Dynamic performance analysis of inverter-driven split air conditioner

被引:12
|
作者
Elsayed, Amr Owes [1 ]
Kayed, T. S. [2 ]
机构
[1] Imam Abdulrahman Bin Faisal Univ, Coll Engn, Mech & Energy Engn Dept, Dammam 31441, Saudi Arabia
[2] Imam Abdulrahman Bin Faisal Univ, Coll Engn, Basic Engn Sci Dept, Dammam 31441, Saudi Arabia
关键词
Inverter-driven air conditioner; Dynamic characteristics of conditioner; Variable speed compressor and fans; Energy efficiency of air conditioner; STARTUP CHARACTERISTICS; R-410A;
D O I
10.1016/j.ijrefrig.2020.05.014
中图分类号
O414.1 [热力学];
学科分类号
摘要
Variable speed technology has a great potential for improving energy efficiency and performance of vapor compression refrigeration cycle. Therefore, the study of dynamic characteristics of the refrigeration cycle using this new technology becomes essential. This study experimentally investigates the dynamic behavior of a split R-410A air conditioner comprising variable speed compressor, variable speed condenser fan, three speed evaporator fan and electronic expansion valve. The characteristics of the conditioner have been presented during the startup and shutdown periods. Furthermore, the effect of changing evaporator fan speed during the running of the conditioner has been illustrated and discussed. The influence of evaporator and condenser inlet air temperatures on the power consumption and coefficient of performance of the conditioner has also been investigated. The experimental results show that increasing the condenser entering air temperature by 7 degrees C, the power consumption has been increased by 18% and the coefficient of performance decreased by 15%. (c) 2020 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:443 / 452
页数:10
相关论文
共 50 条
  • [1] Modeling and Analysis for Simulation of Common-Mode Noises Produced by an Inverter-Driven Air Conditioner
    Koyama, Yoshitsugu
    Tanaka, Mitsuhiro
    Akagi, Hirofumi
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (05) : 2166 - 2174
  • [2] Experimental Study of the Controlling Characteristics of Inverter-Driven Multi-type Air Conditioner
    金纪峰
    陈江平
    陈芝久
    [J]. Journal of Shanghai Jiaotong University(Science), 2004, (04) : 52 - 56
  • [3] Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves
    Choi, JM
    Kim, YC
    [J]. ENERGY, 2003, 28 (02) : 141 - 155
  • [4] The Power Quality Impact of an Inverter-Driven Air Conditioner under Extremely High Temperature Environments
    Luo, Ling
    Liu, Shu
    Ping, Jian
    Chen, Tiantian
    Pan, Aiqiang
    Jin, Jiapei
    [J]. 2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [5] Performance analysis of an adiabatic compressed air energy storage system with a pressure regulation inverter-driven compressor
    Zhang, Lei
    Liu, Liangxu
    Zhang, Cheng
    He, Xinbing
    Zhang, Yanping
    Yang, Tao
    [J]. JOURNAL OF ENERGY STORAGE, 2021, 43
  • [6] Dynamic meshing for the circuit-field analysis of inverter-driven induction motor
    Guan, H
    Zhao, ZM
    Meng, S
    [J]. ICEMS 2003: PROCEEDINGS OF THE SIXTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1 AND 2, 2003, : 834 - 836
  • [7] Performance evaluation of hydrocarbon and its blend in split packaged inverter operated air conditioner
    Mali, Kundlik V.
    Utage, Ashish S.
    Phadake, Heramb C.
    [J]. MATERIALS TODAY-PROCEEDINGS, 2021, 47 : 5589 - 5593
  • [8] Performance analysis on a multi-type inverter air conditioner
    Park, YC
    Kim, YC
    Min, MK
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2001, 42 (13) : 1607 - 1621
  • [9] Multivariable fuzzy control of residential inverter-driven air conditionings
    Xu Jinqiang1
    2. Guangzhou Institute of Energy Conversion
    [J]. Engineering Sciences, 2010, 8 (02) : 56 - 61
  • [10] ANALYSIS OF AN INVERTER-DRIVEN AIR-CONDITIONING SYSTEM AND ITS APPLICATION IN A HOT AND HUMID AREA