Accurate modelling of field stresses in an unshielded three-core power cable

被引:4
|
作者
Ismail, HM
机构
[1] Elec. Power and Machines Department, Faculty of Engineering, Ain Shams University, Cairo
关键词
unshielded conductors; power cables; electric field calculations; charge simulation method; discharge activities;
D O I
10.1016/S0378-7796(96)01087-5
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper uses the charge simulation technique to calculate the potential and electric field stress distribution at the surfaces of the conductors and the dielectric of an unshielded three-core power cable. The conductors and the sheath are simulated by a suitable finite number of complex line charges. The unshielded three-core cable is placed on a grounded plane and at varying heights above it to calculate the electric field as a function of the height of the insulated cable from the ground. The maximum value of the electric field stress at the grounded plane due to the presence of the insulated three-core cable is detected to check the discharge activities at the grounded plane surface. Comparison is made with field stresses arising from a single-core unshielded insulated cable which are given in the literature. The charge simulation technique is found to be satisfactory to model and calculate accurately the field stresses in a three-core unshielded power cable.
引用
收藏
页码:217 / 221
页数:5
相关论文
共 50 条
  • [41] Research of the Inverse Relationship Between Internal and External Temperatures of 10 kV Three-Core Cable Joints
    Chen, Lisheng
    Niu, Rongze
    Zhou, Hongyang
    IEEE ACCESS, 2024, 12 : 167236 - 167244
  • [42] Temperature Field Calculation of Three Core Cable Joint
    Tang K.
    Ruan J.
    Tang L.
    Zhan Q.
    Liu Y.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (11): : 3571 - 3578
  • [43] A New Multiconductor Cell Three-Dimension Matrix-Based Analysis Applied to a Three-Core Armoured Cable
    Benato, Roberto
    Sessa, Sebastian Dambone
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (04) : 1636 - 1646
  • [44] Frequency-Dependent Pi Model of a Three-Core Submarine Cable for Time and Frequency Domain Analysis
    Ruiz, Carlos
    Abad, Gonzalo
    Zubiaga, Markel
    Madariaga, Danel
    Arza, Joseba
    ENERGIES, 2018, 11 (10)
  • [45] Experimental Validation of Three-Dimension Multiconductor Cell Analysis by a 30 km Submarine Three-Core Armoured Cable
    Benato, Roberto
    Sessa, Sebastian Dambone
    Forzan, Michele
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 2910 - 2919
  • [46] A 3d parametric thermal analysis of submarine three-core power cables
    Del-Pino-lópez J.C.
    Cruz-Romero P.
    Renewable Energy and Power Quality Journal, 2020, 18 : 363 - 368
  • [47] Measurement of transmission line parameters of three-core power cables with common earth screen
    Wagenaars, P.
    Wouters, P. A. A. F.
    van der Wielen, P. C. J. M.
    Steennis, E. F.
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2010, 4 (03) : 146 - 155
  • [48] Research on Calculation and Application of Emergency Hours by the Thermal Circuit Model of 10kV Three-core Cable
    Qian, Hua
    Wang, Peng
    Hu, Ripeng
    Miao, Weisang
    Liu, Gang
    2015 4TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENTAL PROTECTION (ICEEP 2015), 2015, : 1694 - 1699
  • [49] Three-Core Cable Fault Line Identification Based on Ground Wire Current and BiGRU-ResNet-MA
    Ding, Can
    Wang, Fei
    Li, Shengtao
    Jiang, Changhua
    Ma, Pengcheng
    IEEE ACCESS, 2024, 12 : 136120 - 136130
  • [50] Accurate Calculation of Induced Voltages and Currents in Fibre Optic Units Integrated in Three-Core Armoured Cables
    Chaleplidis, Iordanis
    Chatzipetros, Dimitrios
    Chrysochos, Andreas I.
    Bitsi, Konstantina
    Traianos, Christos K.
    2023 30TH INTERNATIONAL CONFERENCE ON MIXED DESIGN OF INTEGRATED CIRCUITS AND SYSTEM, MIXDES, 2023, : 49 - 54