Measurement of transient electromagnetic coupling and interference caused by disconnector operation in substation

被引:9
|
作者
Wang Lihui [1 ]
Huang Jiayu [1 ]
Ji Jianfei [2 ]
Pang Fubin [2 ]
Yuan Yubo [2 ]
机构
[1] Southeast Univ, Sch Instrument Sci & Engn, Nanjing 210096, Jiangsu, Peoples R China
[2] Jiangsu Elect Power Co, Res Inst, Nanjing 211103, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Disconnector operation; VFTO; Electromagnetic interference; Improved Agrawal model; FDTD; Measurement; TRANSMISSION-LINES;
D O I
10.1016/j.measurement.2016.10.034
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Disconnector operation in the substation can cause transient electromagnetic disturbance and very fast transient over-voltage (VFTO), and will lead to the misoperation or damage of electrical protection system. To research the characteristics and influence of electromagnetic interference, principle of disconnector operation was analyzed. Then, an improved Agrawal model was adopted to describe the transmission line coupling process of disconnector operation, and telegraph equation was calculated by finite difference time-domain (FDTD) method. With the model and method, the conduction process and characteristics of transient electromagnetic coupling and interference caused by disconnector operation in substation were simulated. Besides, disturbance voltage signal on the secondary cables caused by disconnector operation was measured in a 500 kV substation. Finally, parameters of transient electromagnetic coupling and interference in time domain and frequency domain were calculated respectively. Experiment results show that the quantitative level of transient electromagnetic coupling and interference caused by disconnector operation in substation can be evaluated in theory, and the core frequency points concerned in secondary circuit can be calculated. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 7
页数:7
相关论文
共 50 条
  • [41] TRANSIENT ELECTROMAGNETIC-INTERFERENCE IN SUBSTATIONS
    WIGGINS, CM
    THOMAS, DE
    NICKEL, FS
    WRIGHT, SE
    SALAS, TM
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) : 1869 - 1884
  • [42] Analysis of electromagnetic transients in secondary circuits due to disconnector switching in 400 kV air-insulated substation
    Filipovic-Grcic, B.
    Uglesic, I.
    Milardic, V.
    Filipovic-Grcic, D.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2014, 115 : 11 - 17
  • [43] Research on Very Fast Transient Voltage of 330kV GIS Disconnector Operation
    Yue, Tong
    Qi, Wang
    Jin, Zhang
    Xiang, Liu
    [J]. 2023 5TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM, AEEES, 2023, : 94 - 98
  • [44] Characterization of a malfunction caused by electromagnetic interference
    Saario, T
    Skulic, B
    Segal, B
    Retfalvi, S
    [J]. CANADIAN MEDICAL AND BIOLOGICAL ENGINEERING SOCIETY, PROCEEDINGS, 1997, : 38 - 39
  • [45] Electromagnetic interference caused by aerospace explosives
    Cao, Jingyang
    Xie, Shuguo
    Su, Donglin
    Ma, Zhichao
    [J]. Beijing Hangkong Hangtian Daxue Xuebao/Journal of Beijing University of Aeronautics and Astronautics, 2011, 37 (11): : 1384 - 1387
  • [46] Measurement of electromagnetic interference in the primary electromagnetic laboratory
    Malaric, R.
    Ilic, D.
    Malaric, K.
    [J]. MEASUREMENT 2007: 6TH INTERNATIONAL CONFERENCE ON MEASUREMENT, PROCEEDINGS, 2007, : 259 - +
  • [47] Measurement and Prediction of Electrical Substation Generated Electromagnetic Field
    Ma, Yan
    Karady, George G.
    Hunt, James R.
    Priest, Bryce L.
    [J]. 2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [48] Analysis and identification method of transient over-voltage coupling characteristics of secondary equipment in substation caused by induced lightning
    Zhang, Bin
    Wang, Fei Ming
    Chen, Hao
    Shi, Ke Jian
    Zhao, Dan
    Zhao, Zi Jian
    [J]. 2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1544 - 1549
  • [49] Analysis of Electromagnetic Interference Level for Field Installation of Intelligent Device in Substation
    Yang, Zhi-xin
    Ji, Jian-fei
    Yang, Yi-fei
    Yuan, Yu-bo
    [J]. INTERNATIONAL CONFERENCE ON ELECTRICAL, CONTROL AND AUTOMATION ENGINEERING (ECAE 2013), 2013, : 12 - 19
  • [50] Application of digital lock-in amplifier in complex electromagnetic interference of substation
    Song J.
    Song H.
    Yang X.
    Dong H.
    [J]. Song, Hengli (songhengli@cug.edu.cn); Song, Hengli (songhengli@cug.edu.cn), 1600, Electromagnetics Academy (106): : 105 - 120