A simplified cooling load calculation method based on equivalent heat transfer coefficient for large space buildings with a stratified air-conditioning system

被引:4
|
作者
Wang, Haidong [1 ]
Zhu, Jieke [1 ,2 ]
Dai, Yuwei [1 ]
Hu, Hao [1 ]
机构
[1] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Shanghai, Peoples R China
[2] Shanghai Installat Engn Grp Co Ltd, Inst Engn Technol, Shanghai, Peoples R China
基金
美国国家科学基金会;
关键词
Large space building; Cooling load calculation; Nominal thermal resistance; CFD simulation; Stratified air-conditioning systems; VERTICAL TEMPERATURE DISTRIBUTION; INDOOR THERMAL ENVIRONMENT; FLOW; PERFORMANCE; VENTILATION; SIMULATION; COMFORT; MODEL;
D O I
10.1016/j.enbuild.2023.113370
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The traditional method for calculating the cooling load of stratified air-conditioning (STRAC) systems is complicated, particularly for interzonal heat transfer (IZHT). This study adopted experimental and computational fluid dynamics (CFD) methods to analyze the IZHT at two model scales and proposed a novel cooling load calculation method for STRAC systems. This new method, which is based on the equivalent heat transfer coefficient K-c, is called the interzonal thermal resistance method. According to the CFD simulation results of the fullscale model, the equivalent heat transfer coefficient K-c of the occupied and unoccupied zones ranged from 42.66 to 44.36 W/(m(2.degrees)C) under the nozzle sidewall air supply (NSWAS) system. Based on the magnitude of the coefficient, the difference between the cooling load calculated by the newly developed and traditional methods was only 4.16%, which proves the reliability of the interzonal thermal resistance method. Moreover, compared to the traditional method, the new method is more convenient. This method provides an alternative for calculating the cooling load of STRAC systems in practical engineering applications with a solid theoretical foundation.
引用
收藏
页数:9
相关论文
共 38 条
  • [31] Investigation of vertical thermal stratification and stratified air conditioning load for large space with low-sidewall supply air based on vertical temperature node model
    Lv, Liugen
    Wang, Xin
    Zhang, Qianru
    Xiang, Yi
    Wu, Xiaoyan
    Huang, Chen
    JOURNAL OF BUILDING ENGINEERING, 2023, 69
  • [32] A Flexible Quantification Method for Buildings' Air Conditioning Based on the Light and Heat Transfer Coefficients: A Case Study of a Shanghai Office Building
    Yu, Dan
    Xu, Tingting
    Jiang, Yunxia
    Li, Qin
    Qian, Fanyue
    ENERGIES, 2025, 18 (06)
  • [34] The collocation method of supplementary heat source of air-source heat pump system for space heating based on the MEBPT calculation
    Wu, Zhenjing
    Zhang, Huan
    You, Shijun
    Zheng, Wandong
    Guo, Jin
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 1427 - 1433
  • [35] Proposal of control parameter designing method and actual machine test of short term power fluctuation compensation system by use of heat pump air-conditioning system as controllable load
    Graduate School of Engineering, JSPS Research Fellow, University of Tokyo, 7-3-1, Hongo, Bunkyo-ku, Tokyo
    113-8656, Japan
    不详
    277-8568, Japan
    不详
    135-8530, Japan
    IEEJ Trans. Power Energy, 1 (42-49):
  • [36] Multi-agent-system Based Air-conditioning Load Aggregation Method and Its Shedding by Voltage Reduction and Temperature Adjustment of Active Distribution Network
    Zhou Q.
    Ma R.
    Wang T.
    Lu P.
    Feng C.
    Wu W.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (18): : 6668 - 6680
  • [37] Accuracy verification of simplified calculation method for moisture sorption with external wall performance test house: Simplified numerical model of moisture transfer on interior surfaces for transient room temperature and heat load calculation of multiple zone buildings part 2
    Hosokawa, Takayuki
    Hayashi, Tetsuo
    Yoshimura, Junichi
    Journal of Environmental Engineering, 2008, 73 (633) : 1291 - 1297
  • [38] Verification based on measurements and unsteady CFD analysis that low calculation load for 8 years: Pre-cooling / heating characteristics of the earth-to-air heat exchanger system in long-term operation (Part1)
    Muta A.
    Shiraishi Y.
    Tomoda K.
    Journal of Environmental Engineering (Japan), 2018, 83 (750): : 711 - 718