Pretreatment Method for Immunoassay of Polychlorinated Biphenyls in Transformer Oil Using Multi layer Capillary Column and Microfluidic Liquid-Liquid Partitioning

被引:3
|
作者
Aota, Arata [1 ]
Date, Yasumoto [1 ,2 ]
Terakado, Shingo [1 ]
Ohmura, Naoya [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Environm Sci Res Lab, Abiko, Chiba 2701194, Japan
[2] Tohoku Univ, Grad Sch Environm Studies, Aoba Ku, Sendai, Miyagi 9808579, Japan
关键词
PCBS;
D O I
10.2116/analsci.29.393
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Polychlorinated biphenyls (PCBs) are persistent organic pollutants that are present in the insulating oil inside a large number of transformers. To aid in eliminating PCB-Contaminated transformers, PCBs in oil need to be measured using a rapid and cost-effective analytical method. We previously reported a pretreatment method for the immunoassay of PCBs in oil using a large-scale multilayer column and a microchip with multiple microrecesses, which permitted concentrated solvent extraction. In this paper, we report on a more rapid and facile pretreatment method, without an evaporation process, by improving the column and the microchip. In a miniaturized column, the decomposition and separation of oil were completed in 2 min. PCBs can be eluted from the capillary column at concentrations seven-times higher than those from the previous column. The total volume of the microrecesses was increased by improving the microrecess structure, the enabling extraction of four-times the amount of PCBs achieved with the previous system. By interfacing the capillary column with the improved microchip, PCBs in the eluate from the column were extracted into dimethyl sulfoxide in microrecesses with high enrichment and without the need for evaporation. Pretreatment was completed within 20 min The pretreated oil was analyzed using a flow-based kinetic exclusion immunoassay. The limit of detection of PCBs in oil was 0.15 mg kg(-1), which satisfies the criterion set in Japan of 0.5 mg kg(-1).
引用
收藏
页码:393 / 399
页数:7
相关论文
共 50 条
  • [1] Pretreatment Method for Immunoassay of Polychlorinated Biphenyls in Transformer Oil Using Multilayer Capillary Column and Microfluidic Liquid-Liquid Partitioning
    Arata Aota
    Yasumoto Date
    Shingo Terakado
    Naoya Ohmura
    Analytical Sciences, 2013, 29 : 393 - 399
  • [2] Analysis of polychlorinated biphenyls in transformer oil by using liquid-liquid partitioning in a microfluidic device
    Biotechnology Sector, Central Research Institute of Electric Power Industry, 1646 Abiko, Abiko City, Chiba, 270-1194, Japan
    Anal. Chem., 20 (7834-7840):
  • [3] Analysis of Polychlorinated Biphenyls in Transformer Oil by Using Liquid-Liquid Partitioning in a Microfluidic Device
    Aota, Arata
    Date, Yasumoto
    Terakado, Shingo
    Sugiyama, Hideo
    Ohmura, Naoya
    ANALYTICAL CHEMISTRY, 2011, 83 (20) : 7834 - 7840
  • [4] Immunoassay screening method for polychlorinated biphenyls in transformer oil
    Ohmura, Naoya
    Glass, Thomas R.
    Sasaki, Kazuhiro
    Joh, Takashi
    Taemi, Yukihiro
    Imanishi, Katsuya
    Terakado, Shingo
    BUNSEKI KAGAKU, 2006, 55 (07) : 519 - 523
  • [5] Screening method for rapid determination of polychlorinated biphenyls in transformer oil by liquid-liquid extraction and gas chromatography-mass spectrometry
    Toledo, Carla
    Valle, Luis
    Narvaez, Jessica
    Richter, Pablo
    JOURNAL OF THE BRAZILIAN CHEMICAL SOCIETY, 2007, 18 (05) : 937 - 942
  • [6] New Antibody and Immunoassay Pretreatment Strategy to Screen Polychlorinated Biphenyls in Korean Transformer Oil
    Shingo Terakado
    Naoya Ohmura
    Seok-Un Park
    Seung-Min Lee
    Thomas R. Glass
    Analytical Sciences, 2013, 29 : 963 - 969
  • [7] New Antibody and Immunoassay Pretreatment Strategy to Screen Polychlorinated Biphenyls in Korean Transformer Oil
    Terakado, Shingo
    Ohmura, Naoya
    Park, Seok-Un
    Lee, Seung-Min
    Glass, Thomas R.
    ANALYTICAL SCIENCES, 2013, 29 (10) : 963 - 969
  • [8] Development of a dispersive liquid-liquid microextraction method for the determination of polychlorinated biphenyls in water
    Rezaei, Faterneh
    Bidari, Araz
    Birjandi, Afsoon Pajand
    Hosseini, Mohammad Reza Milani
    Assadi, Yaghoub
    JOURNAL OF HAZARDOUS MATERIALS, 2008, 158 (2-3) : 621 - 627
  • [9] LIQUID GEL PARTITIONING USING LIPIDEX IN THE DETERMINATION OF POLYCHLORINATED-BIPHENYLS IN COD LIVER OIL
    WEISTRAND, C
    NOREN, K
    JOURNAL OF CHROMATOGRAPHY, 1993, 630 (1-2): : 179 - 186
  • [10] The liquid-liquid diffusive extraction of hydrocarbons from a North Sea oil using a microfluidic format
    Bowden, S. A.
    Monaghan, P. B.
    Wilson, R.
    Parnell, J.
    Cooper, J. M.
    LAB ON A CHIP, 2006, 6 (06) : 740 - 743