Accurate Fault Location Method of Distribution Network with Limited Number of PMUs

被引:0
|
作者
Chen, Xi [1 ]
Jiao, Zaibin [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710000, Shaanxi, Peoples R China
关键词
Distribution network; PMU; the change of voltage along transmission line; fault location;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate fault location of distribution network is of great significance for improving the reliability of power supply and reducing the loss caused by continuous power outage. However, due to the distribution networks have multiple feeders and shorter lengths of each feeder, which are different from the transmission network, making it more difficult to locate faults. In this paper, based on the characteristics of the distribution network, an accurate fault location method of distribution network is developed using limited number of synchronization phase measurement units (PMUs). The method including two steps: First, based on the distribution parameter model, after the faults happen, the voltage and current information from the PMUs installed at the end of the line will be collected to calculate the voltage at the headend of the branching point, if the fault line exists fault branch, the headend voltage of the fault branch will be abnormal. Then, the fault distance could be calculated based on voltage distribution along the two ends of the fault branch. The effectiveness of the proposed algorithm is verified by electromagnetic transient simulation. The simulation result shows that the proposed algorithm only use limited number of PMUs to locate fault accurately without the need of PMUs on both ends of lines, which is not affected by transition resistance and fault type. Ensuring high accuracy, the proposed method is also very economic and has well application prospects.
引用
收藏
页码:1503 / 1507
页数:5
相关论文
共 50 条
  • [1] An accurate fault location method of smart distribution network
    Tan Zhihai
    Ge Liang
    Kang Taifeng
    Zhao Fengqing
    Zhao Yu
    Huang Xiaoyun
    Feng Feijin
    Li Xiang
    [J]. 2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [2] An analytical fault location method based on minimum number of installed PMUs
    Mortazavi, Seyed Hossein
    Sadeh, Javad
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2016, 26 (02): : 253 - 273
  • [3] Fault location of active distribution network with limited PMU
    Tao, Weiqing
    Xiao, Songqing
    Qin, Minghui
    Li, Lin
    Cao, Jun
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (04): : 112 - 120
  • [4] Distribution network fault location based on limited PMU configuration
    Yang, Rui
    Gao, Hongjun
    Liu, Junyong
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2022, 42 (04): : 138 - 145
  • [5] Research on Fault Location Method of Distribution Network
    He, Xiangzhen
    [J]. 6TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING, 2021, 647
  • [6] Robust Fault Location Method for Transmission Lines Using PMUs
    Tong, Xiaoyang
    Dong, Xingxing
    Manzoor, Sohail
    Wang, Yabing
    Zhao, Zibin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (04) : 2338 - 2347
  • [7] A Fault Location Method for Active Distribution Network with DGs
    Bao, Wenhong
    Fang, Qian
    Wang, Pin
    Yan, Wenqi
    Pan, Peng
    [J]. 2021 6TH INTERNATIONAL CONFERENCE ON SMART GRID AND ELECTRICAL AUTOMATION (ICSGEA 2021), 2021, : 6 - 10
  • [8] The Fault Location Method of Distribution Network with Fault Indicators Based on Impedance
    Hao, Xinpei
    Meng, Zhaoyong
    Huang, Wuhao
    Tao, Tao
    Wang, Yida
    [J]. PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON AUTOMATION, MECHANICAL CONTROL AND COMPUTATIONAL ENGINEERING, 2015, 124 : 386 - 391
  • [9] An accurate fault location method for distribution network based on active transfer arc-suppression device
    Qiao, Jian
    Yin, Xianggen
    Wang, Yikai
    Xu, Wen
    Tan, Liming
    [J]. ENERGY REPORTS, 2021, 7 : 552 - 560
  • [10] Accurate fault location method in distribution networks containing distributed generations
    Jamali, S.
    Talavat, V.
    [J]. Iranian Journal of Electrical and Computer Engineering, 2011, 10 (01): : 27 - 33