Steady-state Analysis of Voltage Source Converter (VSC) Connected to Weak AC System and Optimal Control Strategies

被引:2
|
作者
Yuan, Bin [1 ]
Xu, Jianzhong [1 ]
Zhao, Chengyong [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, 88 Mail Box, Beijing, Peoples R China
关键词
voltage source converter (VSC); weak AC system; steady-state characteristic; small signal stability; phase-locked loop (PLL); POWER-SYNCHRONIZATION CONTROL; STABILITY ANALYSIS; IMPEDANCE; LINKS; GRIDS;
D O I
10.1080/15325008.2018.1449917
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The power transfer limitation of voltage source converter (VSC) connected to weak AC system is restricted by three main elements: steady-state characteristic, small signal stability, and transient stability. In this paper, according to steady-state analysis, constraint condition and mathematical model of VSC system are established to figure out the appropriate operating point. A novel outer-loop control diagram is proposed. Meanwhile, a small signal model of VSC system is established. Based on participation factor analysis, the dynamic performance of phase-locked loop (PLL) have significant impacts on the system stability assessment. Therefore, an advanced PLL control appending damping factor is proposed. Simulations validated the following conclusions: 1) The optimal AC voltage of point of common coupling is associated with the equivalent AC system voltage, impedance, and the current limitation. The novel outer-loop controller can enhance the power transfer limitations. 2) The small signal stability of VSC can be enhanced by appending an alternative damping factor control on PLL. The advanced PLL has robustness which can endure a great active power disturbance in AC system. Simulations and calculations have been performed to validate the findings.
引用
收藏
页码:445 / 455
页数:11
相关论文
共 50 条
  • [31] Optimal Control Strategy of Back-to-Back Converter Based on AC/DC Voltage Source Converter
    Wu, Haotian
    Wei, Zhong
    Liu, Shiwen
    MOBILE INFORMATION SYSTEMS, 2022, 2022
  • [32] Time-Domain Steady-State Method of a Closed-loop Voltage Source Converter
    Lian, K. L.
    2014 IEEE PES GENERAL MEETING - CONFERENCE & EXPOSITION, 2014,
  • [33] Voltage Source Converter Modeling for Power System State Estimation: STATCOM and VSC-HVDC
    Jaen, Antonio de la Villa
    Acha, Enrique
    Gomez-Exposito, Antonio
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (04) : 1552 - 1559
  • [34] Topology Improvement of the Current Source Modular Multilevel Converter: Steady-State Analysis
    Alskran, Faleh A.
    Simoes, M. Godoy
    2018 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING (IAS), 2018,
  • [35] Steady-state analysis of a series resonant converter with modified PWM control
    Luan, Bo-Yue
    Hu, Song
    Zhang, Yi-Fan
    Li, Xiaodong
    PROCEEDINGS OF THE 2017 12TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2017, : 1143 - 1148
  • [36] Zero Steady-State Error PWM Control System for Sinusoidal Voltage
    Stanciu, Dumitru
    Teodorescu, Mihail
    2015 9TH INTERNATIONAL SYMPOSIUM ON ADVANCED TOPICS IN ELECTRICAL ENGINEERING (ATEE), 2015, : 656 - 661
  • [37] A comprehensive modeling framework for dynamic and steady-state analysis of voltage droop control strategies in HVDC grids
    Beerten, J.
    Belmans, R.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 73 : 691 - 701
  • [38] Description and Comparison of DC Voltage Control Strategies for Offshore MTDC Networks: Steady-State and Fault Analysis
    Pinto, R. Teixeira
    Rodrigues, S. F.
    Bauer, P.
    Pierik, J.
    EPE JOURNAL, 2012, 22 (04) : 31 - 39
  • [39] An Improved Phase-Locked-Loop Control with Alternative Damping Factors for VSC Connected to Weak AC System
    Yuan, Bin
    Xu, Jianzhong
    Zhao, Chengyong
    Yuan, Yijia
    JOURNAL OF CONTROL SCIENCE AND ENGINEERING, 2016, 2016
  • [40] Steady-state solution of the HVDC converter including AC/DC system interaction by a direct method
    Perkins, BK
    IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (04) : 1454 - 1460