Validation of a simple method for predicting the disinfection performance in a flow-through contactor

被引:10
|
作者
Pfeiffer, Valentin [1 ]
Barbeau, Benoit [1 ]
机构
[1] Polytech Montreal, Civil Geol & Min Engn Dept, Ind NSERC Chair Drinking Water, Montreal, PQ H3C 3A7, Canada
关键词
Disinfection calculation method; Escherichia coli inactivation; Chlorine contactor; T10; method; N-CSTR model; Segregated Flow Analysis; SCALE OZONE CONTACTOR; INACTIVATION; KINETICS; SYSTEMS; DESIGN; MODEL;
D O I
10.1016/j.watres.2013.11.003
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Despite its shortcomings, the T10 method introduced by the United States Environmental Protection Agency (USEPA) in 1989 is currently the method most frequently used in North America to calculate disinfection performance. Other methods (e.g., the Integrated Disinfection Design Framework, IDDF) have been advanced as replacements, and more recently, the USEPA suggested the Extended T10 and Extended CSTR (Continuous Stirred-Tank Reactor) methods to improve the inactivation calculations within ozone contactors. To develop a method that fully considers the hydraulic behavior of the contactor, two models (Plug Flow with Dispersion and N-CSTR) were successfully fitted with five tracer tests results derived from four Water Treatment Plants and a pilot-scale contactor. A new method based on the N-CSTR model was defined as the Partially Segregated (Pseg) method. The predictions from all the methods mentioned were compared under conditions of poor and good hydraulic performance, low and high disinfectant decay, and different levels of inactivation. These methods were also compared with experimental results from a chlorine pilot-scale contactor used for Escherichia coli inactivation. The T10 and Extended T10 methods led to large over- and under-estimations. The Segregated Flow Analysis (used in the IDDF) also considerably overestimated the inactivation under high disinfectant decay. Only the Extended CSTR and Pseg methods produced realistic and conservative predictions in all cases. Finally, a simple implementation procedure of the Pseg method was suggested for calculation of disinfection performance. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:144 / 156
页数:13
相关论文
共 50 条
  • [31] The half notching method for Flow-through lymphaticovenular anastomosis
    Furuya, Megumi
    Yamamoto, Takumi
    Yamashita, Marie
    Hayashi, Akitatsu
    MICROSURGERY, 2015, 35 (05) : 415 - 416
  • [32] Accelerated Method for Designing Flow-Through Chromatography of Proteins
    Hasegawa, Sumiko
    Chen, Chyi-Shin
    Yoshimoto, Noriko
    Yamamoto, Shuichi
    JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 2020, 53 (05) : 206 - 213
  • [33] Modeling Cryptosporidium parvum oocyst inactivation and bromate in a flow-through ozone contactor treating natural water
    Kim, Jae-Hong
    Elovitz, Michael S.
    von Gunten, Urs
    Shukairy, Hiba M.
    Marinas, Benito J.
    WATER RESEARCH, 2007, 41 (02) : 467 - 475
  • [34] Validation of a flow-through sampler for pesticides and polybrominated diphenyl ethers in air
    Xiao, Hang
    Hung, Hayley
    Lei, Ying Duan
    Wania, Frank
    ATMOSPHERIC ENVIRONMENT, 2009, 43 (15) : 2401 - 2409
  • [36] A simple and inexpensive control of relative humidity in a flow-through environmental chamber
    Hannusch, DJ
    James, TDW
    Gillespie, TJ
    Boland, GJ
    ENVIRONMENTAL AND EXPERIMENTAL BOTANY, 1995, 35 (03) : 411 - 415
  • [37] Electrochemical flow-through disinfection of Escherichia coli versus Staphylococcus aureus: Identifying impacts of flow patterns on efficiency
    Wang, Peiheng
    Shi, Huanhuan
    Zhang, Kehao
    Han, Yuran
    Zhang, Wei
    Wang, Beibei
    Wang, Hailong
    Liu, Shiliang
    Huang, Qingguo
    Gao, Shixiang
    CHEMICAL ENGINEERING JOURNAL, 2024, 497
  • [38] Performance of stacked, flow-through micropreconcentrators for portable trace detection
    Martin, Michael D.
    Roussel, Thomas J.
    Cambron, Scott
    Aebersold, Julia
    Jackson, Douglas
    Walsh, Kevin
    Lin, Ji-Tzuoh
    O'Toole, Martin G.
    Keynton, Robert
    INTERNATIONAL JOURNAL FOR ION MOBILITY SPECTROMETRY, 2010, 13 (3-4) : 109 - 119
  • [39] THE PERFORMANCE OF SOME LIQUID-PHASE FLOW-THROUGH DETECTORS
    POPPE, H
    ANALYTICA CHIMICA ACTA, 1983, 145 (JAN) : 17 - 26
  • [40] Validation of a Method for Predicting Anechoic Chamber Performance
    Rodriguez, Vince
    IEEE ANTENNAS AND PROPAGATION MAGAZINE, 2018, 60 (04) : 31 - 40