Experimental investigation of negative DC corona on conductor bundles: A comparison with positive corona

被引:0
|
作者
Bousiou, E. I. [1 ]
Mikropoulos, P. N. [1 ]
Zagkanas, V. N. [1 ]
机构
[1] Aristotle Univ Thessaloniki, Sch Elect & Comp Engn, Fac Engn, High Voltage Lab, Thessaloniki 54124, Greece
关键词
Conductor bundles; corona; direct current; electrical discharges; overhead lines; power losses; transmission; SURFACE CONDITIONS; COAXIAL CYLINDERS; PROGRESS REPORT; SPACE-CHARGE; TEST LINE; AIR; MOBILITY; IONS; HUMIDITY; LOSSES;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Negative DC corona on conductor bundles is experimentally investigated in the coaxial configuration. The dependence of the corona characteristics, namely inception voltage and current, thus also inception field and power losses, on bundle radius and number of conductors in the bundle is assessed. The corona inception voltage of conductor bundles is highest at a bundle radius that corresponds to the minimum electric field strength at the conductor surface. The corona inception field strength of conductor bundles can be considered, with reasonable accuracy, as equal to that of the single conductor. Polarity effects on DC corona characteristics are assessed through comparisons with positive DC corona. For both polarities of applied voltage, the corona current can be accurately estimated through a modified Townsend quadratic formula using appropriate values for ion mobility.
引用
收藏
页数:5
相关论文
共 50 条
  • [31] HVDC MONOPOLAR AND BIPOLAR CAGE STUDIES ON THE CORONA PERFORMANCE OF CONDUCTOR BUNDLES
    DALLAIRE, RD
    MARUVADA, PS
    RIVEST, N
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (01): : 84 - 91
  • [32] An experimental investigation on corona quenching
    Riebel, U
    Radtke, R
    Loos, R
    [J]. JOURNAL OF ELECTROSTATICS, 2002, 54 (02) : 159 - 165
  • [33] Experimental and theoretical study on the influence of bundle number on corona loss characteristics of ultra high voltage corona cage positive/ negative DC conductors at high altitude
    Xue, Weiye
    Huang, Shilong
    Mao, Jie
    Yan, Xiaoliang
    Song, Chenming
    Liu, Yunpeng
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2024, 232
  • [34] Comparison between Positive and Negative Corona Discharges by Hydrodynamic Plasma Simulations
    Zogning, Calvin
    Lobry, Jacques
    Moiny, Francis
    [J]. PROCEEDINGS OF 2020 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2020), 2020, : 552 - 560
  • [35] AGING EFFECTS OF CONDUCTOR SURFACE CONDITIONS ON DC CORONA CHARACTERISTICS
    SUDA, T
    HIRAYAMA, Y
    SUNAGA, Y
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) : 1903 - 1912
  • [36] AN INVESTIGATION OF A POSITIVE CORONA DISCHARGE IN HELIUM
    BORTNIK, IM
    [J]. SOVIET PHYSICS TECHNICAL PHYSICS-USSR, 1965, 9 (09): : 1299 - &
  • [37] Laboratory Investigation of AC Corona Loss and Corona Onset Voltage on a Conductor under Icing Conditions
    Yin, Fanghui
    Farzaneh, Masoud
    Jiang, Xingliang
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) : 1862 - 1871
  • [38] An experimental study of relative humidity and air flow effects on positive and negative corona discharges in a corona-needle charger
    Yawootti, Artit
    Intra, Panich
    Tippayawong, Nakorn
    Rattanadecho, Phadungsak
    [J]. JOURNAL OF ELECTROSTATICS, 2015, 77 : 116 - 122
  • [39] Experimental Study on Spectral Characteristics of Corona-Generated Audible Noise From a DC Conductor
    Li, Xuebao
    Cui, Xiang
    Lu, Tiebing
    Wang, Jing
    Hiziroglu, H. R.
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2018, 46 (10) : 3690 - 3699
  • [40] Comparison of laser induced streamers to regular streamers in the positive DC corona discharge
    Kocik, M
    Mizeraczyk, J
    Ohkubo, T
    Kanazawa, S
    [J]. 13th International School on Quantum Electronics: Laser Physics and Applications, 2005, 5830 : 130 - 134