This paper presents an investigation into the recurring failures of pad-mounted generator step-up transformers that have been experienced by Exelon Wind at a wind farm in Northern Texas. Observations indicate that the transformer failures are typically a result of contaminated oil due to arcing within the transformer expulsion fuse tube. To determine the underlying cause of this phenomena, S&C Electric Company installed digital monitoring equipment to capture electrical and thermal data at a pad-mounted generator step-up transformer over a four-month period. Electrical data was also captured at the point of interconnect between the wind farm and the local utility. The data captured in this time frame revealed that high-current surges and current cycling frequently occurred due to the WTG cycling on and off from the highly variable wind speeds in the area. High-current surges and current cycling places thermomechanical stress on the transformer and expulsion fuse links, which may ultimately lead to the types of failures experienced at this location.
引用
收藏
页数:7
相关论文
共 50 条
  • [1] ANALYSIS OF A GENERATOR STEP-UP TRANSFORMER FAILURE FOLLOWING FAULTY SYNCHRONIZATION
    PASTERNACK, BM
    PROVANZANA, JH
    WAGENAAR, LB
    IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (03) : 1051 - 1058
  • [2] ANALYSIS OF GENERATOR STEP-UP TRANSFORMER RELIABILITY.
    Haratyk, John L.
    Skinger, Kenneth R.
    1978,
  • [3] Generator step-up transformer post mortem assessment
    Susa, D.
    Liland, K. B.
    Lundgaard, L.
    Vardal, G.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2011, 21 (05): : 1802 - 1822
  • [4] Development of high voltage step-up transformer as a substitute for a Marx generator
    Masugata, K
    Saitoh, H
    Maekawa, H
    Yatsui, K
    Shibata, K
    Shigeta, M
    REVIEW OF SCIENTIFIC INSTRUMENTS, 1997, 68 (05): : 2214 - 2220
  • [5] Analysis of internal winding stresses in EHV generator step-up transformer failures
    Morched, AS
    Marti, L
    Brierley, RH
    Lackney, JG
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) : 888 - 894
  • [6] An Experience With Transformer Connections and Relay Settings for Temporary Generator Step-Up Unit
    Sutherland, Peter E.
    Garcia, Juan Carlos Parra
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2013, 49 (01) : 275 - 283
  • [7] Influence of pulse rise time and duty cycle on distribution of transients along the wind turbine step-up transformer windings
    Devadiga, Anurag A.
    Jayaram, Shesha H.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 203
  • [8] A Study of Remaining Lifetime Assessment of Generator Step-up Transformer Using Degree of Polymerization
    Sermsukroongsakul, Surin
    Khumchoo, Vithid
    Khumsiri, Rasthapoom
    Ngamsanroaj, Kanchit
    Chimklai, Suthep
    Premrudeepreechacharn, Suttichai
    2019 IEEE PES GTD GRAND INTERNATIONAL CONFERENCE AND EXPOSITION ASIA (GTD ASIA), 2019, : 390 - 393
  • [9] FORENSIC EXAMINATION AND FAILURE ANALYSIS OF A 220 MV STEP-UP TRANSFORMER FIRE
    Ibrahim, Zuhair
    Stepan, Jeremiah
    Reza, Ali
    Slee, Daren
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2013, VOL 15, 2014,
  • [10] ULTRASONIC PULSER NEEDS NO STEP-UP TRANSFORMER
    GAMMELL, PM
    ELECTRONICS, 1978, 51 (15): : 120 - 121