Performances of air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions

被引:98
|
作者
Wang, W. [1 ]
Feng, Y. C. [1 ]
Zhu, J. H. [1 ]
Li, L. T. [1 ]
Guo, Q. C. [1 ]
Lu, W. P. [1 ]
机构
[1] Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
关键词
Air source heat pump; Mal-defrost; COP; Heating capacity; FROST;
D O I
10.1016/j.apenergy.2012.12.054
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 degrees C. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1138 / 1145
页数:8
相关论文
共 26 条
  • [1] Field test investigation of the characteristics for the air source heat pump under two typical mal-defrost phenomena
    Wang, W.
    Xiao, J.
    Guo, Q. C.
    Lu, W. P.
    Feng, Y. C.
    APPLIED ENERGY, 2011, 88 (12) : 4470 - 4480
  • [2] DEFROST PERFORMANCE STUDY OF CONTINUOUS HEATING AIR SOURCE HEAT PUMP SYSTEM WITH SEGMENTED DEFROST
    Liu X.
    Chen H.
    Feng R.
    Huang T.
    He S.
    Tang L.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (11): : 1 - 8
  • [3] New air source heat pump system of energy store for heat flux defrost and it's experimental study
    Han, Zhi-Tao
    Yao, Yang
    Ma, Zui-Liang
    Jiang, Yi-Qiang
    Harbin Gongye Daxue Xuebao/Journal of Harbin Institute of Technology, 2007, 39 (06): : 901 - 903
  • [4] Application of a water-heat storage system for the prevention of duplex defrost using an air-source heat pump
    Lim, K. B.
    Lee, S. H.
    Lee, C. H.
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2010, 224 (E1) : 67 - 71
  • [5] CLIMATE ADAPTATION ANALYSIS OF A SOLAR-AIR COMPOSITE HEAT SOURCE HEAT PUMP SYSTEM
    Liu, Y.
    Zhou, G. H.
    Shen, J. Y.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 840 - 845
  • [6] Combined Cold-climate Air-source Heat Pump and Heat Pump Water Heater System Performance in Multiple Climate Zones
    Guada, Alejandro Baez
    Kingston, Tim
    ASHRAE TRANSACTIONS 2021, VOL 128, PT 1, 2022, 128 : 137 - 145
  • [7] Performance of biogas engine driven air source heat pump system under variable conditions
    Wu J.
    Ma Y.
    Cao W.
    Wu, Jiying (wjyjw@jmu.edu.cn), 1600, Materials China (71): : 3789 - 3796
  • [8] Frosting Phenomenon and Frost-Free Technology of Outdoor Air Heat Exchanger for an Air-Source Heat Pump System in China: An Analysis and Review
    Zhang, Yi
    Zhang, Guanmin
    Zhang, Aiqun
    Jin, Yinhan
    Ru, Ruirui
    Tian, Maocheng
    ENERGIES, 2018, 11 (10)
  • [9] Effects of air flow maldistribution on refrigeration system dynamics of an air source heat pump chiller under frosting conditions
    Gong Jianying
    Gao Tieyu
    Yuan Xiuling
    Huang Dong
    ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (06) : 1645 - 1651
  • [10] Effect of air cooled coil fan pre-start on the refrigeration system dynamics during the reverse-cycle defrost of an air-source heat pump chiller
    Huang, Dong
    Yuan, Xiuling
    Zhang, Bo
    Zhang, Xingqun
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2004, 38 (05): : 448 - 451