Experimental studies on natural bank type heating/cooling energy saving Air conditioning system

被引:1
|
作者
Goyal, Vaishali [1 ]
Asati, Arun Kumar [1 ]
Garg, Rajeev Kumar [2 ]
Arora, Amit [2 ]
机构
[1] Shaheed Bhagat Singh State Univ, Dept Mech Engn, Ferozepur, Punjab, India
[2] Shaheed Bhagat Singh State Univ, Dept Chem Engn, Ferozepur, Punjab, India
关键词
Earth air heat exchanger; full factorial design; factor interactions; effectiveness; temperature difference; dry bulb temperature; wet bulb temperature; earth's undisturbed temperature; EARTH-TO-AIR; HEAT-EXCHANGER; PERFORMANCE; VENTILATION; SIMULATION; BUILDINGS; SUMMER; HOT;
D O I
10.1177/09544089221096052
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The present study reports air-based novel energy saving compact bank type earth air heat exchanger system (EAHE) (having only 25m(2) area) fabricated from Polyvinylchloride pipes of nominal diameter 0.203 mm (8 inches) for inlet and outlet headers and main pipes and 0.150 mm (6 inches nominal diameter) for branched pipes, which is installed in Shaheed Bhagat Singh State University, Ferozepur in Punjab state, India (North West border area of India) and studied for the duration from April to August 2021 using the full factorial design with four inlet variables at multilevel to find a model equation between inlet and outlet variables, i.e., heat exchanger effectiveness and achieved temperature difference. An induced airflow mode has been used to provide near-uniform flow through all corresponding pipes of symmetrical-shaped earth air heat exchangers. The values of Dry bulb temperature (DBT) and wet bulb temperature (WBT) have been measured for air inlet, for air outlet, as well as for ambient air using resistance temperature detectors (RTD) installed at the requisite locations. Earth's undisturbed temperature (EUT) was also noted by installing RTD at a depth of 2 m, and the average measured value of EUT is found to be 28.5 degrees C. The current system has imparted the temperature difference variation from 0.4 C-o to 9.4 C-o, and the effectiveness varied from 0.16 to 0.82 during the whole season. This system could give a cooling potential of 0.0523 kJ/s to 1.587 kJ/s using a mass flow rate of 0.163 kg/s.Experiments have been designed methodically to apply the full factorial technique. Most favorable parameters have been found for hot and dry and hot and humid weather. The current study is novel in terms of significantly improving the effectiveness of EAHE and addressing the central issue of space limitation in urban areas.
引用
收藏
页码:91 / 100
页数:10
相关论文
共 50 条
  • [1] Experimental study of air conditioning control system for building energy saving
    Nasution, Henry
    Sumeru, K.
    Aziz, Azhar Abdul
    Senawi, Mohd. Yusoff
    INTERNATIONAL CONFERENCE ON APPLIED ENERGY, ICAE2014, 2014, 61 : 63 - 66
  • [2] ON JOINT CONTROL OF HEATING, VENTILATION, AND AIR CONDITIONING AND NATURAL VENTILATION IN A MEETING ROOM FOR ENERGY SAVING
    Xu, Xiaoyan
    Jia, Qing-Shan
    Xu, Zhanbo
    Zhang, Beibei
    Guan, Xiaohong
    ASIAN JOURNAL OF CONTROL, 2016, 18 (05) : 1781 - 1804
  • [3] Energy saving analysis of evaporative cooling composite air conditioning system for data centers
    Han, Zongwei
    Sun, Xiaoqing
    Wei, Haotian
    Ji, Qiang
    Xue, Da
    APPLIED THERMAL ENGINEERING, 2021, 186
  • [4] Experimental Study on Energy Performance of a Split-type Air Conditioning System by Cooling Panel Coupled
    Kietkangsadan, S.
    Jiamrittiwong, P.
    Puangngernmak, N.
    Mangkonkaeo, A.
    2021 INTERNATIONAL CONFERENCE ON SMART CITY AND GREEN ENERGY (ICSCGE 2021), 2021, : 18 - 21
  • [5] Energy Saving Performance of Distributed Heating and Cooling System
    Endo, Naoki
    Maeda, Tetsuhiko
    Hasegawa, Yasuo
    ELECTRICAL ENGINEERING IN JAPAN, 2011, 174 (02) : 46 - 53
  • [6] Research on optimal matching of heating ventilation air conditioning system based on energy saving requirements
    Xu, Dongsheng
    Energy Engineering: Journal of the Association of Energy Engineering, 2020, 117 (03): : 143 - 152
  • [8] Experimental study of a Thermal Radiative Cooling/Heating System for Energy Saving and Power Management
    Murakami, K.
    Mitani, Y.
    Yamada, H.
    Qudaih, Y.
    Miyamoto, N.
    Futaeda, T.
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [9] Research and Application of Controlling System of Fresh Air Antifreezing and Energy-Saving of Heating Air Conditioning in Winter
    Ping, Jiang
    2011 INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SYSTEMS SCIENCE AND ENGINEERING (ICESSE 2011), VOL 1, 2011, : 154 - 157
  • [10] Application of Rheology for Energy Saving Air Conditioning System
    Usui, Hiromoto
    Saeko, Takashi
    NIHON REOROJI GAKKAISHI, 2010, 38 (03) : 141 - 147