The Relationship between Partial Discharge Behavior and the Degradation of 10 kV XLPE Cable Joints

被引:0
|
作者
Hui, Baojun [1 ]
Liu, Chang [2 ]
Tian, Ye [1 ]
Fu, Mingli [1 ]
Xu, Yang [3 ]
Zhang, Yuhang [3 ]
机构
[1] China Southern Power Grid Co Ltd, CSG, Elect Power Res Inst, Guangzhou, Guangdong, Peoples R China
[2] China Southern Power Grid Co Ltd, CSG, Guangzhou, Guangdong, Peoples R China
[3] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power, Xian, Peoples R China
关键词
cable joint; partial discharge; condition assessment;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The failure rate of XLPE (Cross-linked polyethylene) cable joints is higher than that of cable in distribution systems due to bad environmental conditions, improper installation, and aging. To evaluate the failure and degradation of a cable joint via partial discharge (PD) detection, a 10kV XLPE cable joint was selected as the experimental sample, which was found partial discharge by field testing under damped AC voltage. An accelerated degradation experimental platform was set up for the 10 kV cable joint to simulate the cable operating conditions in the laboratory, and the PD behavior was monitored using a high frequency current transformer under different voltages and currents. The results indicate that the PD behavior is clearly affected by the voltage, current and aging time for the air-gap defect inside the joint. The degradation of the XLPE cable joint can be well characterized by the PD trend. Based on these results, a parameter is proposed for joints condition evaluation, which is the ratio of the PD magnitude between an interval time and named as a significant growth factor.
引用
收藏
页码:843 / 846
页数:4
相关论文
共 50 条
  • [1] Partial discharge characteristics of 10 kV XLPE cable joints under oscillating voltage
    State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
    400030, China
    不详
    510410, China
    [J]. Gaodianya Jishu, 4 (1068-1074):
  • [2] The Partial Discharge Evolution Characteristics of 10kV XLPE Cable Joint
    Tian, Fuqiang
    Li, Xubin
    Zhang, Shuting
    Cao, Jinmei
    [J]. IEEE ACCESS, 2023, 11 (108680-108687) : 108680 - 108687
  • [3] Study on Ultrasonic Propagation Characteristics of Partial Discharge in 10 kV XLPE Cable
    Zhao, Xiaohe
    Wan, Liujie
    Yang, Jie
    Li, Shiqiang
    Shang, Wenxiang
    [J]. Progress In Electromagnetics Research C, 2023, 137 : 223 - 233
  • [4] Dielectric Loss and Partial Discharge Test Analysis of 10 kV XLPE Cable
    Yuan, Ye
    Lu, Guojun
    Wang, Wei
    Fan, Weinan
    Liao, Weiyan
    Jia, Zhidong
    Guan, Zhicheng
    [J]. 2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 124 - 127
  • [5] Study of 10 kv Joints for XLPE Cable.
    Vlugt, D.N.
    Zandee, P.
    [J]. Elektrotechniek, 1984, 63 (04): : 371 - 373
  • [6] A Capacitive Strip Sensor for Detecting Partial Discharge in 110-kV XLPE Cable Joints
    Jiang, Jun
    Ge, Zhendong
    Zhao, Mingxin
    Yu, Miao
    Chen, Xuewei
    Chen, Min
    Li, Jiansheng
    [J]. IEEE SENSORS JOURNAL, 2018, 18 (17) : 7122 - 7129
  • [7] Analysis on the Propagation Characteristics of Partial Discharge in XLPE Cable Joints
    Yang, Chenbo
    Huang, Feng
    Guo, Jinming
    Huang, Chenxi
    Hei, Weisheng
    Li, Hongji
    [J]. INTERNATIONAL CONFERENCE ON ELECTRICAL AND CONTROL ENGINEERING (ICECE 2015), 2015, : 194 - 198
  • [8] A sensitive method for on-site partial discharge detection on XLPE cable joints
    Schichler, U
    [J]. PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 1997, : 1099 - 1102
  • [9] Influence of contaminants on partial discharge characteristics for model XLPE transmission cable joints
    Nadolny, Z
    Braun, JM
    Densley, RJ
    [J]. CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 140 - 143
  • [10] Comparison of on-line partial discharge detection methods for XLPE cable joints
    Williams, GM
    Lewin, PL
    Davies, AE
    Sutton, SJ
    Swingler, SG
    [J]. QRM 2002: PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON QUALITY, RELIABILITY, AND MAINTENANCE, 2002, : 319 - 322