Quantitative damping reshaping method based on equivalent RLC circuits using an active damper

被引:3
|
作者
Li, Fei [1 ]
Feng, Qiang [1 ]
Wang, Yichao [1 ]
Wang, Hanyu [1 ]
Ma, Mingyao [1 ]
Zhang, Xing [1 ]
机构
[1] Hefei Univ Technol, Natl & Local Joint Engn Lab Renewable Energy Acce, Hefei, Anhui, Peoples R China
基金
中国国家自然科学基金;
关键词
GRID-CONNECTED INVERTERS; HARMONIC INSTABILITY; IMPEDANCE; STABILITY; DESIGN; SSR;
D O I
10.1049/pel2.12363
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Large scale power electronic converters in renewable energy power system (REPS) constitute a complex multi-scale high-order non-linear network. Harmonic amplitude amplification of specific frequency (e.g. harmonic resonance) often occurs in stable REPS, threatening the normal operation of the system. The impedance reshaping methods based on the stability margin cannot quantitatively assess the risk of harmonic resonance, so that the reshaped system damping may be in a state of under- or over-damped. This paper proposes a harmonic damping concise estimation (HDCE) method based on the one port equivalent RLC impedance model, which quantitatively describes the magnitude of harmonic damping of the system. Aiming at the harmonic damping of the system in an ideal power network, a method of quantitative reshaping of system damping based on HDCE using active damper is proposed, which ensures that the reshaped system is neither under-damped nor over-damped. The harmonic resonance is suppressed effectively while the current stress of the active damper is kept as small as possible. Simulation and experimental results verify the correctness of these analytical and quantitative damping reshaping methods.
引用
收藏
页码:64 / 74
页数:11
相关论文
共 50 条