A robust fault detection and diagnosis strategy for centrifugal chillers

被引:65
|
作者
Wang, SW [1 ]
Cui, JT
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Danfoss Shanghai Automat Controls Co Ltd, Shanghai, Peoples R China
来源
HVAC&R RESEARCH | 2006年 / 12卷 / 03期
关键词
D O I
10.1080/10789669.2006.10391187
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a robust fault detection and diagnosis (FDD) strategy for centrifugal chillers. The strategy consists of a model-based chiller FDD scheme and a sensor fault detection, diagnosis, and estimation (FDD&E) scheme, which handle chiller faults and sensor faults, respectively. The sensor FDD&E scheme uses a PCA-based method (principal component analysis) to capture the correlations among the major measured variables in centrifugal chillers, as it performs well even in the presence of typical chiller faults. The chiller FDD scheme has been developed based on six physical performance indices, which are capable of describing the health condition of centrifugal chillers and, thus, indicating chiller faults. Only after all the sensors whose measurements are crucial to the chiller FDD are validated by the sensor FDD&E scheme is the chiller FDD scheme used to conduct the chiller system FDD. The strategy was validated using laboratory data from ASHRAE RP-1043 and field data from a centrifugal chiller in a real building.
引用
收藏
页码:407 / 428
页数:22
相关论文
共 50 条
  • [21] A model-based online fault detection and diagnosis strategy for centrifugal chiller systems
    Cui, JT
    Wang, SW
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (10) : 986 - 999
  • [22] Data-driven Fault Detection and Diagnosis for HVAC water chillers
    Beghi, A.
    Brignoli, R.
    Cecchinato, L.
    Menegazzo, G.
    Rampazzo, M.
    Simmini, F.
    [J]. CONTROL ENGINEERING PRACTICE, 2016, 53 : 79 - 91
  • [23] Fault detection, diagnosis and data-driven modeling in HVAC chillers
    Namburu, SM
    Luo, JH
    Azam, M
    Choi, K
    Pattipati, KR
    [J]. Signal Processing, Sensor Fusion, and Target Recognition XIV, 2005, 5809 : 143 - 154
  • [24] EVALUATION OF THE SIMPLE THERMODYNAMIC MODEL (GORDON AND NG UNIVERSAL CHILLER MODEL) AS A FAULT DETECTION AND DIAGNOSIS TOOL FOR ON-SITE CENTRIFUGAL CHILLERS
    Saththasivam, Jayaprakash
    Tang, Gary
    Chan, Chow Kiat
    Ng, Kim Choon
    [J]. ACRA 2009: PROCEEDINGS OF THE 4TH ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, 2009, : 16 - 21
  • [25] EVALUATION OF THE SIMPLE THERMODYNAMIC MODEL (GORDON AND NG UNIVERSAL CHILLER MODEL) AS A FAULT DETECTION AND DIAGNOSIS TOOL FOR ON-SITE CENTRIFUGAL CHILLERS
    Saththasivam, Jayaprakash
    Tang, Gary
    Ng, Kim Choon
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2010, 18 (01) : 55 - 60
  • [26] A statistical fault detection and diagnosis method for centrifugal chillers based on exponentially-weighted moving average control charts and support vector regression
    Zhao, Yang
    Wang, Shengwei
    Xiao, Fu
    [J]. APPLIED THERMAL ENGINEERING, 2013, 51 (1-2) : 560 - 572
  • [27] A robust fault detection and diagnosis strategy for multiple faults of VAV air handling units
    Wang, Haitao
    Chen, Youming
    [J]. ENERGY AND BUILDINGS, 2016, 127 : 442 - 451
  • [28] An approach to optimally robust fault detection and diagnosis
    Nazih, M
    Michel, V
    [J]. PROCEEDINGS OF THE 2001 IEEE INTERNATIONAL CONFERENCE ON CONTROL APPLICATIONS (CCA'01), 2001, : 94 - 100
  • [29] Robust Fault Detection and Diagnosis for Multimode Processes
    Zuqui, Gercilio C., Jr.
    Rauber, Thomas W.
    Munaro, Celso J.
    Trancoso, Victor G.
    [J]. 2016 12TH IEEE/IAS INTERNATIONAL CONFERENCE ON INDUSTRY APPLICATIONS (INDUSCON), 2016,
  • [30] Characteristic physical parameter approach to modeling chillers suitable for fault detection, diagnosis, and evaluation
    Jia, YZ
    Reddy, TA
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (03): : 258 - 265