Modelling and simulation of air-conditioning cycles

被引:3
|
作者
Rais, Sandi [1 ,2 ,3 ]
Kadono, Yoshinori [1 ]
Murayama, Katsunori [1 ]
Minakuchi, Kazuya [1 ]
Takeuchi, Hisae [2 ]
Hasegawa, Tatsuya [2 ]
机构
[1] Grad Sch Engn, Dept Aerosp Engn, Nagoya, Aichi, Japan
[2] Nagoya Univ, EcoTopia Sci Inst, Chikusa Ku, Furo Cho, Nagoya, Aichi, Japan
[3] Nagoya Univ, Grad Sch Engn, EcoTopia Sci Inst, Hasegawas Lab,Dept Aerosp Engn, Room 524, Nagoya, Aichi 4648603, Japan
关键词
HEAT-PUMP; PERFORMANCE;
D O I
10.1007/s00231-016-1826-1
中图分类号
O414.1 [热力学];
学科分类号
摘要
The heat-pump cycle for air conditioning was investigated both numerically and experimentally by evaluating the coefficient of performance (COP) under Japanese Industrial Standard (JIS B 8619:1999) and ANSI/AHRI standard 750-2007 operating conditions. We used two expansion valve coefficients for standard operating conditions (Case 1) approaching 1.3 MPa at high pressure and 0.2 MPa at low pressure, and namely poor operating conditions (Case 2). To improve the performance of the air conditioner, we compared the performance for two outside air temperatures, 35 and 40 A degrees C (Case 3). The simulation and experiment comparison resulted the decreasing of the COP for standard operating condition is equal to 14 %, from 3.47 to 2.95 and a decrease of the cooling capacity is equal to 18 %, from 309.72 to 253.53 W. This result was also occurred in poor operating condition which the COP was superior at 35 A degrees C temperature.
引用
收藏
页码:425 / 438
页数:14