The Partial Discharge Evolution Characteristics of 10kV XLPE Cable Joint

被引:1
|
作者
Tian, Fuqiang [1 ]
Li, Xubin [1 ]
Zhang, Shuting [1 ]
Cao, Jinmei [1 ]
机构
[1] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
来源
IEEE ACCESS | 2023年 / 11卷
关键词
XLPE cable; partial discharge; accelerated electrical aging; BP neural network; state prediction; ELECTRICAL TREE; GROWTH;
D O I
10.1109/ACCESS.2023.3321805
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The evolution of partial discharge (PD) with time can provide a deep understanding on the insulation status of power cables. It is of great significance for intelligent operation and maintenance of power cables. In this paper, the PD pulse signal in the 10kV cable joint during accelerated electrical aging under 20kV AC voltage was acquired in the real-time for about 160h. The characteristic parameters of partial discharge-pulse number, average voltage, maximum voltage and energy per second were extracted. The results show that the phase of partial discharge is mainly concentrated at 30(degrees)-90(degrees) and 200(degrees)-270(degrees), which can be characterized as internal discharge. PD characteristic parameters gradually increased after 50h. The pulse number, energy per second and the average voltage of PD pulse reached a peak between 60-80h. Then these parameters reached a steady state between 80-130h and showed a steep rise after 130h. The maximum voltage of PD pulse shows a steep rise at about 70h from 0.1V to 0.3V. It rises sharply from 0.3V to 0.5V after about 120h and then enters a relatively stable oscillation stage. The evolution rules of the PD characteristic parameters comply well with the electrical tree growth states-initiation period, lag period and rapid growth period. Furthermore, model for predicting and evaluating the insulation state based on BP neural network are established and the prediction accuracy is verified. The proposed models can provide early warning for the cable joint before the insulation failure, so as to ensure timely maintenance or replacement.
引用
收藏
页码:108680 / 108687
页数:8
相关论文
共 50 条
  • [1] Research on Partial Discharge Mechanism and Characteristics for 10kV Cable Joint With Air Gap Defect
    Zhu, Zhengguo
    Huang, Chao
    Yu, Ying
    Zhang, Ming
    Qin, Yanjia
    [J]. 2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [2] Simulation and partial discharge detection for typical defects of 10kV cable the joint
    Xia, Yunfeng
    Song, Xinming
    He, Jianzong
    Jia, Zhidong
    Wang, Xilin
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2856 - 2859
  • [3] Study on the time evolution of partial discharge characteristics and interfacial phenomena of simulated XLPE cable joint
    Yoshida, H
    Tian, ZH
    Hikita, M
    Miyata, H
    [J]. 1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 501 - 504
  • [4] Dielectric Loss and Partial Discharge Test Analysis of 10 kV XLPE Cable
    Yuan, Ye
    Lu, Guojun
    Wang, Wei
    Fan, Weinan
    Liao, Weiyan
    Jia, Zhidong
    Guan, Zhicheng
    [J]. 2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 124 - 127
  • [5] Partial Discharge Characteristics of XLPE Cable Joint and Interfacial Phenomena with Artificial Defects
    Arief, Yanuar Z.
    Ahmad, Hussein
    Hikita, Masayuki
    [J]. 2008 IEEE 2ND INTERNATIONAL POWER AND ENERGY CONFERENCE: PECON, VOLS 1-3, 2008, : 1518 - +
  • [6] Simulation and Analysis of Propagation Characteristics of Partial Discharge signal in XLPE Cable Joint
    Wang Qian
    Yang Qi
    Hu Xiaorui
    Fu Jin
    Chen Wei
    Yang Fan
    [J]. PROCEEDINGS OF THE 2016 IEEE 11TH CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2016, : 2232 - 2235
  • [7] The Relationship between Partial Discharge Behavior and the Degradation of 10 kV XLPE Cable Joints
    Hui, Baojun
    Liu, Chang
    Tian, Ye
    Fu, Mingli
    Xu, Yang
    Zhang, Yuhang
    [J]. 2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 843 - 846
  • [8] Study on Partial Discharge Pulse Attenuation Characteristics in 110 kV XLPE Power Cable
    Gu, Xiao
    Liu, Bin
    Xu, Yang
    Yang, Dan
    [J]. 2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 788 - 791
  • [9] A Novel 10kV XLPE Cable Failure Prediction Method
    Mao Jun
    Tang HuiDong
    [J]. MACHINERY, MATERIALS SCIENCE AND ENERGY ENGINEERING, 2015, : 58 - 64
  • [10] Study on Diagnostic Method of Aging 10kV XLPE Cable
    Fan Weinan
    Huang Yanguang
    Zhang Yaru
    Xiong Jun
    Wang Yong
    You Jiao
    Zhu Bin
    Jia Zhidong
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,