Root-Cause Identification of Single Line-to-Ground Fault in Urban Small Current Grounding Systems Based on Correlation Dimension and Average Resistance

被引:16
|
作者
Cong, Zihan [1 ]
Liu, Yadong [1 ]
Fang, Jian [2 ]
Wang, Peng [3 ]
Guo, Linhui [4 ]
Jiang, Xiuchen [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai 200240, Peoples R China
[2] Guangzhou Power Supply Bur Co Ltd, Elect Power Test Inst, Guangzhou 510420, Peoples R China
[3] Elect Power Res Inst Elect Power Henan, State Grid, Zhengzhou 450052, Peoples R China
[4] Guangzhou Power Supply Bur Co Ltd, Guangzhou 510420, Peoples R China
基金
中国国家自然科学基金;
关键词
Grounding; Correlation; Delays; Fault diagnosis; Surface resistance; Distribution network; Single line-to-ground fault; Root cause; Phase-space reconstruction; Urban two-layer soil model; Average resistance; PHASE-SPACE RECONSTRUCTION; ELECTRICAL-RESISTIVITY; LOCATION SCHEME; TRANSFORM; MOISTURE; NETWORK;
D O I
10.1109/TPWRD.2019.2955185
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Root-cause identification of faults in a distribution network is conducive to fault inspection as well as reducing injuries and damage. In this article, a novel method based on correlation dimension and average resistance is proposed to identify the root cause of permanent single line-to-ground fault in urban small current grounding systems. First, the reliability of the grounding fault and whether the fault occurred on a dry or wet surface can be identified by the correlation dimension. Then, the average resistance of the fault is used to classify the specific root cause, including wet land, dry land, wet concrete, dry concrete, and water. Experimental results show that this method can realize the classification of root causes and is robust to sampling rate, harmonics, and line impedance.
引用
收藏
页码:1834 / 1843
页数:10
相关论文
共 25 条
  • [21] Single-phase-to-ground fault protection based on zero-sequence current ratio coefficient for low-resistance grounding distribution network
    Li, Jianrui
    Li, Yongli
    Wang, Yonghuan
    Song, Jinzhao
    GLOBAL ENERGY INTERCONNECTION-CHINA, 2021, 4 (06): : 564 - 575
  • [22] Single Phase-to-Ground Fault Line Identification and Section Location Method for Non-Effectively Grounded Distribution Systems Based on Signal Injection
    潘贞存
    王成山
    丛伟
    张帆
    Transactions of Tianjin University, 2008, (02) : 92 - 96
  • [23] Single phase-to-ground fault line identification and section location method for non-effectively grounded distribution systems based on signal injection
    Pan Z.
    Wang C.
    Cong W.
    Zhang F.
    Transactions of Tianjin University, 2008, 14 (02) : 92 - 96
  • [24] A Single-Phase High-Impedance Ground Faulty Feeder Detection Method for Small Resistance to Ground Systems Based on Current-Voltage Phase Difference
    Hou, Zequan
    Zhang, Zhihua
    Wang, Yizhao
    Duan, Jiandong
    Yan, Wanying
    Lu, Wenchao
    SENSORS, 2022, 22 (12)
  • [25] Feature-clustering-based single-line-to-ground fault section location using auto-encoder and fuzzy C-means clustering in resonant grounding distribution systems
    Gao, Jian-Hong
    Guo, Mou-Fa
    Shao, Xiang
    Chen, Duan-Yu
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2021, 15 (05) : 938 - 949