automatic generation control(AGC); deregulation; genetic algorithm (GA); optimal AGC regulators (OARs); redox flow batteries (RFB); thyristor controlled phase shifter (TCPS); AUTOMATIC-GENERATION CONTROL; LOAD FREQUENCY CONTROL; REDOX FLOW BATTERIES; AC/DC PARALLEL LINKS; PID CONTROLLER; OPTIMIZATION; SIMULATION; ALGORITHM; IMPACT; SERIES;
D O I
10.1002/oca.3106
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In today's electric power network, fast changes are the norm, and auxiliary services such as automatic generation control (AGC) play a crucial role in maintaining the quality of the power supply. AGC ensures a balance between power generation, demand, and losses to sustain frequency stability and variation in tie-line power within a set limit, even when the load changes. To accomplish this, it is always beneficial to consider new approaches to controlling the situation. This paper introduces the design of new AGC regulators that consider deviation in DC tie-line power as an extra control variable for the turbine controller. In this study, three different deregulated power systems (containing two control areas), namely three thermal generations, the combination of one thermal and two hydro generations, and three hydro generations, including two power distribution companies (DISCOs) in each control area. These optimal AGC regulators are implemented in the proposed thermal-thermal-thermal system to carry out the various power contracts. The results have shown that the dynamic outcomes meet the AGC standards. To improve further dynamic results and the proposed systems' stability margins by incorporating redox flow batteries (RFB). In actual operating conditions, the system parameters do not remain constant due to the aging effect, assumptions made in simplifying the mathematical model, etc. Thus, +/- 50% deviations in the nominal value of system parameters to assess how well the optimal AGC regulators perform in the system under investigation. The suggested realistic AGC system incorporates many parameter fluctuations and works well with the optimal AGC regulators developed for the proposed plans. This study expanded to include a two-area, thermal-hydro-hydro (THH) system under a deregulated framework connected via an asynchronous transmission link with or without a thyristor-controlled phase shifter (TCPS) and RFB. The genetic algorithm (GA) can solve many issues and has global search, flexibility to varied problem types, intrinsic parallelism, and the ability to handle massive, complex search spaces. Thus, a two-area deregulated hydro-hydro-hydro system with parallel tie-lines utilizes GA-PID, GA-FOPID, and GA-(1 + PI)-FOPID controllers. Moreover, a random load disturbance (RLD) is employed in each section of the offered approach to show the resilience and elite performance of the proposed control strategy. To produce various dynamic reactions in the plans, MATLAB software version R2013a is employed.
引用
收藏
页码:1456 / 1502
页数:47
相关论文
共 50 条
  • [31] Constrained discrete mode control of supercapacitor energy storage system for improved AGC of a multi-area power system with effects of wind power
    Nisa S.U.
    Mufti M.U.-D.
    International Journal of Power Electronics, 2021, 14 (03) : 386 - 403
  • [32] Design and analysis of BFOA-optimized fuzzy PI/PID controller for AGC of multi-area traditional/restructured electrical power systems
    Yogendra Arya
    Narendra Kumar
    Soft Computing, 2017, 21 : 6435 - 6452
  • [33] Design and analysis of BFOA-optimized fuzzy PI/PID controller for AGC of multi-area traditional/restructured electrical power systems
    Arya, Yogendra
    Kumar, Narendra
    SOFT COMPUTING, 2017, 21 (21) : 6435 - 6452
  • [34] Multi-area unit commitment for large-scale power systems
    Tseng, CL
    Guan, X
    Svoboda, AJ
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1998, 145 (04) : 415 - 421
  • [35] Hybrid-Peak-Area-Based Performance Index Criteria for AGC of Multi-Area Power Systems
    Pathak, Nikhil
    Hu, Zechun
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2019, 15 (11) : 5792 - 5802
  • [36] Optimal and Suboptimal Linear Regulator Design of AGC for Two Area Interconnected Power System
    Ghadimi, Esmail
    Mandavi, Sina
    2017 IEEE 4TH INTERNATIONAL CONFERENCE ON KNOWLEDGE-BASED ENGINEERING AND INNOVATION (KBEI), 2017, : 243 - 251
  • [37] DECENTRALIZED OPTIMAL-CONTROL OF MULTI-AREA POWER-SYSTEMS
    ELMETWALLY, MM
    RAO, ND
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (03): : 761 - 761
  • [38] Assessment of the Capacity Credit of Renewables and Storage in Multi-Area Power Systems
    Liu, Guanchi
    Vrakopoulou, Maria
    Mancarella, Pierluigi
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2021, 36 (03) : 2334 - 2344
  • [39] A hierarchical multi-area capacity planning model considering configuration ratios of renewable energy and energy storage systems with multi-area coordination
    Li, Qingtao
    Wang, Jianxue
    Chen, Jie
    Ding, Tao
    Gu, Chenjia
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (16) : 3658 - 3677
  • [40] Multi-area Scheduling Model and Strategy for Power Systems with Large-scale New Energy and Energy Storage
    Yuan, Wei
    Wang, Caixia
    Lei, Xuejiao
    Li, Qionghui
    Shi, Zhiyong
    Yu, Ye
    2018 CHINESE AUTOMATION CONGRESS (CAC), 2018, : 2419 - 2424