A Principle of Fault Line Selection Based on Increasing Zero-sequence Current in Non-ground Neutral System

被引:0
|
作者
Huang, Tantan [1 ]
Zhang, Huifen [1 ]
Gao, Zhipeng [2 ]
Guo, Yao [3 ]
机构
[1] Univ Jinan, Sch Elect Engn, Jinan, Shandong, Peoples R China
[2] SINOPEC Shengli Oilfield Co, Elect Serv Ctr, Dongying, Peoples R China
[3] Shandong Univ Technol, Coll Elect & Elect Engn, Zibo, Peoples R China
关键词
non-ground neutral system; single-phase earth fault; principle of fault line selection based on increasing zero-sequence current (IZC); power capacitor used for increasing zero-sequence current;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to solve the problem of low accuracy of single-phase earth fault selection in non-ground neutral system, in this paper, the method that increasing the zero current of fault line at a short time when the single-phase earth fault occurs is proposed by using injection principle to strengthen the fault steady-state characteristic so as to expand the gap of circuit criterion between the fault line and the non-fault line, meanwhile, improve the selection criterion based on fault steady-state characteristics. According to the single-phase earth fault steady-state characteristics of zero-sequence current, the power capacitor is used to inject the capacitance current to realize the increase. Depending on the principle of not affecting the operation of distribution network, the strength of the increased current is determined. Such equipment has been implemented in power networks, and the result of detecting fault line is accurately.
引用
收藏
页码:2052 / 2056
页数:5
相关论文
共 50 条
  • [1] Fault Line Selection Principle of Single-phase-to-ground Fault Based on Improved Zero-sequence Admittance
    Luan X.
    Wu S.
    Jia C.
    Yang Y.
    Zhang Z.
    Luo X.
    Dianwang Jishu/Power System Technology, 2022, 46 (01): : 353 - 360
  • [2] A new method for fault line selection based on correlation between zero-sequence voltage in bus and zero-sequence current in feeders
    Xiang, Yunkun
    Jiang, Yun
    Ning, Yuanzhi
    Tao, Fang
    Liu, Bohan
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1196 - 1199
  • [3] Single-phase ground fault line selection method of small current grounding system of multiple zero-sequence current transformer based on compensation parameters
    Zhang G.
    Zhang W.
    Ge Q.
    Xu L.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (02): : 1 - 9
  • [4] Fault line selection device for non-solid earthed network based on transient zero-sequence current features
    Xu, Jingdong
    Zhang, Baohui
    You, Min
    Yan, Haishan
    Liu, Haifeng
    Yang, Lu
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2009, 29 (04): : 101 - 105
  • [5] Single Phase To Ground Fault Location Based On Phase Of Zero-sequence Current
    Li Jinjie
    Qi Yulin
    Gao Qiaomei
    Sun Shihao
    2013 IEEE INTERNATIONAL CONFERENCE ON INFORMATION AND AUTOMATION (ICIA), 2013, : 856 - 859
  • [6] Single-phase grounding fault line selection method based on zero-sequence current increment
    Hao, Bai
    ENERGY REPORTS, 2022, 8 : 305 - 312
  • [7] Ground-fault protection based on active component of zero-sequence current in resistance neutral grounded distribution systems
    Mu, LH
    Meng, QH
    2002 IEEE REGION 10 CONFERENCE ON COMPUTERS, COMMUNICATIONS, CONTROL AND POWER ENGINEERING, VOLS I-III, PROCEEDINGS, 2002, : 1897 - 1900
  • [8] Principle of Flexible Ground-Fault Arc Suppression Device Based on Zero-Sequence Voltage Regulation
    Fan, Bishuang
    Yao, Ganzhou
    Yu, Kun
    Zeng, Xiangjun
    Wang, Wen
    Zhuo, Chao
    Guerrero, Josep M.
    IEEE ACCESS, 2021, 9 : 2382 - 2389
  • [9] Zero-sequence current differential phase selection based on three-sequence differential currents similar principle
    Liu, Huanzhang
    Wang, Xingguo
    Li, Ming
    Zhou, Zexin
    Du, Dingxiang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2013, 37 (16): : 92 - 95
  • [10] Fault line selection method of grounding fault with high resistance in resonant grounding system based on intensive zero-sequence impedance characteristics
    Shao W.
    Liu Y.
    Cheng Y.
    Zhang Z.
    Cheng C.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (11): : 120 - 126