Performance analysis of a CO2/NH3 cascade refrigeration system with subcooling for low temperature freezing applications

被引:4
|
作者
Vaishak, S. [1 ]
Singha, Prosenjit [1 ]
Dasgupta, Mani Sankar [1 ]
Hafner, Armin [2 ]
Widell, Kristina [3 ]
Bhattacharyya, Souvik [1 ]
Saini, Santosh Kumar [1 ]
Arun, B. S. [4 ]
Samuel, Manoj P. [4 ]
Ninan, George [4 ]
机构
[1] Birla Inst Technol & Sci Pilani, Pilani 333031, India
[2] Norwegian Univ Sci & Technol, N-7034 Trondheim, Norway
[3] SINTEF Ocean AS, N-7465 Trondheim, Norway
[4] ICAR Cent Inst Fisheries Technol, Cochin 682029, India
关键词
cascade refrigeration system; subcooling; carbon dioxide; ammonia; total equivalent warming impact; natural refrigerants; CO2; DESIGN;
D O I
10.1016/j.ijrefrig.2023.05.013
中图分类号
O414.1 [热力学];
学科分类号
摘要
CO2/NH3 cascade refrigeration system is an all-natural refrigeration option which can be specifically designed and gainfully operated for low temperature applications in warm ambient conditions. In the present study, a novel CO2/NH3 cascade refrigeration system with subcooling is proposed and evaluated as an alternative to the HFC-404A refrigeration system, which is typically used for blast freezer applications in the seafood processing industry. The performance of the proposed system is also compared with a conventional CO2/NH3 cascade refrigeration system without any subcooling arrangement. Real compressor specific equations were used to simulate the performance of the systems under various conditions. The proposed system yields 26% higher performance ratio (COP) than the conventional HFC-404A system at the design condition. In addition, the proposed subcooling arrangement enhances COP of the conventional CO2/NH3 cascade unit by around 5%. The system performance is investigated theoretically under various condensing temperatures and subcooling degrees. The annual energy demand and total equivalent warming impact (TEWI) of the proposed system are 15% and 48% lower than for the conventional HFC-404A system which results in significant economic and environmental benefits. Overall, the proposed system exhibits superior energy efficiency and offers a climate and environmental friendly alternative to the conventional environmentally harmful systems within the seafood industry. Adoption of such energy efficient all natural and clean refrigerant technology is crucial for the future phase out of hydrofluorocarbon (HFC) fluids, as ratified in accordance with the Kigali Amendment to the Montreal Protocol in India and other tropical countries.
引用
收藏
页码:140 / 154
页数:15
相关论文
共 50 条
  • [41] Thermodynamic analysis of a CO2 refrigeration cycle with integrated mechanical subcooling
    Nebot-Andrés L.
    Calleja-Anta D.
    Sánchez D.
    Cabello R.
    Llopis R.
    Energies, 2019, 13 (01)
  • [42] Comparative thermodynamic performance analysis of a cascade refrigeration system with new refrigerants paired with CO2
    Adebayo, Victor
    Abid, Muhammad
    Adedeji, Michael
    Dagbasi, Mustafa
    Bamisile, Olusola
    APPLIED THERMAL ENGINEERING, 2021, 184
  • [43] Performance analysis of two-stage compression transcritical CO2 refrigeration system with 8290 mechanical subcooling unit
    Liu, Shengchun
    Lu, Fenping
    Dai, Baomin
    Nian, Victor
    Li, Hailong
    Qi, Haifeng
    Li, Jiayu
    ENERGY, 2019, 189
  • [44] CO2 /NH3 systems
    Pearson, SF
    ASHRAE JOURNAL, 2002, 44 (12) : 11 - 11
  • [45] Exergoeconomic and environmental analyses of CO2/NH3 cascade refrigeration systems equipped with different types of flash tank intercoolers
    Mosaffa, A. H.
    Farshi, L. Garousi
    Ferreira, C. A. Infante
    Rosen, M. A.
    ENERGY CONVERSION AND MANAGEMENT, 2016, 117 : 442 - 453
  • [46] Performance evaluation of CO2 supermarket refrigeration system with multi-ejector and dedicated mechanical subcooling
    Liu, Xi
    Yu, Kaihong
    Wan, Xinchen
    Li, Xuelai
    ENERGY REPORTS, 2021, 7 : 5214 - 5227
  • [47] Theoretical analysis of the interaction of Co, Co2, and Nh3, with ZnO
    Martins, JBL
    Sambrano, JR
    Vasconcellos, LAS
    Longo, E
    Taft, CA
    QUIMICA NOVA, 2004, 27 (01): : 10 - 16
  • [48] Exergy, carbon footprint and cost lifecycle evaluation of cascade mechanical subcooling CO2 commercial refrigeration system in China
    Dai, Baomin
    Cao, Yu
    Zhou, Xuan
    Liu, Shengchun
    Fu, Rao
    Li, Cenxi
    Wang, Dabiao
    JOURNAL OF CLEANER PRODUCTION, 2024, 434
  • [49] Role of ejector expander in optimal inherently safety design of cascade NH3/Propane/CO2 vapor compression refrigeration systems
    Rostamzadeh, Hadi
    Gholizadeh, Towhid
    Rostamzadeh, Sajjad
    Vosoughi, Shahram
    Farshad, Ali Asghar
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2021, 146 : 745 - 762
  • [50] Exploration of NH3 and NH3/DME laminar flame propagation in O2/CO2 atmosphere: Insights into NH3/CO2 interactions
    Shi, Xiaoxiang
    Li, Wei
    Zhang, Jianguo
    Fang, Qilong
    Zhang, Yi
    Xi, Zhongya
    Li, Yuyang
    COMBUSTION AND FLAME, 2024, 260