An Improved Grid Synchronization Control of Doubly-Fed Induction Generator

被引:0
|
作者
Zhan, Liangyu [1 ]
Jin, Xinmin [1 ]
Zhang, Lu [1 ]
机构
[1] Beijing Jiaotong Univ, Inst Renewable Energy, Beijing, Peoples R China
关键词
Wind power generation system; doubly-fed induction generator; synchronization control scheme; vector control;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The dynamic performance of Doubly-Fed Induction Generator (DFIG) before and after connection is analyzed based on corresponding mathematical models and transfer functions in decoupled vector control. The parameter tuning methods of rotor current regulator before and after connection are given. To reach same dynamic performance the parameters should take different values and be switched before and after connection. However on one hand the closing moment of stator contactor is difficult to get as the feedback signal is usually twenty millisecond delay or so. The delay in parameter switching will affect rotor current and torque dynamics after connection. On the other hand parameter switching is troublesome. Hence a synchronization control strategy without parameter switching is proposed and analyzed in detail, which has linear rising exciting current to avoid current overshooting. The dynamic performance of the proposed strategy is analyzed in frequency domain and implemented on a DFIG experimental platform subsequently. The proposed synchronization strategy in the paper is validated by experimental results.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] A Novel Grid Synchronization Control of Doubly-fed Induction Generator
    ZHAN Liang-yu
    [J]. 电力电子技术, 2012, 46 (04) : 38 - 42
  • [2] Control method of a doubly-fed induction generator with automatic grid synchronization
    Park, Jungwoo
    Lee, Kiwook
    Kim, Dongwook
    [J]. IECON 2006 - 32ND ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS, VOLS 1-11, 2006, : 1093 - +
  • [3] Grid Synchronization of Doubly-fed Induction Generator Using Integral Variable Structure Control
    Chen, Si Zhe
    Cheung, Norbert C.
    Wong, Ka Chung
    Wu, Jie
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2009, 24 (04) : 875 - 883
  • [4] Unified Grid Integration Algorithm for Synchronization and Power Control of Doubly-Fed Induction Generator
    Nair, Ramu R.
    Narayanan, G.
    [J]. THIRTY-FOURTH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC 2019), 2019, : 1829 - 1834
  • [5] Grid Synchronization of Doubly-Fed Induction Generator System Using Current Vector Control
    Mueangngoen, Sutthimat
    Kumsuwan, Yuttana
    [J]. 2018 15TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING/ELECTRONICS, COMPUTER, TELECOMMUNICATIONS AND INFORMATION TECHNOLOGY (ECTI-CON), 2018, : 752 - 755
  • [6] Grid-Flux-Oriented Control and Synchronization for a Doubly-Fed Induction Generator System
    Mueangngoen, Sutthimat
    Kumsuwan, Yuttana
    [J]. TENCON 2017 - 2017 IEEE REGION 10 CONFERENCE, 2017, : 1257 - 1262
  • [7] Improved Demagnetization Control of a Doubly-Fed Induction Generator Under Balanced Grid Fault
    Zhou, Linyuan
    Liu, Jinjun
    Zhou, Sizhan
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (12) : 6695 - 6705
  • [8] Improved Grid Synchronization Control of Doubly Fed Induction Generator Under Unbalanced Grid Voltage
    Chen, Si Zhe
    Cheung, Norbert C.
    Zhang, Yun
    Zhang, Miao
    Tang, Xiong Min
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (03) : 799 - 810
  • [9] An encoder-free grid synchronization method for a doubly-fed induction generator
    Park, Jungwoo
    Lee, Kiwook
    Kim, Dongwook
    Lee, Kwangsoo
    Park, Jinsoon
    [J]. 2007 EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS, VOLS 1-10, 2007, : 3602 - +
  • [10] Direct voltage control for grid synchronization of doubly-fed induction generators
    Wong, K. C.
    Ho, S. L.
    Cheng, K. W. E.
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2008, 36 (09) : 960 - 976