Study of Sub-Synchronous Control Interaction due to the Interconnection of Wind Farms to a Series Compensated Transmission System

被引:0
|
作者
Nath, Ram
Grande-Moran, Carlos
机构
关键词
Sub-synchronous control interaction; Type 3 wind turbine generator; Type 4 wind turbine generator; impedance scan; time-domain simulation;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An instance of severe damage to wind turbines due to Sub-Synchronous Control Interaction (SSCI) has been observed in the case of an interconnection of a wind farm to a series compensated transmission system. This paper presents the methodology to be followed to perform a SSCI study. The frequency-domain impedance scanning and the time-domain simulation approach are used to identify and verify the SSCI. It is necessary to perform transient simulations utilizing a detailed model of the Wind Turbine Generator (WTG). Typical fault types and disturbances that could trigger an unstable SSCI response of the WTG are simulated. The studies are performed on the IEEE Second Benchmark Model. The study compares the time-domain response of a wind farm comprised of Type 3 Doubly Fed Induction Generator (DFIG) WTGs with that of a wind farm comprised of Type 4 (Full converter) WTGs as far as SSCI is considered.
引用
收藏
页数:6
相关论文
共 50 条
  • [41] Robust H-infinity and μ-synthesis controllers to mitigate sub-synchronous control interaction in DFIG wind farms considering time delay
    Bodapatla, Sampath Kumar
    Gaddam, Mallesham
    Sarma, P. Mallikarjuna
    [J]. ELECTRICAL ENGINEERING, 2024,
  • [42] Sub-Synchronous Resonance Damping Control for Series-Compensated DFIG-Based Wind Farm With Improved Particle Swarm Optimization Algorithm
    Yao, Jun
    Wang, Xuewei
    Li, Jiawei
    Liu, Ruikuo
    Zhang, Hailin
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2019, 34 (02) : 849 - 859
  • [43] Evaluation of the Sub-Synchronous Control Interaction Based on the Elastic Energy Equivalent System
    Liu, Chengxi
    Han, Jiangbei
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2023, 38 (04) : 3897 - 3910
  • [44] Sub-synchronous resonance mitigation by a STATCOM in doubly fed induction generator-based wind farm connected to a series-compensated transmission network
    Gao, Benfeng
    Hu, Yunting
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 812 - 815
  • [45] Proposed sub-synchronous resonance damping controller for large-scale wind farms
    Moradi-Shahrbabak, Zahra
    [J]. IET RENEWABLE POWER GENERATION, 2023, 17 (13) : 3209 - 3220
  • [46] General Methodology for Analysis of Sub-Synchronous Interaction in Wind Power Plants
    Badrzadeh, Babak
    Sahni, Mandhir
    Zhou, Yi
    Muthumuni, Dharshana
    Gole, Ani
    [J]. 2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [47] A review of recent studies on the mechanisms and analysis methods of sub-synchronous oscillation in wind farms
    Wang, Chenggen
    Zhou, Qian
    Gao, Shuning
    Luo, Jia
    Diao, Junchao
    Zhao, Haoran
    Bu, Jing
    [J]. 2018 ASIA CONFERENCE ON ENERGY AND ENVIRONMENT ENGINEERING (ACEEE 18), 2018, 133
  • [48] A Simplified Model of the HVDC Transmission System for Sub-Synchronous Oscillations
    Wang, Yanwen
    Wu, Lingjie
    Chen, Shaoyang
    [J]. SUSTAINABILITY, 2023, 15 (09)
  • [49] Equivalent Modeling of Dfig-Based Wind Farms for Sub-Synchronous Resonance Analysis
    Yan, Gangui
    Wang, Dan
    Jia, Qi
    Hu, Wenbo
    [J]. ENERGIES, 2020, 13 (20)
  • [50] Effect of Control Parameters on Infliction of Sub-synchronous Control Interaction in DFIGs
    Ali, Muhammad Taha
    Ghandhari, Mehrdad
    Harnefors, Lennart
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON POWER AND RENEWABLE ENERGY (ICPRE), 2016, : 72 - 78