The impact of atrium shape on natural smoke ventilation

被引:16
|
作者
Doheim, R. M. [1 ]
Yohanis, Y. G. [1 ]
Nadjai, A. [1 ]
Elkadi, H. [2 ]
机构
[1] Univ Ulster, Fac Art Design & Built Environm, Sch Built Environm, Belfast BT37 0QB, Antrim, North Ireland
[2] Deakin Univ, Sch Architecture & Built Environm, Fac Sci Engn & Built Environm, Melbourne, Vic, Australia
关键词
Atrium; Natural smoke ventilation; Smoke filling; FDS; FIRE; CORRIDOR; HEIGHT; TESTS; TIME; MW;
D O I
10.1016/j.firesaf.2013.11.005
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The performance efficiency of natural smoke ventilation in atria spaces are influenced greatly by several design decisions such as atrium shape, height, size and openings location. This paper investigates the impact of atrium shape (horizontal profile) on smoke ventilation performance in naturally ventilated atria. Three different configurations (square, rectangular and triangular prism) with the same area, height, and hence, volume were tested. The smoke ventilation performance is being assessed in terms of smoke filling time using a computational fire dynamic simulator (FDS). FDS is used to simulate the natural smoke filling resulting from atrium fire in the three configurations. The smoke layer interface height as a function of time and soot mass fraction and temperature as a function of height have been registered during the simulation. The predicted transport lag time for initial formation of the smoke layer beneath the ceiling (ceiling jet) was compared for the three tests. In order to test sensitivity of the shapes, all other parameters were designed to be similar in the three tests, and the same fire scenario was applied including inlet and outlet area, and fire size and location. The results showed that the rectangular configuration contributes better to smoke ventilation, and that the triangular configuration is the most critical in terms of smoke filling time, followed by the square configuration. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:9 / 16
页数:8
相关论文
共 50 条
  • [41] Effects of "wall angularity of atrium" on "buildings natural ventilation and thermal performance" and CFD model
    Fini, Ali Shafiei
    Moosavi, Ali
    ENERGY AND BUILDINGS, 2016, 121 : 265 - 283
  • [42] Numerical studies of displacement natural ventilation in multi-storey buildings connected to an atrium
    Ji, Y.
    Cook, M. J.
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2007, 28 (03): : 207 - 222
  • [43] Using helium smoke as a surrogate of fire smoke for the study of atrium smoke filling
    Zhao, Guanchao
    Wang, Liangzhu
    JOURNAL OF FIRE SCIENCES, 2014, 32 (05) : 431 - 447
  • [44] Atrium smoke exhaust and technical issues on hot smoke tests
    Chow, W. K.
    HT2005: Proceedings of the ASME Summer Heat Transfer Conference 2005, Vol 1, 2005, : 683 - 687
  • [45] Effect of unpowered ventilation caps and shaft parameters on fire smoke spread in the natural ventilation tunnel with shafts
    Zhao, Xueqian
    Chi, Junwei
    Luo, Huan
    Zhou, Ru
    Hao, Min
    Jiang, Juncheng
    JOURNAL OF BUILDING ENGINEERING, 2024, 87
  • [46] Tenability Analysis and Atrium Smoke Control
    Klote, John H.
    2017 ASHRAE ANNUAL CONFERENCE PAPERS, 2017,
  • [47] On atrium smoke management system design
    Chow, WK
    Li, J
    ASHRAE Transactions 2005, Vol 111, Pt 1, 2005, 111 : 395 - 406
  • [48] Atrium Smoke Management in Commercial Buildings
    Ahmed, M. M. S.
    Khalil, E. E.
    Hassan, M. M. A.
    Haridi, H. O.
    2018 ASHRAE WINTER CONFERENCE, 2018,
  • [49] The Impact of Urban Wind Environments on Natural Ventilation
    Turkbeyler, Erdal
    Yao, Runming
    Nobile, Rosario
    Bentham, Tom
    Lim, David
    INTERNATIONAL JOURNAL OF VENTILATION, 2012, 11 (01) : 17 - 28
  • [50] Study on the smoke layer height in subway platform fire under natural ventilation
    Long, Zeng
    Chen, Junfeng
    Qiu, Peiyun
    Zhong, Maohua
    JOURNAL OF BUILDING ENGINEERING, 2022, 56