Performances of air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions

被引:98
|
作者
Wang, W. [1 ]
Feng, Y. C. [1 ]
Zhu, J. H. [1 ]
Li, L. T. [1 ]
Guo, Q. C. [1 ]
Lu, W. P. [1 ]
机构
[1] Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
关键词
Air source heat pump; Mal-defrost; COP; Heating capacity; FROST;
D O I
10.1016/j.apenergy.2012.12.054
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 degrees C. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1138 / 1145
页数:8
相关论文
共 26 条
  • [21] PERFORMANCE AND ECONOMY ANALYSIS OF A SOLAR ASSISTED CO2 GROUND SOURCE HEAT PUMP WITH AIR-COOLED GAS COOLER UNDER DIFFERENT CLIMATE CONDITIONS
    Ye, J.
    Eikevik, T. M.
    Neksa, P.
    Hafner, A.
    Ding, G.
    Hu, H.
    11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014): NATURAL REFRIGERANTS AND ENVIRONMENTAL PROTECTION, 2014, : 543 - 550
  • [22] Optimization of design parameters and operation conditions of solar-air source heat pump coupled system for rural buildings in cold and severe cold regions
    Zhang, Zhibin
    Cao, Ying
    Qin, Siyu
    Wang, Zheng
    Gao, Wei
    Jia, Guosheng
    Jin, Linwen
    SOLAR ENERGY, 2025, 286
  • [23] Performance Evaluation of an Air Source Heat Pump Coupled with a Building-Integrated Photovoltaic/Thermal (BIPV/T) System under Cold Climatic Conditions
    Hailu, Getu
    Dash, Peter
    Fung, Alan S.
    6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 : 1913 - 1918
  • [24] Energy and emission performance of enhanced vapor injection air source heat pump system using low global warming potential refrigerants in different climate regions
    Zhang, Libiao
    Jing, Wuhui
    Wang, Qilong
    Zhang, Jianing
    Yang, Peifang
    FRONTIERS IN ENERGY RESEARCH, 2023, 11
  • [25] Experimental study and exergy analysis of electric vehicle single-stage compression secondary throttling CO 2 air-source heat pump system in cold climate
    Wang, Fengxian
    Wu, Weidong
    Wang, Rujin
    Chen, Lang
    Zhang, Hua
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 164 : 75 - 85
  • [26] Experimental study and exergy analysis of electric vehicle single-stage compression secondary throttling CO 2 air-source heat pump system in cold climate
    Wang, Fengxian
    Wu, Weidong
    Wang, Rujin
    Chen, Lang
    Zhang, Hua
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 164 : 75 - 85