Suppression of lightning-induced overvoltages by distribution line surge arresters

被引:0
|
作者
Fujiwara, N [1 ]
Yoneyama, T [1 ]
Hamada, Y [1 ]
Yokota, T [1 ]
Asakawa, A [1 ]
Shimomura, T [1 ]
Yamaoka, K [1 ]
Ishibe, S [1 ]
机构
[1] CENT RES INST ELECT POWER IND,ELECT & PHYS DEPT,LIGHTNING DISCHARGE GRP,KOMAE LAB,KOMAE,TOKYO 201,JAPAN
关键词
distribution line; direct lightning stroke; overhead ground wire; arrester; experiment; analysis;
D O I
10.1002/eej.4391160604
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The primary aim of surge arresters in power distribution lines is to protect lines and equipment from the voltage induced by nearby lightning strokes. To further improve power systems, methods to protect distribution lines against direct lightning strokes are still needed. An effective measure against direct lightning strokes is to increase the number of arresters. However, if the surge current is too large, some surge arresters absorb energy in excess of their capability and may break; this leads to a line fault. To evaluate the protective effect of the surge arresters against direct lightning strokes to overhead ground wire, the authors measured both the voltage across the surge arresters and the energy absorbed by them using a full-scale model line and a 12 MV impulse generator. The results were compared with simulation results by EMTP. There have been no previous studies making a comparison of this kind.
引用
收藏
页码:32 / 42
页数:11
相关论文
共 50 条
  • [21] CALCULATION OF LIGHTNING INDUCED VOLTAGES ON A DISTRIBUTION LINE WITH LIGHTNING ARRESTERS USING THE FDTD METHOD
    Tatematsu, Akiyoshi
    2010 30TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2010,
  • [22] Optimizing the surge arresters location for improving lightning induced voltage performance of distribution network
    Perez, Ernesto
    Delgadillo, Andres
    Urrutia, Diego
    Torres, Horacio
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 543 - +
  • [23] Modeling and Simulation of Surge Arresters for Lightning Protection of Distribution Systems
    Araujo, M. A.
    Flauzino, R. A.
    Moro, V. C.
    Vieira, J. C. M.
    IEEE LATIN AMERICA TRANSACTIONS, 2015, 13 (07) : 2225 - 2231
  • [24] An Exact Closed-Form Solution for Lightning-Induced Overvoltages Calculations
    Andreotti, A.
    Assante, D.
    Mottola, F.
    Verolino, L.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) : 1328 - 1343
  • [25] Analytical investigation of parameters effect on lightning-induced overvoltages on overhead lines
    Bidi M.
    Latreche M.H.
    International Journal of System Assurance Engineering and Management, 2016, 7 (1) : 114 - 120
  • [26] Mitigation of Transient Overvoltages under Lightning in Networks with Wind Farms Connection using MOV Surge Arresters
    Malcolm, Newman
    Aggarwal, Raj
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [27] Optimal Line Surge Arresters Installation Using Lightning Location System
    Milardic, Viktor
    Uglesic, Ivo
    Xemard, Alain
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2012, 7 (02): : 4077 - 4084
  • [28] Lightning flashover rate of an overhead transmission line protected by surge arresters
    Martinez, J. A.
    Castro-Aranda, F.
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 1240 - 1245
  • [29] Lightning-Induced Overvoltages Transmitted Over Distribution Transformer With MV Spark-Gap Operation - Part II: Mitigation Using LV Surge Arrester
    Sabiha, Nehmdoh A.
    Lehtonen, Matti
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2565 - 2573
  • [30] Lightning Performance Analysis of an Overhead Transmission Line Protected by Surge Arresters
    Velasco, J. A. M.
    Aranda, F. C.
    IEEE LATIN AMERICA TRANSACTIONS, 2009, 7 (01) : 62 - 70