Power hardware in the loop validation of fault ride through of VSC HVDC connected offshore wind power plants

被引:34
|
作者
Sharma, Ranjan [1 ]
Wu, Qiuwei [2 ]
Cha, Seung Tae [2 ]
Jensen, Kim H. [1 ]
Rasmussen, Tonny W. [2 ]
Ostegaard, Jacob [2 ]
机构
[1] Siemens Wind Power AS, DK-7330 Brander, Denmark
[2] Tech Univ Denmark, Dept Elect Engn, Ctr Elect Power & Energy, DK-2800 Lyngby, Denmark
关键词
Fault ride through; High voltage DC (HVDC); Offshore wind power plant; Power hardware in the loop (PHIL); Voltage source converter (VSC); FARMS;
D O I
10.1007/s40565-014-0049-z
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the power hardware in the loop (PHIL) validation of a feed forward DC voltage control scheme for the fault ride through (FRT) of voltage source converter (VSC) high voltage DC (HVDC) connected offshore wind power plants (WPPs). In the proposed FRT scheme, the WPP collector network AC voltage is actively controlled by considering both the DC voltage error and the AC current from the WPP AC collector system which ensures fast and robust FRT of the VSC HVDC connected offshore WPPs. The PHIL tests were carried out in order to verify the efficacy of the proposed feed forward DC voltage control scheme for enhancing the FRT capability of the VSC HVDC connected WPPs. The PHIL test results have demonstrated the proper control coordination between the offshore WPP and the WPP side VSC and the efficient FRT of the VSC HVDC connected WPPs.
引用
收藏
页码:23 / 29
页数:7
相关论文
共 50 条
  • [11] Optimal fault ride through compliance of offshore wind power plants with VSC-HVDC connection by meta-heuristic based tuning
    Ndreko, Mario
    Rueda, Jose L.
    Popov, Marjan
    van der Meijden, Mart A. M. M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 145 : 99 - 111
  • [12] Fault Ride-Through of HVDC Connected Large Offshore Wind Farms
    Xu, Lie
    Yao, Liangzhong
    Green Energy and Technology, 2012, 78 : 415 - 430
  • [13] Power reduction coordinated scheme for wind power plants connected with VSC-HVDC
    Egea-Alvarez, Agusti
    Aragues-Penalba, Monica
    Prieto-Araujo, Eduardo
    Gomis-Bellmunt, Oriol
    RENEWABLE ENERGY, 2017, 107 : 1 - 13
  • [14] A Study on Fault Ride-Through of VSC-Connected Offshore Wind Farms
    Mohammadi, M.
    Avendano-Mora, M.
    Barnes, M.
    Chan, J. Y.
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [15] Impact of fault ride-through methods on wind power generators in a VSC-HVDC system
    Li, Xuan
    Song, Qiang
    Liu, Wenhua
    Ma, Yulong
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (11): : 31 - 36
  • [16] Fault Ride Through Characteristics of Connection of Large Wind Power Island to VSC-HVDC Grid
    Li Yan
    Liu Chao
    Chi Yongning
    Tang Haiyan
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 1230 - 1234
  • [17] Fault Ride Through Certification of Wind Turbines based on a Power Hardware in the Loop Setup
    Helmedag, Alexander
    Isermann, Timo
    Monti, Antonello
    2013 IEEE INTERNATIONAL WORKSHOP ON APPLIED MEASUREMENTS FOR POWER SYSTEMS (AMPS), 2013, : 150 - 155
  • [18] VSC HVDC active damping for the Sylwin 1 offshore wind power plants
    Manchola, Alvaro Hernandez
    Priebe, Torsten
    Hoelzer, Michael
    Dommaschk, Mike
    JOURNAL OF ENGINEERING-JOE, 2019, (18): : 4748 - 4753
  • [19] Black Start by HVdc-connected Offshore Wind Power Plants
    Sakamuri, Jayachandra N.
    Goksu, Omer
    Bidadfar, Ali
    Saborio-Romano, Oscar
    Jain, Anubhav
    Cutululis, Nicolaos A.
    45TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2019), 2019, : 7045 - 7050
  • [20] Fault Ride Through Strategy of VSC-MTDC System Connected with Offshore Wind Farms
    Li, Jing
    Li, Yong
    Wang, Weiyu
    Cao, Yijia
    PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 1756 - 1761