A virtual condenser fouling sensor for chillers

被引:45
|
作者
Zhao, Xinzhi [1 ]
Yang, Mo [1 ]
Li, Haorong [1 ]
机构
[1] Nodal Partners LLC, Dept Res & Dev, Austin, TX USA
关键词
Chiller; Condenser fouling; Virtual sensor; FDD; FAULT-DETECTION; DECOUPLING FEATURES; DIAGNOSIS STRATEGY;
D O I
10.1016/j.enbuild.2012.05.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the field, almost every condenser suffers from some kind of fouling problems. The chiller performance degrades naturally and gradually as fouling increases. Early identification of fouling in the condenser is essential to maintain an optimal chiller operation. In this paper, a method (virtual fouling monitor sensor) using low cost and commonly available onboard chiller measurements for monitoring the fouling status of the condenser is presented. The performance of the proposed virtual fouling monitor sensor was evaluated using lab data over a wide range of operating conditions in both normal and faulty conditions. Moreover, the proposed virtual fouling monitor sensor was also implemented and evaluated on a field chiller. The laboratory and field test results show that the proposed method gives a good and robust performance in terms of detecting the condenser fouling faults in chillers. In terms of possible applications, the proposed method has the potential to be implemented as an individual fouling monitor sensor/tool, incorporated within the commercial chiller FDD tool, or embedded in the control systems onboard the chiller to automatically monitor the condenser fouling status. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:68 / 76
页数:9
相关论文
共 50 条
  • [41] Online measurement of fouling in steam condenser based on character selection and fuzzy modeling
    Fan Shaosheng
    Wang Xiaohua
    Li Hong
    [J]. SIGNAL ANALYSIS, MEASUREMENT THEORY, PHOTO-ELECTRONIC TECHNOLOGY, AND ARTIFICIAL INTELLIGENCE, PTS 1 AND 2, 2006, 6357
  • [42] Fault analysis in a domestic refrigerator: Fan fault, condenser fouling, and area restriction
    Pardo-Cely, D.
    Belman-Flores, J. M.
    Heredia-Aricapa, Y.
    Rodriguez-Valderrama, D. A.
    Morales-Fuentes, A.
    Gallegos-Munoz, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 154 : 290 - 299
  • [43] Analysis of the thermoeconomical behavior on an split type air conditioner due to condenser fouling
    Alvarez Pineda, Juan Fernando
    Marin Munoz, Sebastian
    Valencia Hernandez, Carlos Alberto
    Salazar Hincapie, Arley
    Romero Maya, Andres Felipe
    [J]. 2017 CHILEAN CONFERENCE ON ELECTRICAL, ELECTRONICS ENGINEERING, INFORMATION AND COMMUNICATION TECHNOLOGIES (CHILECON), 2017,
  • [44] The influence of condenser cooling seawater fouling on the thermal performance of a nuclear power plant
    Ibrahim, Said M. A.
    Attia, Sami I.
    [J]. ANNALS OF NUCLEAR ENERGY, 2015, 76 : 421 - 430
  • [45] Numerical investigation on fouling cleaning of direct air cooled condenser finned tube
    Wang, Jianjiang
    Li, Tao
    Jing, Xuehui
    Wang, Shenglong
    Song, He Yu Jiang
    Li, Ji
    Zhang, Siwen
    [J]. Huagong Jinzhan/Chemical Industry and Engineering Progress, 2016, 35 (S2): : 99 - 102
  • [46] A novel approach based on fuzzy modeling for online measurement of fouling in steam condenser
    Fan, SS
    Wang, YA
    [J]. ICEMI 2005: Conference Proceedings of the Seventh International Conference on Electronic Measurement & Instruments, Vol 5, 2005, : 176 - 180
  • [47] Economic benefits of improved condenser features for air-cooled chillers serving an air-conditioned hotel
    Yu, FW
    Chan, KT
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (10) : 1063 - 1073
  • [48] Energy saving and environmental impact of optimizing the number of condenser fans in centrifugal chillers under partial load operation
    Deymi-Dashtebayaz, Mahdi
    Farahnak, Mehdi
    Abadi, Reza Nazeri Boori
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 103 : 163 - 179
  • [49] Estimating cooling production and monitoring efficiency in chillers using a soft sensor
    Serafín Alonso
    Antonio Morán
    Daniel Pérez
    Miguel A. Prada
    Ignacio Díaz
    Manuel Domínguez
    [J]. Neural Computing and Applications, 2020, 32 : 17291 - 17308
  • [50] Estimating cooling production and monitoring efficiency in chillers using a soft sensor
    Alonso, Serafin
    Moran, Antonio
    Perez, Daniel
    Prada, Miguel A.
    Diaz, Ignacio
    Dominguez, Manuel
    [J]. NEURAL COMPUTING & APPLICATIONS, 2020, 32 (23): : 17291 - 17308