Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil

被引:10
|
作者
Susilo, A. [1 ,2 ,3 ]
Suwarno [2 ]
Khayam, U. [2 ]
Tsuchie, M. [1 ,2 ]
Thein, M. [1 ]
Hikita, M. [1 ]
Saito, T. [4 ]
机构
[1] Kyushu Inst Technol, Dept Elect Engn & Elect, Kitakyushu, Fukuoka 804, Japan
[2] Inst Teknol Bandung, Sch Elect Engn & Informat, Bandung 40132, Indonesia
[3] PT PLN Persero, Jakarta 12160, Indonesia
[4] Kitashiba Elect Co Ltd, Fukushima, Japan
关键词
Dissolved gas analysis (DGA); low temperature overheating; degree of polymerization (DP); CO2/CO ratio;
D O I
10.1016/j.protcy.2013.12.189
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Dissolved gas analysis (DGA) is a powerful tool to diagnose transformer condition. Some internal fault can be depicted with the amount of generated gases or the ratio of some generated gases. This paper will discuss about generated gas tendency for two degradation level of insulating paper under low temperature overheating. Low temperature overheating simulation is conducted in several level of overheating temperature, 75 - 200 degrees C with 25 degrees C interval. New insulating paper (DP1040) has different behavior than bad degraded insulating paper (DP390) regarding to CO2 generation but has similar behavior regarding to CO generation as function of temperature. At low temperature overheating, degradation speed of new insulating paper is faster than bad degraded insulating paper. (C) 2013 The Authors. Published by Elsevier Ltd. Selection and peer-review under responsibility of the Faculty of Information Science & Technology, Universiti Kebangsaan Malaysia.
引用
收藏
页码:257 / 262
页数:6
相关论文
共 50 条
  • [31] Estimation of Dissolved Gas Concentrations in Transformer Oil From Membranes
    Li, Yangliu
    Zhao, Xuezeng
    IEEE ELECTRICAL INSULATION MAGAZINE, 2011, 27 (02) : 30 - 33
  • [32] GAS-CHROMATOGRAPHIC ANALYSIS OF DISSOLVED GASES IN TRANSFORMER OIL
    WATANABE, C
    YANAGISAWA, N
    KUBO, Y
    BUNSEKI KAGAKU, 1975, 24 (12) : 737 - 741
  • [33] APPARATUS FOR CONTINUOUSLY MONITORING HYDROGEN GAS DISSOLVED IN TRANSFORMER OIL
    TSUKIOKA, H
    SUGAWARA, K
    MORI, E
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1981, 16 (06): : 502 - 509
  • [34] GAS EVOLUTION FROM TRANSFORMER INSULATING MATERIALS DUE TO AGING DETERIORATION
    ISHII, T
    NAMBA, S
    ELECTRICAL ENGINEERING IN JAPAN, 1970, 90 (03) : 53 - &
  • [35] Investigation on the Effect of Benzotriazole Passivator on the Characteristics of Dissolved Gas in the Insulating Oil
    Gao S.
    Li W.
    Ke T.
    He Y.
    Li J.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (08): : 2715 - 2724
  • [36] DETERMINATION OF GAS DISSOLVED IN ELECTRICAL INSULATING OIL BY HEAD SPACE AND GAS-CHROMATOGRAPHY
    POY, F
    COBELLI, L
    BANFI, S
    FRESENIUS ZEITSCHRIFT FUR ANALYTISCHE CHEMIE, 1989, 334 (07): : 704 - 705
  • [37] Using the Analysis of the Gases Dissolved in Oil in Diagnosis of Transformer Bushings with Paper-Oil Insulation-A Case Study
    Piotrowski, Tomasz
    Rozga, Pawel
    Kozak, Ryszard
    Szymanski, Zbigniew
    ENERGIES, 2020, 13 (24)
  • [38] A review of optical gas sensing technology for dissolved gas analysis in transformer oil
    Dai, Jialiang
    Luo, Bing
    Shen, Xiaowen
    Han, Wenfei
    Cui, Ruyue
    Wu, Jintao
    Zhang, Haofeng
    Xiao, Wei
    Zhong, Zheng
    Dong, Lei
    Wu, Hongpeng
    FRONTIERS IN PHYSICS, 2025, 13
  • [39] A Pragmatic Approach to Diagnose on Transformer's Insulating Oil with Gas Pattern
    Lin, Ming-Jong
    Yu, Chao-Tang
    2014 INTERNATIONAL SYMPOSIUM ON COMPUTER, CONSUMER AND CONTROL (IS3C 2014), 2014, : 1002 - 1005
  • [40] Anomalies in Interpretation of Transformer Oil Tests For Thermally Upgraded Paper - A Case History
    Merritt, Stanley Y.
    CONFERENCE RECORD OF 2015 61ST IEEE ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE (PPIC), 2015, : 91 - 97