Ultrasonic localization of Partial Discharge in Power Transformer Based on Improved Genetic Algorithm

被引:0
|
作者
Ren, Shuangzan
Yang, Xu
Zhu, Ruihua
Xi, Baofeng
Cao, Xiaolong
机构
关键词
Transformer; Partial discharge; Ultrasonic; Location; Improved genetic algorithm;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge is one of the main reasons for degradation of power transformer, ultrasonic method has attracted attention for its anti-interference ability and convenience of location for partial discharge measuring. Resorting to the method of electrical-mechanical-ultrasonic analogy, an equivalent circuit for partial discharge-generated ultrasonic waves based on model of gap is established, and an ultrasonic-ultrasonic locating method based on improved genetic algorithm which takes the equivalent velocity of ultrasonic as a variable is introduced in this paper. Besides, the relationship between ultrasonic intensity of pressure and apparent discharge magnitude is discussed and the accuracy and feasibility of this ultrasonic location model has been demonstrated by the laboratory data.
引用
收藏
页码:99 / 99
页数:1
相关论文
共 50 条
  • [21] Study of partial discharge localization using ultrasonics in power transformer based on particle swarm optimization
    Tang, Lijun
    Luo, Richeng
    Deng, Min
    Su, Jun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) : 492 - 495
  • [22] A Partial Discharge Localization Method for AC XLPE Cable Based on Improved GCC Algorithm
    Guo, Maosen
    Xu, Jiajie
    Zhang, Yi
    Xiao, Xiaolong
    Yang, Zhencheng
    Wu, Zaijun
    IEEE OPEN ACCESS JOURNAL OF POWER AND ENERGY, 2023, 10 : 605 - 616
  • [23] Partial discharge localization in power transformer tanks using machine learning methods
    Khodaveisi, Farzin
    Karami, Hamidreza
    Karimpour, Matin Zarei
    Rubinstein, Marcos
    Rachidi, Farhad
    SCIENTIFIC REPORTS, 2024, 14 (01):
  • [24] Partial Discharge Localization and Classification Using Acoustic Emission Analysis in Power Transformer
    Mohammadi, Ezatollah
    Niroomand, Mehdi
    Rezaeian, Mandie
    Amini, Zahra
    INTELEC 09 - 31ST INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE, 2009, : 1186 - 1191
  • [25] Single-Sensor Based Acoustic Time Reversal Technique for Partial Discharge Localization in Power Transformer
    Rathod, Viral B.
    Kumbhar, Ganesh B.
    Bhalja, Bhavesh R.
    PROCEEDINGS OF 2021 5TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (IEEE CATCON 2021), 2021, : 151 - 156
  • [26] Application in transformer partial discharge location of improved particle swarm optimization algorithm
    Wang, B. (nxwbo@163.com), 1785, Binary Information Press (10):
  • [27] A Technique Based on an Archimedean Copula for the Localization of Partial Discharge in a Transformer Winding
    Mondal, Mithun
    Kumbhar, G. B.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (05) : 2908 - 2916
  • [28] Research on Transformer Partial Discharge Fault Location Based on Improved UCA-RB-MUSIC Algorithm
    Lv, Yanling
    Ai, Kexian
    Guo, Feng
    IEEE ACCESS, 2024, 12 : 16299 - 16309
  • [29] Study on Partial Discharge detection of power transformer based on AVR
    Guo, J
    Shu, W
    Zhang, XQ
    Gao, B
    Wang, P
    Wu, GN
    Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 522 - 525
  • [30] Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization
    She C.
    Zheng J.
    He J.
    Chen H.
    Ma Z.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (08): : 2820 - 2827