Failure of MV Cable Terminations Due to Supraharmonic Voltages: A Risk Indicator

被引:14
|
作者
Espin-Delgado, Angela [1 ]
Letha, Shimi Sudha [1 ]
Ronnberg, Sarah K. [1 ]
Bollen, Math H. J. [1 ]
机构
[1] Lulea Univ Technol, Elect Power Engn Grp, S-97187 Skelleftea, Sweden
关键词
Dielectric breakdown; dielectric losses; power cable insulation; power quality; power system harmonics; supraharmonics;
D O I
10.1109/OJIA.2020.2998000
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper addresses the accelerated aging of medium-voltage (MV) cable terminations with resistive stress-grading due to supraharmonics. The paper introduces a simple and quick way to relate the risk of cable termination failure to the characteristics of supraharmonic distortion in the system. The motivation is to give practical recommendations and guidelines to evaluate the risk of failure of cable terminations under the presence of supraharmonics in MV networks. The underlying model relates the heating in the cable termination linearly with the frequency of the voltage applied and proportionally with the square of the magnitude of the voltage. The indicator can be used to decide whether given levels and frequencies of supraharmonics in the MV network represent a risk to cable terminations. The parameters of the cable termination design are not needed for that decision. However, the decision criterion is based on one sample data (Eagle Pass) and more field information is crucial to improve the approach.
引用
收藏
页码:42 / 51
页数:10
相关论文
共 50 条
  • [1] A new concept in construction of cable terminations for medium voltages
    Nikolajevic, SV
    Pekaric-Nad, NM
    Dimitrijevic, RM
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (03) : 712 - 717
  • [2] Cable transient voltages due to microphonics
    Kaiser, Kenneth L.
    Palmer, Karen I.
    [J]. JOURNAL OF ELECTROSTATICS, 2007, 65 (12) : 723 - 727
  • [3] The application of on-line PDM on in-service MV cable terminations
    Chiu, Min-Yen
    Lee, Chang-Hsing
    Huang, Chih-Hsien
    Yen, Shih-Shong
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1171 - +
  • [4] Defect Classification in MV Cable Terminations Based on Residual Neural Network
    Uckol, Halil Ibrahim
    Ilhan, Suat
    [J]. 2020 12TH INTERNATIONAL CONFERENCE ON ELECTRICAL AND ELECTRONICS ENGINEERING (ELECO), 2020, : 6 - 9
  • [5] A Survey of the Portuguese MV Underground Cable Failure
    Maggioli, E.
    Leite, H.
    Morais, C.
    [J]. 2016 13TH INTERNATIONAL CONFERENCE ON THE EUROPEAN ENERGY MARKET (EEM), 2016,
  • [6] An Online Condition Monitoring Thermal Prognostic Indicator System for MV Cable Circuits
    Christou, S.
    Lewin, P. L.
    Pilgrim, J. A.
    Swingler, S. G.
    [J]. 2015 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2015, : 535 - 538
  • [7] Spice equivalent circuit of a two-parallel-wires shielded cable for evaluation of the RF induced voltages at the terminations
    Antonini, G
    Orlandi, A
    [J]. IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2004, 46 (02) : 189 - 198
  • [8] Measured and simulated time-evolution PD characteristics of typical installation defects in MV XLPE cable terminations
    Haikali, E. N. N.
    Nyamupangedengu, C.
    [J]. SAIEE AFRICA RESEARCH JOURNAL, 2019, 110 (03) : 136 - 144
  • [9] Failure Analysis of a Cable Dome Due to Cable Slack or Rupture
    Zhu, Ming-liang
    Dong, Shi-lin
    Yuan, Xing-fei
    [J]. ADVANCES IN STRUCTURAL ENGINEERING, 2013, 16 (02) : 259 - 271
  • [10] Temperature Dependent Signal Propagation Velocity: Possible Indicator for MV Cable Dynamic Rating
    Li, Yan
    Wouters, Peter A. A. F.
    Wagenaars, Paul
    van der Wielen, Peter C. J. M.
    Steennis, E. Fred
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (02) : 665 - 672