A study on the control indices and emission limits of substation noise

被引:3
|
作者
Di, Guoqing [1 ]
Jiang, Haojie [1 ]
Chen, Cong [1 ]
Ma, Jiangang [2 ]
Wu, Jian [2 ]
机构
[1] Zhejiang Univ, Coll Environm & Resource Sci, Hangzhou 310058, Peoples R China
[2] State Grid Shaanxi Elect Power Co, Elect Power Res Inst, Xian 710100, Peoples R China
关键词
Substation noise; Control indices; Emission limits; Mean noise annoyance; Low-frequency noise rating number ( LFNR ); LOW-FREQUENCY NOISE; CRITERION;
D O I
10.1016/j.apacoust.2023.109275
中图分类号
O42 [声学];
学科分类号
070206 ; 082403 ;
摘要
Equivalent continuous A-weighted sound pressure level (LAeq) underestimates the influence of low-frequency components of substation noise, so it is necessary to optimise control indices and emission limits of substation noise. To this end, 148 noise samples from 110 kV-1000 kV substations were selected. 280 subjects were randomly recruited for listening tests in which the 11-point numerical scale specified by ISO 15666-2021 was used. The mean noise annoyance (Am) of each noise sample was obtained to establish the LAeq-Am model of substation noise. Meanwhile, the LAeq-LFNR model was estab-lished based on the low-frequency noise rating number (LFNR) proposed by Broner. Based on these mod -els, the LFNR corresponding to the limit of LAeq could be determined. The limit of sound pressure level of substation noise was proposed at each 1/1 octave band from 31.5 Hz to 500 Hz and the limit-exceeding ratio for the existing substations noise of China was analyzed. Results showed that Am of 500 kV-1000 kV substation noise was 1.0 higher than that of 110 kV-220 kV substation noise on average when LAeq was 25 dBA-80 dBA. LAeq of the latter were 6.1 dBA higher than that of the former on average when Am was 1- 10. It was estimated that utmost 20 % of substations need further to take noise control measures in order to meet the limit suggested by this study in China. Binding with the limit of LAeq, the limit of sound pres-sure level at each octave band proposed according to equal noise annoyance can better evaluate the influ-ence of substation noise.(c) 2023 Elsevier Ltd. All rights reserved.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Study on Noise Prediction Model and Control Schemes for Substation
    Chen, Chuanmin
    Gao, Yang
    Liu, Songtao
    SCIENTIFIC WORLD JOURNAL, 2014,
  • [2] Critical indices as limits of control functions
    Yukalov, VI
    Gluzman, S
    PHYSICAL REVIEW LETTERS, 1997, 79 (03) : 333 - 336
  • [3] Discussion on Substation Noise Control Target and Simulation Analysis
    Yang, Bo
    Chen, Libo
    Zou, Anxin
    Xu, Luwen
    2020 2ND INTERNATIONAL CONFERENCE ON CIVIL ENGINEERING, ENVIRONMENT RESOURCES AND ENERGY MATERIALS, 2021, 634
  • [4] Analysis and Control of Noise Reduction and Ventilation for Indoor Substation
    Wu Fayuan
    Cai, Jun
    Ping, Liu
    Ming, Fang
    Zhou Jinquan
    Rui, Xu
    Deng Yongqiang
    2017 INTERNATIONAL CONFERENCE ON SMART GRID AND ELECTRICAL AUTOMATION (ICSGEA), 2017, : 329 - 334
  • [5] Control of the HVAC system noise emission: A case study
    Jeng, MS
    Tsau, FH
    Chen, KC
    Hoo, MD
    PROCEEDINGS OF NOISE-CON 96 - THE 1996 NATIONAL CONFERENCE ON NOISE CONTROL ENGINEERING, VOLS 1 AND 2, 1996, : 539 - 544
  • [6] Interpretation of Harmonic Contribution Indices with respect to Calculated Emission Limits
    Pourarab, Morteza
    Meyer, Jan
    Halpin, Mark
    Iqbal, Zafar
    Djokic, Sasa
    2020 19TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2020,
  • [7] A case study of noise pollution and its control in an Eco-friendly 500 kV substation
    Li, Hualiang
    Li, Li
    Zhang, Kai
    Chen, Min
    Fan, Xiaopeng
    Liu, Yuzhong
    Wu, Peiqi
    Shen, Yali
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 3336 - 3340
  • [8] Design and experimental study of 110kV Substation Transformer active noise control system
    Wang, J. W.
    Ying, L. M.
    Yang, P.
    Jia, Y. T.
    Yang, L.
    Liu, Q.
    Proceedings of the 2016 4th International Conference on Mechanical Materials and Manufacturing Engineering (MMME 2016), 2016, 79 : 751 - 754
  • [9] Design of noise Control Scheme for 500kV Substation
    Hu, Sheng
    Chen, Wei
    Wu, Xiaowen
    Xie, Yine
    Tang, Qi
    Lu, Ling
    2019 5TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING (ICAESEE 2019), 2020, 446
  • [10] Urban 110 kV indoor substation noise analysis and control schemes: A real case study
    Wang, Lv
    Geng, Mingxin
    Bai, Xiaochun
    Ma, Jiangang
    Zhao, Yalin
    Shen, Chen
    Yang, Bin
    APPLIED ACOUSTICS, 2021, 183 (183)