MV/LV parallel transformers: an experimental study on circulating currents

被引:0
|
作者
Calcara, Luigi [1 ]
Maccioni, Marco [1 ]
Pompili, Massimo [1 ]
机构
[1] Univ Roma La Sapienza, Rome, Italy
关键词
MV/LV; transformers; circulation current; electrical resilience;
D O I
10.1109/EEEIC/ICPSEUROPE54979.2022.9854775
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
When a high value load is to be supplied and greater system reliability is required, the medium voltage power supply is generally used with a low voltage conversion by means of two or more MV/LV transformers. This configuration is also more suitable for maintenance or resilience aspects. In Europe, in case of use of these distribution transformers, the windings configuration is Delta (primary winding) and Star (secondary winding). To obtain a common ground reference for the three phases and neutral system, the star point is grounded. In case of parallel transformers, this ground point is common. Furthermore, when using transformers in parallel, a proportional reduction of the short-circuit impedance is obtained with the consequent increase in the short-circuit current during faults and the need to adopt cables and protections that consider this aspect. From the other hands, the use of parallel transformers may introduce an increasing of the no load losses. In transformers parallel configuration system, if the transformation ratios are not identical, a circulation current is generated. This current is proportional to the voltage difference divided by the sum of the impedances along the path comprising windings and ground connections of the star centers. In a distribution substation with two parallel transformers of identical characteristics, the circulating currents in each transformer are of equal amplitude and in opposite directions. Few studies have investigated what happens at the connection points between the star centers of the transformers and the earth bar of the secondary substations. This paper gives a contribution on the evaluation of the circulating currents based both on theoretical considerations and experimental measurements.
引用
收藏
页数:4
相关论文
共 50 条
  • [11] Current Transformers Effects on the Measurement of Harmonic Active Power in LV and MV Networks
    Cataliotti, Antonio
    Di Cara, Dario
    Emanuel, Alexander E.
    Nuccio, Salvatore
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) : 360 - 368
  • [12] Estimation of Year Peak Loads of MV/LV Transformers Using PSO Algorithms
    Baczynski, Dariusz
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (08): : 96 - 98
  • [13] Ageing Diagnosis of MV/LV Distribution Transformers via Chemical Indicators in Oil
    Laurichesse, Delphine
    Bertrand, Yves
    Chau Tran-Duy
    Murin, Valerie
    2013 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2013, : 464 - 468
  • [14] Experimental Study of the Parameter Mismatch Effects on the Low Frequency Circulating Currents of Parallel Three Phase Inverters
    Liberos, Marian
    Gonzalez-Medina, Raul
    Patrao, Ivan
    Toran, Enric
    Garcera, Gabriel
    Figueres, Emilio
    ENG, 2023, 4 (02): : 1356 - 1376
  • [15] Selection of MV/LV Transformers to be Protected by Surge Arresters against Indirect Lightning Overvoltages
    Borghetti, Alberto
    Napolitano, Fabio
    Nucci, Carlo Alberto
    Tossani, Fabio
    Dos Santos, Gilnei J. G.
    Fagundes, Donorvan R.
    Lopes, Gustavo P.
    Martinez, Manuel L. B.
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 1891 - 1896
  • [16] Design and Performance Evaluation of a High-Impedance REF Scheme for MV/LV Transformers
    Apostolopoulos, Christos
    Tsakiris, Dimitris
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 5398 - 5409
  • [17] Siting, Sizing, Timing and Determining the Service Area of MV/LV Transformers: A Novel Approach
    Hana Jannaty
    Jamal Moshtagh
    Arabian Journal for Science and Engineering, 2012, 37 : 683 - 695
  • [18] Siting, Sizing, Timing and Determining the Service Area of MV/LV Transformers: A Novel Approach
    Jannaty, Hana
    Moshtagh, Jamal
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2012, 37 (03) : 683 - 695
  • [19] An Enhanced Model for Siting, Sizing, Timing and Determining the Service Area of MV/LV Transformers
    Moshtagh, Jamal
    Jannaty, Hannah
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [20] Implementation and Experimental Tests of a Management System for MV/LV Distribution Grids
    Artale, G.
    Cataliotti, A.
    Cosentino, V
    Di Cara, D.
    Guaiana, S.
    Panzavecchia, N.
    Tine, G.
    7TH INTERNATIONAL CONFERENCE ON CLEAN ELECTRICAL POWER (ICCEP 2019): RENEWABLE ENERGY RESOURCES IMPACT, 2019, : 76 - 81