 2018, 145 : 375 - 385
  • [8] Model-based optimization strategy for a liquid desiccant cooling and dehumidification system
    Ou, Xianhua
    Cai, Wenjian
    He, Xiongxiong
    ENERGY AND BUILDINGS, 2019, 194 : 21 - 32
  • [9] Investigating dehumidification performance of solar-assisted liquid desiccant dehumidifiers considering different surface properties
    Dong, Chuanshuai
    Lu, Lin
    Wen, Tao
    ENERGY, 2018, 164 : 978 - 994
  • [10] Performance assessment of a membrane liquid desiccant dehumidification cooling system based on experimental investigations
    Chen, Ziwei
    Zhu, Jie
    Bai, Hongyu
    ENERGY AND BUILDINGS, 2017, 139 : 665 - 679