Model-based optimization strategy for a liquid desiccant cooling and dehumidification system

被引:21
|
作者
Ou, Xianhua [1 ]
Cai, Wenjian [1 ]
He, Xiongxiong [2 ]
机构
[1] Nanyang Technol Univ, Sch Elect & Elect Engn, Ctr E City, EXQUISITUS, Singapore 639798, Singapore
[2] Zhejiang Univ Technol, Coll Informat Engn, Hangzhou 310023, Zhejiang, Peoples R China
基金
中国国家自然科学基金;
关键词
Liquid desiccant cooling and dehumidification system; Energy models; Optimization strategy; Improved self-adaptive firefly algorithm; Energy saving; HEAT-PUMP DRIVEN; MASS-TRANSFER; HVAC SYSTEMS; ENERGY; PERFORMANCE; REGENERATOR; VALIDATION; SIMULATION;
D O I
10.1016/j.enbuild.2019.04.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, a model-based optimization strategy for a liquid desiccant cooling and dehumidification (LDCD) system is proposed to improve system energy efficiency. The energy models of the LDCD system are established to predict system energy consumption under different operating conditions. To minimize the system energy consumption while maintaining the system thermal performance, the system energy consumption and thermal performance indicators are normalized by introducing a weight factor in cost function, then an optimization problem considering the interactions between components and system constraints is formulated. An improved self-adaptive firefly algorithm with fast convergence rate is proposed to solve the optimization problem and obtain the optimal set-points for control settings. Tests on an experimental apparatus are carried out to verify the energy saving potential of optimal control strategy under different weight factors and operating conditions. The results indicate that the energy consumption of LDCD system in the proposed optimization strategy is reduced by 12.49% over the conventional strategy. Meanwhile, the energy saving potential of the optimal control strategy is more remarkable for high cooling and dehumidification load. The proposed optimal control strategy can work well for applications in control and energy efficiency improvement of the existing dehumidification systems. (C) 2019 Elsevier B.V. All rights reserved.
引用
下载
收藏
页码:21 / 32
页数:12
相关论文
共 50 条
  • [1] A liquid desiccant system for solar cooling and dehumidification
    Gommed, K
    Grossman, G
    PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, 2002, : 655 - 660
  • [2] A liquid desiccant system for solar cooling and dehumidification
    Gommed, K
    Grossman, G
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2004, 126 (03): : 879 - 885
  • [3] A kinetic mass transfer model of liquid dehumidification for liquid desiccant cooling system
    Li, Xiu-Wei
    Zhang, Xiao-Song
    Wang, Fang
    ENERGY AND BUILDINGS, 2013, 61 : 93 - 99
  • [4] Exergy analysis of liquid desiccant dehumidification and cooling system
    Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200240, China
    Huagong Xuebao, 2008, SUPPL. (37-42):
  • [5] Model-based investigation of a heat pump driven, internally cooled liquid desiccant dehumidification system
    Liu, Jun
    Zhang, Tao
    Liu, Xiaohua
    BUILDING AND ENVIRONMENT, 2018, 143 : 431 - 442
  • [6] A simulation model for the performance of a hybrid liquid desiccant system during cooling and dehumidification
    Mago, PJ
    Chamra, L
    Steele, G
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2006, 30 (01) : 51 - 66
  • [7] Cooling & dehumidification using liquid desiccant
    Rane, MV
    Reddy, SVK
    Bajaj, JS
    PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, 2002, : 414 - 418
  • [8] Modeling of liquid desiccant cooling and dehumidification system based on artificial neural network
    Ou, Xianhua
    Cai, Wenjian
    He, Xiongxiong
    Zhang, Xin
    IECON 2020: THE 46TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2020, : 4810 - 4814
  • [9] Dynamic modeling and validation of a liquid desiccant cooling and dehumidification system
    Ou, Xianhua
    Cai, Wenjian
    He, Xiongxiong
    Zhai, Deqing
    Wang, Xinli
    ENERGY AND BUILDINGS, 2018, 163 : 44 - 57
  • [10] Experimental investigation of a liquid desiccant system for solar cooling and dehumidification
    Gommed, K.
    Grossman, G.
    SOLAR ENERGY, 2007, 81 (01) : 131 - 138