Effect of UPFC on protection of transmission lines with infeed current

被引:14
|
作者
Pazoki, Mohammad [1 ]
Moravej, Zahra [1 ]
Khederzadeh, Mojtaba [2 ]
Nair, Nirmal-Kumar C. [3 ]
机构
[1] Semnan Univ, Elect & Comp Engn Fac, Semnan, Iran
[2] Shahid Beheshti Univ, Elect & Comp Engn Dept, Tehran, AC, Iran
[3] Univ Auckland, Dept Elect & Comp Engn, Auckland, New Zealand
关键词
distance protection; infeed current; UPFC; real-time simulation; REAL-TIME IMPLEMENTATION; DISTANCE PROTECTION; PERFORMANCE; RELAY; SHUNT; SYSTEMS; SSSC;
D O I
10.1002/etep.2212
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The increasing penetration of flexible AC transmission system devices and renewable generation resources within existing conventional power system networks has necessitated the relook into protective relaying schemes for ensuring grid security and integrity. This paper investigates the impact of a unified power flow controller (UPFC) on Zones 1 and 2 (with infeed current) of the conventional distance relay and pilot protection schemes. Using both analytical and detailed simulation techniques, these schemes have been very thoroughly assessed. The protection impacts for four functions of UPFC are compared with each other comprehensively. The infeed current effect for existing distance relay, as represented by standard MHO characteristics, has been adapted to factor the effect of source and line impedances. In addition, a proposed modification procedure highlights the main reasons for the impedance trajectory changes during faults at Zones 1 and 2 resulting due to the presence of the UPFC. A detailed model of UPFC and six measuring units of distance protection have been developed in the MATLAB/Simulink environment. The accuracy of compensated network and impedance measuring units are verified using Opal-RT's RT-LAB real-time engineering emulator. Copyright (c) 2016 John Wiley & Sons, Ltd.
引用
收藏
页码:2385 / 2401
页数:17
相关论文
共 50 条
  • [41] Current differential protection of double-circuit transmission lines in modal domain
    Snehal Unde
    Sanjay Dambhare
    Electrical Engineering, 2020, 102 : 2401 - 2411
  • [42] Improved differential current protection scheme for CSC-HVDC transmission lines
    Kong, Fei
    Hao, Zhiguo
    Zhang, Baohui
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (04) : 978 - 986
  • [43] Performance of current differential protection for transmission lines in HVDC/AC interconnected system
    Zhang, Pu
    Wang, Gang
    Li, Hai-Feng
    Zhu, Ge-Lan
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (10): : 1 - 5
  • [44] Transient current protection for transmission lines based on the Kalman filter measurement residual
    Dantas, Daniel Texidor
    Neto, Jesus Anicio de Oliveira
    Manassero Junior, Giovanni
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 154
  • [45] Phase Related Current Differential Protection of Three-terminal Transmission Lines
    Li, Bin
    Luo, Tao
    Bo, Zhiqian
    MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 5542 - +
  • [46] A new current differential protection scheme for two-terminal transmission lines
    Zhang, Min
    Dong, Xinzhou
    Bo, Z. Q.
    Caunce, B. R. J.
    Klimek, A.
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 4570 - +
  • [47] Distance Protection of Transmission Line with Infeed Based on Real-Time Simulator
    Pazoki, Mohammad
    Moravej, Zahra
    Khederzadeh, Mojtaba
    Nair, Nirmal K. C.
    2014 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2014,
  • [48] A transient current based double line transmission system protection using fuzzy-wavelet approach in the presence of UPFC
    Goli, Ravi Kumar
    Shaik, Abdul Gafoor
    Ram, S. S. Tulasi
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 70 : 91 - 98
  • [49] Coupling effect in multi-infeed direct current transmission system based on reactive power flow analysis
    State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing
    102206, China
    不详
    102200, China
    Dianli Xitong Zidonghue, 13 (153-159):
  • [50] Effect of UPFC Allocation on Transmission System Power Loss
    Sarkar, Mithu
    2013 INTERNATIONAL CONFERENCE ON ENERGY EFFICIENT TECHNOLOGIES FOR SUSTAINABILITY (ICEETS), 2013,