Experimental study on the heat flux profile upon the building facade of the window-ejected fire plume

被引:2
|
作者
Sun, Xiepeng [1 ]
Hu, Longhua [1 ]
Lv, Jiang [1 ]
Fang, Xiang [1 ]
Chen, Xiaotao [1 ]
Zhang, Xiaolei [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei, Anhui, Peoples R China
基金
中国国家自然科学基金;
关键词
Window-ejected fire plume; Fuel released inside the compartment; Transverse heat flux upon the building; facade; Gaussian profile model; Facade flame height; FLAME HEIGHT; SPILL PLUME; TEMPERATURE PROFILE; EXTERNAL FLAMES; COMPARTMENT; WALL; CONSTRAINT; ENTRAINMENT; TRANSITION; PRESSURE;
D O I
10.1016/j.ijheatmasstransfer.2023.124391
中图分类号
O414.1 [热力学];
学科分类号
摘要
The window-ejected fire plume with the excess fuel released outside the opening poses great threat to the building facade due to the hazardous heat flux. This paper investigates experimentally the temper-ature inside the compartment, convective-and excess-heat release rate, facade flame height and the heat flux profile upon the building facade of the under-ventilated window-ejected fire plume. A set of experiments are carried out with a compartment-facade model consisting of a 0.40 m reduced cubic compartment and a vertical facade. An opening with various sizes is set at the center of the sidewall of the compartment. The temperature inside the compartment, convective-and excess-heat release rate, facade flame height and the heat flux profile upon the building facade are measured and quantified by thermocouples, camera and heat flux gauge array upon the building facade of the under-ventilated window-ejected fire plume for various openings and heat release rates. The center line heat flux could be correlated well with the non-dimensional height normalized by the flame height involving the correc-tion factor. A global model on the heat flux profile upon the building facade incorporating the aspect ratio of the opening, flame height and the convective heat release rate, is developed to describe the transverse heat flux evolution in a general dimensionless form, and the proposed model correlates the experimen-tal data well. The obtained experimental data and proposed model provide a basic understanding of the heat/thermal impact on the facade of the window-ejected fire plume due to excess fuel diffusion com-bustion. & COPY; 2023 Elsevier Ltd. All rights reserved.
引用
收藏
页数:18
相关论文
共 46 条
  • [31] Experimental study on flame height and temperature profile of buoyant window spill plume from an under-ventilated compartment fire
    Tang, F.
    Hu, L. H.
    Delichatsios, M. A.
    Lu, K. H.
    Zhu, W.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2012, 55 (1-3) : 93 - 101
  • [32] An experimental study of temperature and heat flux in a channel with an asymmetric thermal plume
    Fan, Chuan Gang
    Zhang, Jia-Qing
    Zhu, Kong Jin
    Li, Kai Yuan
    APPLIED THERMAL ENGINEERING, 2017, 113 : 1128 - 1136
  • [33] Experimental study on the vertical temperature distribution of window ejected fire from an enclosure with adjacent side walls
    Xu, Tong
    He, Qing
    Tang, Fei
    Lei, Peng
    Pang, Huanping
    FIRE AND MATERIALS, 2020, 44 (01) : 152 - 162
  • [34] Experimental Study on Heat Transfer Characteristics of Hollowing Defect Areas on Building Facade
    Gong, Xue
    Zhu, Darong
    Li, Jianguo
    Liu, Yanli
    Wang, Ping
    BUILDINGS, 2024, 14 (08)
  • [35] A computational study on structural barrier to vertical spread of window spill plume along building exterior facade under external wind
    Zhao, Nan
    PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON INFORMATION, ELECTRONICS AND COMPUTER, 2014, 59 : 82 - 86
  • [36] A computational study on structural barrier to vertical spread of window spill plume along building exterior facade under external wind
    Zhao Nan
    Zhang Jing-yan
    Xing Xue-fei
    ADVANCES IN CIVIL AND STRUCTURAL ENGINEERING III, PTS 1-4, 2014, 501-504 : 2392 - +
  • [37] A numerical study of the effect of window configuration on the external heat and smoke spread in building fire
    Chen, DH
    Lo, SM
    Lu, WZ
    Yuen, KK
    Fang, Z
    NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2001, 40 (08) : 821 - 839
  • [38] Contribution to the study by numerical simulation of a fire plume coming out through a window on facade "Application to the comprehension of the wind influence on an eventually stack effect"
    Martinez, Bernardo R.
    1ST INTERNATIONAL SEMINAR FOR FIRE SAFETY OF FACADES, 2013, 9
  • [39] Experimental study on vertical temperature profile of buoyant window spill plume from intermediate-scale compartments
    Zhou, Biao
    Yoshioka, Hideki
    Noguchi, Takafumi
    Ando, Tatsuo
    FIRE AND MATERIALS, 2020, 44 (04) : 516 - 529
  • [40] A Study on the Heating Behavior of Soffit Member Exposed to Fire Plume Ejected from an Opening -Temperature and Incident Heat Flux Under the Soffit Member with H-Beam Steel Placed at the Tip-
    Kang S.
    Ohmiya Y.
    Kimura K.
    Bulletin of Japan Association for Fire Science and Engineering, 2020, 70 (03): : 83 - 94