Experimental Study of the Interaction Between Water Sprays and Smoke Layer

被引:7
|
作者
Blanchard, E. [1 ]
Morlon, R. [1 ,2 ,3 ]
Parent, G. [2 ,3 ]
Fromy, P. [1 ]
Boulet, P. [2 ,3 ]
Borgiallo, D. [4 ]
机构
[1] CSTB, 84 Ave Jean Jaures Champs Marne, F-77447 Marne La Vallee 2, France
[2] Univ Lorraine, LEMTA, UMR 7563, F-54500 Vandoeuvre Les Nancy, France
[3] CNRS, LEMTA, UMR 7563, F-54500 Vandoeuvre Les Nancy, France
[4] PROFOG, Parc Activite Moulin Massy,39 Rue Saule Trapu, F-91300 Massy, France
关键词
Smoke; Water spray; Stratification; Destratification; Opacimetry; Transmission; Visibility; SPRINKLER SPRAY; FIRE SUPPRESSION; MODEL; MIST; STRATIFICATION; DISPLACEMENT;
D O I
10.1007/s10694-017-0693-8
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper concerns the interaction between water sprays and a smoke layer in a corridor, without any interaction with fire activity. Three water sprays are tested, a high-pressure water mist system and two sprinkler systems under different operating pressures. Our study aims to compare the impact of these three sprays on the smoke layer, based on the analysis of temperature and transmittance profiles. Characterization of the smoke layer before spray activation, based on either temperature or transmittance was found to be similar, providing a smoke free layer at around middle height in the corridor. During spray operation, discrepancies were observed in some cases depending on whether the smoke layer was studied based on the temperature or the transmittance profiles. Spray operation may provide gas cooling, resulting in homogeneous temperature profiles, while vertical variations of droplet size and soot or droplet concentration can still induce a variation in transmittance. The impact of water spray on the smoke layer varies with the spray system. For the water mist system and the highest-pressure sprinkler system, the spray operation induces a complete de-stratification with well-mixed steady-state conditions along the corridor as well as strong smoke cooling and visibility alteration. With the lowest-pressure sprinkler system, only a localized alteration of this stratification is observed under the spray, while the environment remains thermally and optically stratified downstream in the corridor despite spray operation. Relationships described in the literature were used to confirm and explain these observations. Ratios were evaluated to compare the drag effect due to the spray and the buoyancy effect related to the fire. All tests provided ratios of drag number over buoyancy number much greater than one. This confirms the ability of these relationships to predict the occurrence of de-stratification. Qualitatively, the highest ratios were found for the high pressure system and for the water mist system, which actually led to the most important de-stratification effects. In contrast, the weaker ratio found for the lower pressure system was still above one, i.e., coherent with a de-stratification which did not affect the whole corridor however.
引用
收藏
页码:479 / 501
页数:23
相关论文
共 50 条
  • [21] Experimental study on the extinction of liquid pool fire by water droplet streams and sprays
    Chang, Jy-Cheng
    Lin, Chih-Ming
    Huang, Sheng-Lung
    FIRE SAFETY JOURNAL, 2007, 42 (04) : 295 - 309
  • [22] Experimental study on the interaction between fire and water mist in long and narrow spaces
    Zhang, Peihong
    Tang, Xing
    Tian, Xiangliang
    Liu, Chang
    Zhong, Maohua
    APPLIED THERMAL ENGINEERING, 2016, 94 : 706 - 714
  • [23] Experimental study on the interaction between water and cylindrical structure under earthquake action
    Li, Zhong-Xian
    Wu, Kun
    Shi, Yundong
    Ning, Li
    Yang, Ding
    OCEAN ENGINEERING, 2019, 188
  • [24] Experimental study of dynamic interaction between large thin wall aqueduct and water
    Wang H.
    Li C.
    Zhu C.
    He J.
    Shuili Xuebao/Journal of Hydraulic Engineering, 2020, 51 (06): : 653 - 663
  • [25] An Experimental and Computational Study of Interaction between Water Mist and Gas Jet Flame
    Huang, Xianjia
    Wang, Xishi
    Lu, Jia
    Ding, Zhongjun
    Liao, Guangxuan
    MECHANICAL AND ELECTRONICS ENGINEERING III, PTS 1-5, 2012, 130-134 : 1720 - +
  • [26] Visually activated sprinklers applied in atria to mitigate the interaction of water spray with the smoke layer
    Chiu, Chih Kuo
    Chuah, Yew Khoy
    Shih, Yang-Cheng
    CASE STUDIES IN THERMAL ENGINEERING, 2023, 51
  • [27] Numerical studies on the interaction of sprinkler and smoke layer
    Zhang, Cunfeng
    Chow, Wanki
    9TH ASIA-OCEANIA SYMPOSIUM ON FIRE SCIENCE AND TECHNOLOGY, 2013, 62 : 453 - 462
  • [28] THE INTERACTION OF A SHOCK WAVE WITH A PERMEABLE LAYER: AN EXPERIMENTAL STUDY
    Bulovich, S. V.
    Masiukevich, A. V.
    ST PETERSBURG POLYTECHNIC UNIVERSITY JOURNAL-PHYSICS AND MATHEMATICS, 2019, 12 (04): : 135 - 144
  • [29] Experimental investigation on smoke spread characteristics and smoke layer height in tunnels
    Xu, Zhisheng
    Zhao, Jiaming
    Liu, Qiulin
    Chen, Hongguang
    Liu, Yaohui
    Geng, Zhongyang
    He, Lu
    FIRE AND MATERIALS, 2019, 43 (03) : 303 - 309
  • [30] An experimental study of interaction between pure water and alkaline feldspar at high temperatures and pressures
    Li T.
    Li H.
    Xu L.
    Acta Geochimica, 2018, 37 (01) : 60 - 67